27
show “0.5”,it means the compressor discharge temperature is 105
degree.)
35
AD value of current
The display value is hex number.
For example ,the digital display tube show “Cd”, it means AD value
is 205.
36
AD value of voltage
37
EXV open angle for A indoor unit
Actual data/4.
If the value is higher than 99, the digital display tube will show single
digit and tens digit.
For example ,the digital display tube show “2.0”,it means the EXV
open angle is 120×4=480p.)
38
EXV open angle for B indoor unit
39
EXV open angle for C indoor unit
40
EXV open angle for D indoor unit
41
EXV open angle for E indoor unit
42
Frequency limit symbol
Bit7
Frequency limit caused by IGBT
radiator
The display value
is hex number.
For example, the
digital display
tube show
2A,then Bit5=1,
Bit3=1, Bit1=1.
It means
frequency limit
caused by T4,T3
and current.
Bit6
Frequency limit caused by PFC
Bit5
Frequency limit caused by T4.
Bit4
Frequency limit caused by T2.
Bit3
Frequency limit caused by T3.
Bit2
Frequency limit caused by T5.
Bit1
Frequency limit caused by current
Bit0
Frequency limit caused by voltage
43
Average value of T2
(Sum T2 value of all indoor units)/( number of indoor units in good
connection)(cooling:T2B, heating:T2)
44
Outdoor unit fan motor state
Fan off:0, High speed:1, Med speed:2, Low speed:3 Breeze:4, Super
breeze:5
45
The last error or protection code
00 means no malfunction and protection
9.5 Protection
9.5.1 Three minutes delay at restart for compressor.
9.5.2 Temperature protection of compressor discharge.
When the compressor discharge temperature is getting higher, the running frequency will be limited as below
rules:
T 5
C o m p re s s o r o ff
F re q u e n c y lim it
N o rm a l
F re q u e n c y h o ld in g
9.5.3 Low voltage protection
Summary of Contents for YU2E14YEEBMHO-X
Page 8: ...7 5 Wiring diagram YU2E14YEEBMHO X YU2E18YEEBMHO X...
Page 10: ...9...
Page 11: ...10 YU4E28YEEBMHO X YU4E36YEEBMHO X...
Page 12: ...11 YU5E42YEEBMHO X...
Page 34: ...33 10 3 1 2 Indoor outdoor units communication error...
Page 39: ...38 10 3 1 4 Open or short circuit of temperature sensor 10 3 1 5 Full water malfunction...
Page 42: ...41 10 3 3 2 Communication malfunction between IPM board and outdoor main board ODU E3...
Page 45: ...44 10 3 3 5 High pressure protection ODU P1 ForYU4E28YEEBMHO X YU4E36YEEBMHO X YU5E42YEEBMHO X...
Page 47: ...46 10 3 3 7 Current protection of compressor ODU P3...
Page 48: ...47 10 3 3 8 Temperature protection of compressor discharge ODU P4...