ALLinBOX 1612 v2 / 88 / 46 / Hospitality
Technical Support:
40
441
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Heating Valve: Anti-Seize
Protection (Status)
0 = Not Active; 1 = Active
442
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[FCx] Valve (Status)
0 - 100%
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[FCx] Cooling Valve (Status)
0 - 100%
443
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[FCx] Heating Valve (Status)
0 - 100%
444
1 Bit
O
C R - T -
DPT_Bool
0/1
[FCx] Control Value - Error
0 = No Error; 1 = Error
445
2 Bytes
I
C - W - U
DPT_Value_Temp
-273.00º - 670433.28º
[FCx] Ambient Temperature
Ambient Temperature
446
2 Bytes
I
C - W - U
DPT_Value_Temp
-273.00º - 670433.28º
[FCx] Setpoint Temperature
Setpoint Temperature
447
2 Bytes
I/O
C R W T U
DPT_TimePeriodMin
0 - 65535
[FCx] Duration of Manual Control
0 = Endless; 1 - 1440 min
2 Bytes
I/O
C R W T U
DPT_TimePeriodHrs
0 - 65535
[FCx] Duration of Manual Control
0 = Endless; 1 - 24 h
513, 519, 525, 531, 537, 543
1 Bit
I
C - W - -
DPT_Enable
0/1
[Ix] Input Lock
0 = Unlock; 1 = Lock
514, 520, 526, 532, 538, 544
1 Bit
C - - T -
DPT_Switch
0/1
[Ix] [Short Press] 0
Sending of 0
1 Bit
C - - T -
DPT_Switch
0/1
[Ix] [Short Press] 1
Sending of 1
1 Bit
I
C - W T -
DPT_Switch
0/1
[Ix] [Short Press] 0/1 Switching
Switching 0/1
1 Bit
C - - T -
DPT_UpDown
0/1
[Ix] [Short Press] Move Up
Shutter
Sending of 0 (Up)
1 Bit
C - - T -
DPT_UpDown
0/1
[Ix] [Short Press] Move Down
Shutter
Sending of 1 (Down)
1 Bit
C - - T -
DPT_UpDown
0/1
[Ix] [Short Press] Move Up/Down
Shutter
Switching 0/1 (Up/Down)
1 Bit
C - - T -
DPT_Step
0/1
[Ix] [Short Press] Stop/Step Up
Shutter
Sending of 0 (Stop/Step Up)
1 Bit
C - - T -
DPT_Step
0/1
[Ix] [Short Press] Stop/Step Down
Shutter
Sending of 1 (Stop/Step Down)
1 Bit
C - - T -
DPT_Step
0/1
[Ix] [Short Press] Stop/Step
Shutter (Switched)
Switching of 0/1 (Stop/Step
Up/Down)
4 Bit
C - - T -
DPT_Control_Dimming
0x0 (Stop)
0x1 (Dec. by 100%)
...
0x7 (Dec. by 1%)
0x8 (Stop)
0xD (Inc. by 100%)
...
0xF (Inc. by 1%)
[Ix] [Short Press] Brighter
Increase Brightness
4 Bit
C - - T -
DPT_Control_Dimming
0x0 (Stop)
0x1 (Dec. by 100%)
...
0x7 (Dec. by 1%)
0x8 (Stop)
0xD (Inc. by 100%)
[Ix] [Short Press] Darker
Decrease Brightness