background image

30

440 01 2020 01

6. Electrical Wiring

Electrical shock hazard.
Turn OFF electrical power at fuse box or service

panel before making any electrical connections

and ensure a proper ground connection is made

before connecting line voltage.
Failure to do so can result in death, personal injury

and/or property damage.

!

Power Supply Wiring

The furnace

MUST

be electrically wired and grounded in accor-

dance with local codes, or in the absence of local codes with the

latest edition of The National Electric Code, ANSI NFPA 70 and/or

The Canadian Electric Code CSA C22.1.
Field wiring connections must be made inside the furnace connec-

tion box. A suitable strain relief should be used at the point the

wires exit the furnace casing.

Copper conductors must be used

. Line voltage wires should be

sized for the input amps stated on the rating plate. Furnace should

be connected to its own separate circuit.

Thermostat

The 2--stage furnace control will operate with either a single stage

or a two stage heating thermostat and will provide 2--stage heating

operation. For single stage thermostat installations, the

R

and

W

wires from the thermostat connect to the

R

and

W1

connections on

the furnace control.

Note:

The fourth (4th) DIP switch must be in

the off position, failure to change DIP switch will result in Lo Fire

ONLY operation. (See furnace wiring digram) See “

Furnace Wiring

Diagram

” for switch settings. Failure to set DIP switch will result in

Lo fire operation ONLY with single stage thermostat. During opera-

tion, the furnace will operate on low fire for 12 minutesIf the heat

request exists for more than 12 minutes. If the heat request exists

for more that 12 minutes, the furnace will automatically shift to the

high fire mode for the remaining duration of the heating cycle. For

two stage thermostat installations, the

R, W1

and

W2

wires from

the thermostat connect to the

R, W1

and

W2

connections on the

furnace control. During operation, the furnace will shift from low fire

to high fire as requested by the thermostat. The thermostat heat

anticipators should be adjusted to a .10 setting for both types of

thermostats.
Low voltage connections to furnace must be made on terminal

board to fan control.

Optional Equipment

All wiring from furnace to optional equipment

MUST

conform to lo-

cal codes or, in the absence of local codes with the latest edition of

The National Electric Code, ANSI NFPA 70 and/or The Canadian

Electric Code CSA C22.1. Install wiring in accordance with

manufacturer’s instructions. The wiring

MUST

have a minimum

temperature rating of 105

°

C. codes or, in the absence of local

codes, the applicable national codes. Install wiring in accordance

with manufacturer’s instructions.

Humidifier/Electronic Air Cleaner

The furnace is wired for humidifier and/or electronic air cleaner

connection.

CAUTION

Do NOT exceed 115V/0.8 amp. maximum current load for both

the EAC terminal and the HUM terminal combined.
NOTE:

The humidifier will be powered when the furnace is fired

and the circulating air blower comes on. The electronic air cleaner

will be powered anytime the air circulating blower is energized.

However, the electronic air cleaner is

NOT

energized during con-

tinuous fan operation controlled by the electronic fan control.

Fan Control

The fan control is preset at the factory with a fixed blower

ON

delay

of 30 seconds in the heating mode. The blower

OFF

timing is pre-

set at 140 seconds. If desired, the fan

OFF

delay can be reset to

obtain the longest delay times while still maintaining comfort levels.

See “Furnace Wiring Diagram” .

W2

Figure 31

Electrical Connections

NOTE: Junction Box can be mounted to either the left or right side.

25--23--42a

W2

W2

NOTE: 115 VAC/60Hz/single--phase

Operating voltage range*: 127 max, 104 min.

* Permissible limits of voltage at which unit will operate satisfactorily

Dehumidification -- Variable Speed ONLY (*9MPV)

The fan control is wired for 24 VAC normally open (N/O) dehumidis-

tat connection. Connect dehumidistat to the

R

terminal and the

1

/

4

²

male quick connect Y2 terminal on the fan control (See

Figure 32

and “Furnace Wiring Diagram”). A 20% reduction of cooling airflow

will occur when the Y2 dehumidistat terminal is energized during a

call for cooling from the thermostat.

Control Center Fuse

The 24V circuit contains a 5--amp, automotive--type fuse located

on fan timer board. (See

Figure 32

) Any electrical shorts of 24V

wiring during installation, service, or maintenance may cause fuse

to blow. If fuse replacement is required, use only a fuse of identical

size (5 amp.)

Summary of Contents for 9MPT050F12A

Page 1: ...l should install repair or service heating equipment Untrained service personnel can perform basic maintenance functions such as cleaning and replacing air filters All other operations must be perform...

Page 2: ...ly Return F or C Lo Fire Supply Return F or C Filter Type and Size Fan Time ON Setting Fan Time OFF Setting Manual Gas Shut Off Upstream of Furnace Drip Leg YES NO Condensate Drain Connected YES NO Co...

Page 3: ...rn air ducts Install correct filter type and size Unit MUST be installed so electrical components are pro tected from direct contact with water Safety Rules Yourunitis builtto provide many years of sa...

Page 4: ...me your furnace will be ready to start as it is not necessary to drain the antifreeze from the furnace 2 Installation CARBON MONOXIDE POISONING HAZARD Failure toproperly ventthis furnace orother appli...

Page 5: ...pflow horizontal either left or right or downflow airflow position DO NOT install this furnace on its back For the upflow position the return air ductwork can be at tached to either the left or right...

Page 6: ...11 16 111 16 175 16 215 8 21 4 131 4 24 47 8 215 8 17 8 297 8 273 16 913 16 3311 16 6 440 01 2020 01 Cabinet to Combustible Clearances TOP BOT RH LH BACK FRONT FLUE 1 0 0 0 0 3 0 U it Cabinet Bottom...

Page 7: ...entdam age by overflow due to blocked condensate drain 3 Combustion Ventilation Air For Single Pipe Installation CARBON MONOXIDE POISONING HAZARD Failure to provide adequate combustion and ventilation...

Page 8: ...e theequipmenthasclearances of at least 1 from the sides and back and 6 from the front of the appliance The opening shall directly communicate with the out doors or shall communicate through a vertica...

Page 9: ...DE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system beingplaced into operation while all other appliances connected to the venting system...

Page 10: ...isture in the flue gases that may condense as it leaves the vent pipe See Special Instruction For Horizontal Vents 5 The vertical vent pipe MUST be supported so that no weight is allowed to rest on th...

Page 11: ...VC pipe or 100 000 Btuh Furnace 40 5 90 elbows with 3 PVC pipe 125 000 Btuh Furnace 40 5 90 elbows with 3 PVC pipe Elbows are DWV Long Radius Type for 2 and 3 vents If more than five elbows are requir...

Page 12: ...des The drain line must maintain a 1 4 per footdownward slope toward the drain 1 4 per foot is recommended Installation of an overflow line is recommended when the 1 4 per foot slope to the conden sat...

Page 13: ...it Install casing grommet black rubber 5 8 ID grommet in loose parts bag Install the 1 2 CPVC street elbow on discharge of Trap Install the black PVC tube connector 3 4 PVC x 1 2 CPVC from loose parts...

Page 14: ...ommet in side of casing Cut an appropriate length of 2 PVC pipe long enough to exit the cabinet and connect the vent drain to either A 2 PVC coupling fastened onto the Drain Tee 9MPT or V models Insta...

Page 15: ...to the Trap Secure all connections with clamps Install the vent pipe grommet into the casing Cut an appropriate length of 2 PVC pipe long enough to exit the cabinet and connect the vent drain to eith...

Page 16: ...e unit using the 2 screws provided Cut the 5 8 ID corrugated hose as shown above and fasten the 90 bend end to the Trap and fasten the straight end to the transition drain Secure both connections with...

Page 17: ...ap and mount the Trap externally to the right side of the unit using the 2 screws provided Connect the corrugated Drain Tube from the transition box to the Trap as shown If an extension is required us...

Page 18: ...tration above Con nect the corrugated hose from the transition to the Trap Secure connections with clamps Remove the black 1 2 ID Drain Tube from the Drain Tee Install a yellow cap and clamp over the...

Page 19: ...he illustration above Con nect the corrugated hose from the transition to the Trap Secure connections with clamps Connect the black 1 2 ID Drain Tube from the Vent Drain to the Trap If an extension is...

Page 20: ...as shown in the illustration above Con nect the corrugated hose from the transition to the Trap Secure connections with clamps Connect the black 1 2 ID Drain Tube from the Vent Drain to the Trap If a...

Page 21: ...rrugated hose from the transition to the Trap Secure connections with clamps Connect the black 1 2 ID Drain Tube from the Vent Drain to the Trap If an extension is required use the 1 2 OD barbed coupl...

Page 22: ...flue gases from the condensate drain line and open tee for a period of time and may result in temporary lockout of the furnace upon start up Main drain line construction is left to the discretion of...

Page 23: ...ts and avoid contact with skin or eyes This furnaceis approvedforventingwith Schedule40 PVC CPVC ABS Cellular Core pipe fittings and SDR 26 PVC NOTE All PVC CPVC ABS and Cellular Core pipe fittings so...

Page 24: ...l to restrain pipe from moving 3 Insulate pipe with Armaflex or equivalent moisture resistant closed cell foam insulation or Fiberglass insulation if boxed in and sealed against moisture 8 MIN 20 MAX...

Page 25: ...t Vent and Exhaust Air Ter mination Dimension A is touching or 2 maximum separation 12 Min Grade or Snow Level 18 Min for Cold Climates Sustained Below 0 F 8 Min 20 Max 8 Min Exhaust 8 Min 8 Min 20 Ma...

Page 26: ...Gas input to burners MUST NOT exceed the rated input shown on rating plate 3 Do NOT allow minimum gas supply pressure to vary down ward Doing so will decrease input to furnace Refer to Table 5 for nor...

Page 27: ...The derating of these units at 2 Natural and 4 L P has been tested and approved by CSA MANIFOLD PRESSURE AND ORIFICE SIZE FOR HIGH ALTITUDE APPLICATIONS Table 6 High Altitude Pressure Chart 2000 8000...

Page 28: ...sed on a natural gas BTU content of 1 000 BTU s per cubic meter Check with gas supplier for actual BTU content 1 Turn OFFgas supplyto allappliances andstartfurnace Use jumper wire on R to W1 and W2 fo...

Page 29: ...eel pipe and fittings or other pipe ap proved by local code 5 Use ground joint unions and install a drip leg no less than 3 long to trap dirt and moisture before it can enter gas valve 6 Use two pipe...

Page 30: ...nace must be made on terminal board to fan control Optional Equipment All wiring from furnace to optional equipment MUST conform to lo cal codes or in the absence of local codes with the latest editio...

Page 31: ...death personal injury and or property damage Cool air passing over heat exchanger can cause condensate to form resulting in heat exchanger failure Connections NOTE On upflow installations return air...

Page 32: ...lter to clear the front raised edge of the furnace Insert filter into side clips first and push filter back until it is fully engaged into back clip When filter is in place slide clips back into place...

Page 33: ...dimensions listed in Table 7 since the base is equipped with locating tabs that center the base over the opening The opening in the base is 11 4 shorterand 11 8 narrower than the recommended size of t...

Page 34: ...power to furnace Check for wiring errors or obstruction to blower Failure to correct hazard could result in death personal injury and or property damage CAUTION Gas Supply Pressure Gas supply pressur...

Page 35: ...fter the adjustments are com plete Return fourth 4th to previous setting Changing Blower Speed 9MPT Models ELECTRICAL SHOCK HAZARD Failure to do so can result in death and or personal injury Turn OFF...

Page 36: ...jury and or property damage Turn OFF power to furnace before changing speed taps NOTE The blowerspeeds thatthe manufacturersetsfromthefac tory for this product are based on a nominal 400 CFM per ton c...

Page 37: ...p period on a call for Heating that occurs during a G request NOTE3 Heating or Cooling requests received during a Fan request cause the fan speed to change to the appropriate heat or cool speed after...

Page 38: ...Low Pressure switch circuit was still sensed as open 30 seconds after the inducer was energized System is in 5 minute delay mode with inducer off After 5 minute delay a new ignition sequence will be...

Page 39: ...alve Honeywell Figure 44 INLET OUTLET Diagnostic Light on some models 25 22 25a On Off Switch Pilot Adjustment Manifold Adjustment Hidden Manifold Pressure Adjustment INLET OUTLET 25 22 49a LO HI 39 4...

Page 40: ...TO OPEN 1 Ignitor turns OFF about 30 seconds into the trial for ignition If the pilot flame has not lit it turns back ON for the final 30 seconds of the 90 second trial for ignition The pilot valve is...

Page 41: ...speed Main limit switch Manual reset burner rollout switch Limit and rollout switch wiring is in good condition and securely connected 5 Flashes Flame signal sensed out of proper sequence Combustion b...

Page 42: ...ate a new ignition sequence Main limit switch Limit and rollout switch wiring is in good condition and securely connected Restriction in duct work Dirty filter 7 Flashes Soft Lockout Blower failure ty...

Page 43: ...and the exhaust vent pipes must attach to the termination kit The termination kit must terminate outside the structure and must be installed per the instructions outlined below for vertical or horizon...

Page 44: ...nt the parts using the procedures for Joining Pipe and Fittingssection ofthe manual A Cementthe YConcen tric fitting to the 4 diameter kit pipe See Figure 48 B Ce ment the 3 rain cap to the 21 2 diame...

Page 45: ...be field installed to prevent movement of ter mination kit in side wall Figure 50 8 Install the rain cap and the small diameter pipe assembly in the Y concentric fitting and the large pipe assembly En...

Page 46: ...46 440 01 2020 01...

Page 47: ...9MPT100J16B1 9MPT125L20B1 9MPV050F12B1 9MPV075F14B1 9MPV100J16B1 9MPV125L20B1 Denotes Brand Save This Manual For Future Reference Four Position Furnace 25 23 30 International Comfort Products Corpora...

Page 48: ...Blower Transition Box Lo Fire Std Pressures of WC 5 No Elbows 40 5 90 DWV Elbows 1 80 2 60 1 30 2 30 1 20 1 90 1 00 1 80 1 80 2 60 1 30 2 30 1 20 1 90 1 00 1 80 1 80 2 60 1 70 2 50 1 20 1 90 1 00 1 8...

Page 49: ...631 921 1309 1530 0 5 609 891 1252 1460 0 6 569 845 1187 1380 0 7 529 799 1122 1300 0 8 490 730 1030 1190 0 9 680 950 1080 1 0 831 969 For 100 Models 4 Ton Units For 125 Models 5 Ton Units Speed Tap L...

Page 50: ...RANGE MHI RED LO BLACK HI BLUE MLO SPEED TAP CODE HEAT LOW IND LOW PURPLE P YELLOW Y WHITE W RED R ORANGE O GREEN G BROWN BR BLUE BL BLACK BK IND IN IND HI 3 COLOR CODE 24V SECONDARY 115V PRIMARY P1 4...

Page 51: ...1 440 01 2020 01 13 9MPT 25 23 95 AA 13 14 Z 19 YY WW 15 FF N LL EE 16 Z BB 12 16 GG 17 DD 11 CC FF 18 V W R S T U J L JJ Q P Y X F UU VV TT SS H RR QQ KK 5 4 3 9 10 M K 2 1 B A 8 6 7 HH K 25 23 95c O...

Page 52: ...e Pilot 018 503211 1 1 1 1 20 Filter HH 16X25X1 2 1010365 1 1 2 2 Key Description Part 9MPT Key No Description Non Functional Part Number 050 F12 075 F14 100 J16 125 L20 A Panel Top 1012866 1012867 10...

Page 53: ...1 1 1 SS Bracket Trap Bracket 1171987 1 1 1 1 TT Tube Drain Coll Box 5 8 ID 1171988 1 1 1 1 UU Tube Drain Tee 1 2 ID 1171989 1 1 1 1 VV Tube Relief 1009238 1 1 1 1 WW Drain Vent 1014003 1 1 1 1 YY Te...

Page 54: ...tion Box Hi Fire Std Pressures of WC 5 No Elbows 40 5 90 DWV Elbows Blower Transition Box Lo Fire Std Pressures of WC 5 No Elbows 40 5 90 DWV Elbows 1 80 2 60 1 30 2 30 1 20 1 90 1 00 1 80 1 80 2 60 1...

Page 55: ...ic on high heat Lo Heat Air Temperature Adjustment F Switch Settings Furnace Model 3 4 5 50K 75K 100K 125K 0 0 0 0 0 0 0 0 0 1 1 1 1 6 0 1 0 4 2 2 8 0 1 1 7 3 5 12 1 0 0 11 6 8 16 1 0 1 7 4 5 1 1 1 0...

Page 56: ...us Airflow Settings Figure 1 ESP W C 9MPV050 COOLING CFM VS EXTERNAL STATIC PRESSURE SCFM 0 200 400 600 800 1000 1200 1400 0 1 0 3 0 5 0 7 1 000 001 010 011 100 101 110 111 Figure 2 ESP W C 9MPV050 Hi...

Page 57: ...ettings Figure 3 ESP W C 9MPV050 Lo HEAT CFM VS EXTERNAL STATIC PRESSURE SCFM 0 100 200 300 400 500 600 700 800 900 1000 0 1 0 2 0 5 0 7 1 000 001 010 011 100 101 110 111 Figure 4 0 200 400 600 800 10...

Page 58: ...Airflow Settings Figure 5 9MPV075 Hi HEAT CFM VS EXTERNAL STATIC PRESSURE SCFM 0 200 400 600 800 1000 1200 1400 0 1 0 2 0 5 0 7 1 000 001 010 011 100 101 110 111 ESP W C 0 200 400 600 800 1000 1200 1...

Page 59: ...nuous Airflow Settings Figure 7 ESP W C 9MPV100 COOLING CFM VS EXTERNAL STATIC PRESSURE SCFM 0 500 1000 1500 2000 2500 0 1 0 3 0 5 0 7 1 000 001 010 011 100 101 110 111 Figure 8 ESP W C 9MPV100 Hi HEA...

Page 60: ...flow Settings Figure 9 ESP W C 9MPV100 Lo HEAT CFM VS EXTERNAL STATIC PRESSURE SCFM 0 200 400 600 800 1000 1200 1400 1600 1800 0 1 0 2 0 3 0 5 0 7 1 000 001 010 011 100 101 110 111 Figure 10 ESP W C 9...

Page 61: ...inuous Airflow Settings Figure 11 ESP W C 9MPV125 Lo HEAT CFM VS EXTERNAL STATIC PRESSURE SCFM 0 500 1000 1500 2000 2500 0 1 0 2 0 5 0 7 1 000 001 010 011 100 101 110 111 Figure 12 ESP W C 9MPV125 Hi...

Page 62: ...120 VAC XFMR DC MTR P1 COM 3 NEUTRAL 2 1 VAC 24 4 7 P2 Y2 C R OPTIONAL HUMIDISTAT W G Y Y W1 G TRANSFORMER HIGH INDH MOTOR INDUCER LO INDIN INDL 1 2 3 4 3 1 115V R R COM BR 24VAC BR 5 A FUSE 24VAC IGN...

Page 63: ...L 2 1 VAC 24 4 7 P2 Y2 C R OPTIONAL HUMIDISTAT W G 1 2 3 4 Y Y W1 G TRANSFORMER HIGH INDH MOTOR INDUCER LO INDIN INDL 1 2 3 4 3 1 115V R R COM BR 24VAC BR 5 A FUSE 24VAC IGNITER SENSOR 2 STAGE SHIELD...

Page 64: ...0 01 2020 01 15 9MPV 25 23 95b 21 AA 13 14 Z 19 YY WW 15 FF N LL EE 16 Z BB 12 16 GG 17 DD 11 CC FF 18 V W R S T U J L JJ Q P Y X F UU VV TT SS H RR QQ KK 5 4 3 9 10 M K 2 1 B A 8 6 7 HH OO 20 MM MM P...

Page 65: ...20 Filter HH 16X25X1 2 1010365 1 1 2 2 21 Control Mtr Variable Spd 1013410 1013411 1013412 1013413 1 1 1 1 Key Part 9MPV Key No Description Part Number 050 F12A 075 F12A 100 J20A 125 L20A A Panel Top...

Page 66: ...S Bracket Trap Bracket 1171987 1 1 1 1 TT Tube Drain Coll Box 5 8 ID 1171988 1 1 1 1 UU Tube Drain Tee 1 2 ID 1171989 1 1 1 1 VV Tube Relief 1009238 1 1 1 1 WW Drain Vent 1014003 1 1 1 1 YY Tee Drain...

Reviews: