ZoningBOX 6 / ZoningBOX 4
Technical Support:
33
A
closing time
for the connected grille (
positional mode
exclusive).
An
additional time
, to
force
further motion once the end-of-stroke position
has been reached.
The
initial position
, which will be adopted by the grille after a bus power
failure or at the end of an ETS download.
The
Advance Current Control.
If it is enabled, it will be possible to set which
current increment over the nominal value determines the grill movement end.
Important: Its use is not recommended except for exceptional cases where
advanced control of the ZoningBOX is necessary
.
ETS PARAMETERISATION
Once a specific grille has been enabled (see section 2.3.1), the following options will be
available:
Figure 25.
Grilles - Grille
“y”
Opening Time
[
0…
20
…255 s
]: determines the time it takes for the connected
grille to open (
positional mode
exclusive).
Closing Time
[
0…
20
…255 s
]: determines the time it takes for the connected
grille to close (
positional mode
exclusive).
Additional Time
[
0
…
2
…255
]:
sets an extra time to extend the motion of the
grille once the end-of-stroke position has been detected. The available range
is 0 to 255 tenths of a second.