[Group n] [Gi] [Control] Grille Status
”: one-bit or
1-Byte
object for
receiving the feedback of the grille status. This is typically to be grouped
with the analogous object in the Grilles module (see section 2.3).
Control Type in Heat Mode
[
HVAC Control
/ Grille
Control / Adjust Setpoint
]:
defines the behaviour of the system when there is only one open grille left
under heat mode.
Control Type in Cool Mode
[
HVAC Control / Grille
Control /
Adjust
Setpoint
]:
defines the behaviour of the system when there is only one open grille left
under cool mode.
The
option “Adjust Setpoint
”
entails configuring an additional parameter:
➢
Setpoint Decrement/Increment
[
1…
2
…5ºC
]: sets the increment (in the
cooling mode) or the decrement (in the heating mode), between 1º and
5º, that should be applied over the setpoint.
Figure 8
. Zoning - Behaviour with only one grille open
Enable Bypass in Group
“n”
[
disabled
/enabled
]: enables/disables the
possibility of controlling the valve of a bypass.
➢
Open if nº of Open Grilles is Less than or Equal to
[
1
...m
] (m = number
of grilles configured in group n): sets how many grilles, at least, must
remain open so the bypass is not forced to be open as well.
Figure 9
. Zoning
– Bypass