Zeta Alarm Systems.
Classic 2000 Mk II Operation Manual
Revision 1.0
Part # MAN-Z3K-01
Page 54
4.2.2.2 Timing
The Timing menu allows you to establish AC Power Fail reporting delays, Auto-Silence of Alarm
and Trouble Time, Silence Inhibit Time, and Alarm Verification times. In addition, this menu allows
for individual system programming for Holidays, Day/Night Schedules, and On/Off Schedules.
Menu Option 1 – AC Low Delay: XXh - To select AC power fail time for UL Central Station or
Remote Station Operation (AC Low Delay), use key 1 to choose between a 0, 8, or 16 hour delay
for reporting the AC Low/Fail trouble condition to the monitoring service. Other panel troubles will
be reported immediately.
Menu Option 2 – Auto Silence: XXm - The Auto Silence mechanism can be set by pressing 2
and toggling between 0, 15, and 30 minutes. This will automatically silence alarm and trouble
alerts after the specified time.
Menu Option 3 – Silence Inh: XXs - To provide a silence inhibit period, Silence Inh is selected by
pressing 3 to toggle between 0, 30, 60, 90, 120, 180, 240, and 300 seconds. This selection will
prevent silencing of all enabled NAC or sounder outputs for the specified time.
Menu Option 4 – Alarm Verify: XXs - Program the alarm verification time ( Alarm Verify) by
pressing key 4 and entering any amount of time from 0 to 60 seconds. This sets a period of time in
which the panel can confirm an alarm condition on inputs that have been selected for Alarm Verifi-
cation before reporting an alarm. Alarm verification is only available for photoelectric and ion-
ization sensors. Only use compatible sensors listed in Appendix C. Alarm verification may
not be used with devices having their own alarm verification capabilities.
Menu Option 5 – Holidays - Program up to 18 annual holidays to work in conjunction with day/
night sensitivity schedules. Select 1 to specify the first holiday. Enter the month, then press ENTER
to move to the day of the month. Enter the day of the month, then press ENTER to complete the
first holiday. Press ESCAPE to back up to the previous field should you need to make a correction.
Menu Option 6 – Schedules - On/Off Schedules and Day/Night Sensitivity Schedules. To select a
schedule to program, press 1 - 4 to select a Day/Night schedule and 5 - 8 to select an On/Off
Schedule. Simply enter the values as prompted by the screens.