Zeta Alarm Systems.
Classic 2000 Mk II Operation Manual
Revision 1.0
Part # MAN-Z3K-01
Page 93
5. On/Off Sch #1
1. On: Off:
Default On: 00/00
2. On: Off:
Default Off: 00/00
3. On: Off:
6. On/Off Sch #2
…same as #1…
7. On/off Sch #3
…same as #1…
8. On/Off Sch #4
…same as #1…
3. Access Codes
Default = 111111 for level 1
Default = 222222 for level 2
4. Edit Banner Msg
Default =
Zeta Alarm Systems Class 2000 Mk II
3. Network
1. Scan
2. Browse Devices
3. Style
Default = 4 (Class B)
4. Inputs
1. Options
1. Test Time
In 24-hour mode 00:00
2. LED Blink
Default = Yes (LED Blink enabled)
2. Sensitivity Levels
1. Ion Sensitivity
1. Low
Default = 67
2. Medium
Default = 60
3. High
Default = 56
2. Photo Sensitivity
1. Low
Default = 62
2. Medium
Default = 55
3. High
Default = 48
3. Heat Setting
1. Low
Default = 090
2. Medium
Default = 071
3. High
Default = 055
3. Alerts
1. Ion Alerts
Maintenance:
Default = 35
Menu Description
Default Setting
Access
Level
Required
Summary of Contents for Classic 2000 MKII