56 / 136
Identification: MD-AL-GI-00
Rev. 1.1 of 15/03/2021 - Application: GID
User’s Manual 3PH 20000TL - 33000TL-V2
Rev. 1.1 15/03/2021
06
Greece - mainland
18
EUEN50438
30
Slovakia SSE
07
Netherlands
19
IEC EN61727
31
Slovakia ZSD
08
Belgium
20
Korea
32
CEI 0-21 Areti
09
UK-G59
21
Sweden
33-49
Reserved
10
China
22
General Europe
11
France
23
CEI 0-21 External
Table 3 – Country Codes
Contr On-Off
Select “5. Contr On-Off” and press “OK” to enter the menu for setting the remote control switch. The display
will show “Enter PWD!” Press “OK” to enter the password “0001” using the “Up” and “Down” keys to select
the number and “OK” to move to the next digit. If the display shows “Incorrect, try again!” press the “Back”
key and enter the password again. When the password has been entered correctly, you can enter the menu.
Use the “Up” and “Down” keys to select the “1.Enable” or “2.Disable” option and select it with the “OK” key. If
the “Enable” option is selected, you will then need to indicate how many days you want to keep the inverter
switched off using the Up and Down keys, and confirming with OK. After setting the “Enable” option, contact
the installer to obtain the password for restarting the inverter.
Relay command
Select “6. Relay Command” and press “OK” to enter the menu for setting the relay command. Use the “Up”
and “Down” keys to select the respective configuration items, as shown below. Press “OK” to select them. If
the setting is successful, “OK” will be displayed; otherwise, “Error” will be displayed.
6. Relay command
1. Production
2. Alarm
3. ConfigAlarm
4. Disab Relay
Below is a detailed definition of the configurations that can be set: