10.3.2 For the super-slim cassette with up-down panel
10.3.2.1 Communication error between indoor unit and up-down panel
10.3.2.2 Up-down panel is defective
F8 Displayed
Up-down panel is defective
Retry. Can the panel move
up and down normally?
Check the wiring of
left and right
sensors. Are they
correctly wired?
Yes
No
The main control PCB of up-down
panel is defective. Replace it
Yes
No
If panel can move, power off, then
restart the unit 2 minutes later.
Has the problem been solved
?
No
If panel can not move,
check the wiring of the
louver motors. Are they
wired incorrectly?
Yes
Reconnect
Replace the louver
motors
Reconnect
No
No
No