ZoningBOX 6 / ZoningBOX 4
Technical Support:
5
1.2
INSTALLATION
ZoningBOX connects to the KNX bus through the on-board KNX connector. Once the
device is provided with power from the KNX bus, both the individual address and the
associated application program may be downloaded.
The main elements of the device are described next.
Prog./Test Pushbutton (7)
: a short press on this button sets the device into
the programming mode, making the associated LED (3) light in red.
Note
: if this button is held while plugging the device into the KNX bus, the
device will enter into
safe mode
. In such case, the LED will blink in red every
0.5 seconds.
Output channels (5)
: output ports for the insertion of the stripped cables of
the grilles being controlled by the actuator. Please secure the connection by
means of the on-board screws.
Phase and neutral inputs
(1)
: ports for the connection of the voltage cables
(phase and neutral) that will power the grilles during operation.
Voltage selector 12V / 24V (6)
: switch for the selection of the grille type (12V
or 24V).
3
4
6
9
7
1
5
2
5
8
1.
230V power input.
2.
Power indicator LED.
3.
Grille control pushbutton.
4.
Grille status LED indicator.
5.
Grille output channels.
6.
12/24V switch.
7.
Prog./Test pushbutton.
8.
Prog./Test LED.
9.
KNX Connection.
Figure 2.
Element diagram (ZoningBOX 6)