26
9.4 Outdoor unit point check function
There is a check switch in outdoor PCB.
Press the switch N times it will display the content corresponding to No. N. After getting into the check function, it
will display No. N with 1.5s, meanwhile the low bit decimal of digit display flashing, indicated to get into the check
function display. After 1.5s, it will display the content corresponding to No. N.
the digital display tube will display the follow procedure when push SW1 each time.
Display
Remark
0
Normal display
Display running frequency, running state or malfunction code
1
No. of indoor units in good connection
Actual data
2
Outdoor unit running mode code
Standby:0,Fan only 1, Cooling:2, Heating:3, Forced cooling:4
Forced defrosting:5
3
A indoor unit capacity
The capacity unit is horse power. If the indoor unit is not connected,
the digital display tube will show: “――”
(7K:0.8HP, 9K:1HP,12K:1.2HP,18K:1.5HP)
4
B indoor unit capacity
5
C indoor unit capacity
6
D indoor unit capacity
7
E indoor unit capacity
8
A Indoor unit capacity demand code
Norm value*HP
(7K:0.8HP, 9K:1HP,12K:1.2HP,18K:1.5HP)
9
B Indoor unit capacity demand code
10
C Indoor unit capacity demand code
11
D Indoor unit capacity demand code
12
E Indoor unit capacity demand code
13
Total indoor units amendatory capacity
demand code
14
The frequency corresponding to the total
indoor units amendatory capacity demand
15
The frequency after the frequency limit
16
The frequency sending to compressor
control chip
17
A
indoor
unit
evaporator
outlet
temperature(T
2B
A)
If the temperature is lower than -9 degree, the digital display tube
will show “-9”.If the temperature is higher than 70 degree, the digital
display tube will show “70”. If the indoor unit is not connected, the
digital display tube will show: “――”
18
B
indoor
unit
evaporator
outlet
temperature(T
2B
B)
19
C
indoor
unit
evaporator
outlet
temperature(T
2B
C)
20
D
indoor
unit
evaporator
outlet
temperature(T
2B
D)
21
E
indoor
unit
evaporator
outlet
temperature(T
2B
E)
22
A indoor unit room temperature(T
1
A)
If the temperature is lower than 0 degree, the digital display tube will
show “0”.If the temperature is higher than 70 degree, the digital
display tube will show “70”. If the indoor unit is not connected, the
digital display tube will show: “――”
23
B indoor unit room temperature(T
1
B)
24
C indoor unit room temperature(T
1
C)
25
D indoor unit room temperature(T
1
D)
26
E indoor unit room temperature(T
1
E)
27
A indoor unit evaporator temperature(T
2
A)
If the temperature is lower than -9 degree, the digital display tube
will show “-9”.If the temperature is higher than 70 degree, the digital
display tube will show “70”. If the indoor unit is not connected, the
digital display tube will show: “――”
28
B indoor unit evaporator temperature(T
2
B)
29
C indoor unit evaporator temperature(T
2
C)
30
D indoor unit evaporator temperature(T
2
D)
31
E indoor unit evaporator temperature(T
2
E)
32
Condenser pipe temperature(T3)
33
Outdoor ambient temperature(T4)
34
Compressor discharge temperature(T5)
The display value is between 30~129 degree. If the temperature is
lower than 30 degree, the digital display tube will show “30”.If the
temperature is higher than 99 degree, the digital display tube will
show single digit and tens digit. For example, the digital display tube
Summary of Contents for YU2E14YEEBMHO-X
Page 8: ...7 5 Wiring diagram YU2E14YEEBMHO X YU2E18YEEBMHO X...
Page 10: ...9...
Page 11: ...10 YU4E28YEEBMHO X YU4E36YEEBMHO X...
Page 12: ...11 YU5E42YEEBMHO X...
Page 34: ...33 10 3 1 2 Indoor outdoor units communication error...
Page 39: ...38 10 3 1 4 Open or short circuit of temperature sensor 10 3 1 5 Full water malfunction...
Page 42: ...41 10 3 3 2 Communication malfunction between IPM board and outdoor main board ODU E3...
Page 45: ...44 10 3 3 5 High pressure protection ODU P1 ForYU4E28YEEBMHO X YU4E36YEEBMHO X YU5E42YEEBMHO X...
Page 47: ...46 10 3 3 7 Current protection of compressor ODU P3...
Page 48: ...47 10 3 3 8 Temperature protection of compressor discharge ODU P4...