Troubleshooting and maintenance
7.1.
Troubleshooting
This section contains information and procedures on how to troubleshoot any faults and errors that may
occur during operation of the 3PH 20000TL - 33000TL-V2 inverter.
If you have any problems with the inverter, please follow these steps.
Check the warning messages and error codes on the information panel of the inverter. Record them
before carrying out any further operation.
If the inverter does not display any errors, perform the following checks:
-
Is the inverter located in a clean, dry and properly ventilated place?
-
Is the DC switch closed?
-
Are the cables correctly sized and as short as possible?
-
Are the input/output connections and the cables in good condition?
-
Are the configuration settings correct for the type of installation?
-
Are the display panel and flat communication cable correctly connected and not damaged?
Follow the steps below to display the recorded alarms:
Press “Menu/Back” to enter the main menu from the standard interface. Select “Event List” in the menu
screen, then press “OK” to access the list of alarms and errors.
Information on event list
Error
code
Error name
Error description
Possible solution
ID01
GridOVP
The grid voltage is too
high.
If the alarm occurs occasionally, the
probable cause is that the electric grid
is in an abnormal state.
The inverter will automatically return
to its normal operating state when the
electrical grid is restored to its
normal state.
If the alarm occurs frequently, check
whether the grid voltage/frequency is
within the correct range. If not,
contact technical support. If so, check
ID02
GridUVP
The grid voltage is too
low.
ID03
GridOFP
The grid frequency is
too high.