When refrigerant pipe diameter is different from that of outdoor unit union (for 18K&24K indoor unit),
additional transfer connector needs to be used on outdoor unit union.
Indoor unit
Extension pipe diameter (mm/inch)
Model
Pipe diameter (mm/inch)
7K9K12K
Liquid
6.35(1/4)
Liquid
6.35(1/4)
Gas
9.52(3/8)
Gas
9.52(3/8)
18K
Liquid
6.35(1/4)
Liquid
6.35(1/4)
Gas
12.7(1/2)
Gas
12.7(1/2)
24K
Liquid
9.52(3/8)
Liquid
9.52(3/8)
Gas
15.9(5/8)
Gas
15.9(5/8)
Outdoor unit union diameter (mm/inch)
Indoor unit A/B/C/D/E
Liquid
6.35(1/4)
Gas
9.52(3/8)
12.7(1/2)
8.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
●
Pressure in the system rises.
●
Operating current rises.
●
Cooling or heating efficiency drops.
●
Moisture in the refrigerant circuit may freeze and block capillary tubing.
●
Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested and
evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit connections
by a soft brush to check for leakage of the connecting points of the piping. If bubbles come out, the pipes
have leakage.
1. Air purging with vacuum pump
Summary of Contents for YU2E14YEEBMHO-X
Page 8: ...7 5 Wiring diagram YU2E14YEEBMHO X YU2E18YEEBMHO X...
Page 10: ...9...
Page 11: ...10 YU4E28YEEBMHO X YU4E36YEEBMHO X...
Page 12: ...11 YU5E42YEEBMHO X...
Page 34: ...33 10 3 1 2 Indoor outdoor units communication error...
Page 39: ...38 10 3 1 4 Open or short circuit of temperature sensor 10 3 1 5 Full water malfunction...
Page 42: ...41 10 3 3 2 Communication malfunction between IPM board and outdoor main board ODU E3...
Page 45: ...44 10 3 3 5 High pressure protection ODU P1 ForYU4E28YEEBMHO X YU4E36YEEBMHO X YU5E42YEEBMHO X...
Page 47: ...46 10 3 3 7 Current protection of compressor ODU P3...
Page 48: ...47 10 3 3 8 Temperature protection of compressor discharge ODU P4...