Zeta Alarm Systems.
Classic 2000 Mk II Operation Manual
Revision 1.0
Part # MAN-Z3K-01
Page 86
Appendix B:
Classic 2000 Mk II Battery Backup Calculation
SYSTEM COMPONENTS
Quantity
Stand-By
Current
(mA)
Maximum
Alarm
Current
(mA)
Total
Stand-By
Current
(mA)
Total
Alarm
Current
3000-6400 System Board (CP3, LPD, PSC, 1 ZACM)
0
155
165
0
0
3000-6855 Addressable Communication Module (ZACM)
0
30
30
0
0
2918 Zone Relay Module (ZZRM)
0
1
75
0
0
SERIAL DEVICES
3000-6825 City Box Module (ZCBM)
0
45
60
0
0
2996 Networked Digital Communicator (ZNDC)
0
56
76
0
0
3000-6807 Remote Display Annunciator (ZRDA)
0
45
60
0
0
4010 Remote Annunciator (ZRAN)
0
40
420
0
0
4025 Remote Annunciator Expander (ZRAN-EX)
0
0
420
0
0
4035 Remote LED Driver (ZRLD)
0
40
420
0
0
4040 Remote LED Driver Expander (ZRLD-EX)
0
0
420
0
0
3000-6860 Remote Power Converter (ZRPC)
1
0
50
50
0
0
2936 Ten Zone Class B (ZTZB)
0
65
515
0
0
2941 Five Zone Class A (ZFZA)
0
90
270
0
0
DETECTORS / MODULES
55000-550 ISH-550 Ion Sensor Head
0
.28
2
0
0
55000-650 PSH-650 Photoelectric Sensor Head
0
.34
4
0
0
55000-450 TSH-450 Temperature Sensor Head
0
.25
4
0
0
55000-750 IMB-750 Isolator Module
0
.12
8
0
0
55000-830 MPM-830 Mini Priority Switch Monitor Module
0
.6
4
0
0
55000-806 PMM-806 Priority Switch Monitor Module
0
.6
4
0
0
55000-820 SMIO-820 Switch Monitor Input-Output Module
0
.85
4
0
0
55000-825 SCM-825 Sounder Control Module
0
1
4
0
0
Number of SLC Loops in System
2
0
0
.80
0
0
NOTIFICATION APPLIANCES
Other - NAC #1, 2.75 Amps Maximum
0
0
0
0
0
GMS24 - 15/75WR
0
0
139
0
0
GEC24 - 15/75WR
0
0
142
0
0
Other - NAC #2, 2.75 Amps Maximum
0
0
0
0
0
GMS24-15/75WR
0
0
139
0
0
GEC24-15/75WR
0
0
142
0
0
Other - NAC #3, 2.75 Amps Maximum
0
0
0
0
0
GMS24-15/75WR
0
0
139
0
0
GEC24-15/75WR
0
0
142
0
0