Manual of 07/06/2019 Rev. 1.1 “User Manual for 20K-33KTL”
4.1.
Electrical connections
Figure 17 – Steps for connecting the cables
4.2.
Connecting PNGD cables (grounding)
Connect the 20K-33K TL inverter to the ground electrode using ground protection cables (PGND).
The inverter does not have a transformer, therefore the positive pole and
negative pole of the photovoltaic string does NOT need to be grounded.
Otherwise, the inverter may fail. All non-current-carrying metal parts (such as
the PV module frame, PV rack, housing of the combiner box, and housing of the
inverter) in the PV power system must be connected to the ground.
Attention
Note:
Connect the PGND cable before connecting the AC, DC power and communication cables.
For systems with one inverter, connect the PGND cable to the ground. For systems with multiple inverters,
connect the PGND cables of each inverter to the ground electrode using equipotential connections.
If the installation place is near the ground, connect the PGND cable to the ground before installing the
inverter on the wall.
Figure 18 – Connecting the ground terminal