Zeta Alarm Systems.
Classic 2000 Mk II Operation Manual
Revision 1.0
Part # MAN-Z3K-01
Page 80
6.4.7 ZPNI DIP Switch Configuration
The ZPNI may be addressed to one of 32 network addresses. Use the DIP switch on the board to
set the address.
*Global Silence and Reset apply only to the ZPNI-DRV. See ZPNI product documentaion for explanation
and application.
6.5 Serial Device Technical Specifications
6.5.1 ZTZB/ZFZA Specifications
Bit
Number
Description
0
Network Address Bit 0
1
Network Address Bit 1
2
Network Address Bit 2
3
Network Address Bit 3
4
Network Address Bit 4
5
6
Global Silence*
7
Global Reset*
POWER REQUIREMENT
To be connected to a UL listed Power Limited
Class II or Class III source of supply only
Input Voltage
Minimum
22VDC
Nominal
24VDC
Maximum
25.5VDC
Normal Mode (Standby)
ZTZB
65mA
ZZRM
1.5mA
10% Alarm Condition
ZTZB (1 zone)
110mA
ZZRM (1 zone)
18mA
Each zone in alarm adds …
45mA
Each ZZRM relay on adds …
16mA
Summary of Contents for Classic 2000 MKII