48
10.3.3.9
High temperature protection of condenser (ODU P5)
When outdoor pipe temperature is more than 65°C, the unit will stop, and unit runs again when outdoor pipe
temperature less than 52°C.
High temperature protection of
condenser
Check whether the
condenser temperature is
Higher than 65°C
Yes
Check whether the
resistance of condenser
temp. sensor is normal
refer to the
Appendix
1
Replace the temperature sensor
No
No
Check whether the outdoor
ambient temperature is
higher than 50
℃
No
Stop the unit
Yes
Check if the outdoor unit
ventilation is good
Yes
Make the outdoor unit ventilate well
Check whether the heat
exchanger is dirty
No
Clean the heat exchanger
Yes
Check whether the refrigerant
system is ok
Replace outdoor main
board
No
Refrigerant is not enough add the
refrigerant
No
Check if the outdoor fan runs
properly
please refer to the solution of fan
speed has been out of control
malfunction . Find out the cause and
have it solved.
No
Yes
No
Correct the connection
No
Yes
Check the connection
between temperature
sensor and PCB.
Yes
Summary of Contents for YU2E14YEEBMHO-X
Page 8: ...7 5 Wiring diagram YU2E14YEEBMHO X YU2E18YEEBMHO X...
Page 10: ...9...
Page 11: ...10 YU4E28YEEBMHO X YU4E36YEEBMHO X...
Page 12: ...11 YU5E42YEEBMHO X...
Page 34: ...33 10 3 1 2 Indoor outdoor units communication error...
Page 39: ...38 10 3 1 4 Open or short circuit of temperature sensor 10 3 1 5 Full water malfunction...
Page 42: ...41 10 3 3 2 Communication malfunction between IPM board and outdoor main board ODU E3...
Page 45: ...44 10 3 3 5 High pressure protection ODU P1 ForYU4E28YEEBMHO X YU4E36YEEBMHO X YU5E42YEEBMHO X...
Page 47: ...46 10 3 3 7 Current protection of compressor ODU P3...
Page 48: ...47 10 3 3 8 Temperature protection of compressor discharge ODU P4...