PREMIER SX INSTALLATION MANUAL.
Approved Document No: GLT.MAN-101
PAGE 15
Issue : 1.95 Authorised: GH Date: 09/06/2004
11. PCB TERMINATION CONNECTIONS.
FS2
BATTERY
1.6A
FS4
SND1
400mA
FS3
En54 SUP
1.6A
FS1
CHARGER
1.6A
FS5
SND2
400mA
LIVE NEUT- EARTH
RAL
MAINS TO TRANSFORMER PRIMARY
MAI
N
S F
USE
2A
HB
C CE
RA
M
IC
CONN5
CONN 27
1 2 3 4 5 6 7 8 9
11.1 CONNECTIONS
Connection No Description
Use
1
ZONE 1 +&-
Connect to Zone 1
2
ZONE 2 +&-
Connect to Zone 2
3
ZONE 3 +&-
Connect to Zone 3
4
ZONE 4 +&-
Connect to Zone 4
5
ZONE 5 +&-
Connect to Zone 5
6
ZONE 6 +&-
Connect to Zone 6
7
ZONE 7 +&-
Connect to Zone 7
8
ZONE 8 +&-
Connect to Zone 8
9
SND 1 +&-
Connect to sounder circuit 1 (sirens/bells)
10
SND 2 +&-
Connect to sounder circuit 2 (sirens/bells)
11
CLASS CHANGE
Join terminals to activate sounders
12
FIRE RELAY NO/CM/NC
Activates on fire (including test mode)
13
FAULT RELAY NO/CM/NC
Normally powered ie NO is closed with no fault
14
B & -
Connect 2 x 12V SLA batteries in SERIES (ie 24V)
15
AC AC
Connected to transformer secondary (30VAC)
16
EN54 supply - & +
NOT CONNECTED IN STAND ALONE PANEL.
17
CONN 1
20 way ribbon cable to display PCB
18
CONN 27
EARTH connection to display PCB & SCREEN TAG
19
CONN 26
Filtered mains to transformer
20
CONN 5
MAINS TERMINAL BLOCK
11.2 FUSES
FUSE NO
DESCRIPTION
RATING
FS1
Charger Fuse
1.6A time delay 5 x 20mm glass
FS2
Battery Fuse
1.6A time delay 5 x 20mm glass
FS3
EN54 SUPPLY (NOT USED)
1.6A time delay 5 x 20mm glass
FS4
Sounder circuit 1
400mA time delay 5 x 20mm glass
FS5
Sounder circuit 2
400mA time delay 5 x 20mm glass
INLET FUSE
Mains Protection Fuse
2A Quick Blow HBC 5 x 20mm ceramic
Summary of Contents for NPSX1