background image

MAINTENANCE

CLEAN OR REPLACE AIR FILTERS REGULARLY

The intervals at which fi lters require replacement 
depend on local conditions.

Under normal conditions, the room air fi lter requires 
replacement every six to eight weeks.  In a new build-
ing, loose dirt tracked in from the outside may shorten 
this period.

To ensure proper maintenance of the fi lters, it is best 
to follow an organized maintenance procedure. 

MONTHLY CHECK LIST

• Inspect the unit air fi lters.  Clean or replace as 

required.

• Inspect the drainpan to be sure it is clean to permit 

the fl ow of condensate through the drain lines.

• Inspect the fan belt for wear and alignment.  Replace 

or adjust as required.

YEARLY CHECK LIST

• Inspect the blower coil unit casing for corrosion and 

loose fasteners.

• Inspect the blower wheel and housing. Clean if 

necessary.

• Check the motor pulley and blower pulley for 

alignment and tighten their set screws.  Adjust belt 
tension if necesssary.

• Inspect all coil connections for leaks  Inspect the coil 

fi ns for excessive dirt or damage.  clean or repair if 
required.

PULLEY ALIGNMENT AND BELT TENSION

Belt tension and pulley alignment should be checked.  
Belt tension is adjusted by means of the motor tailpiece 
adjusting bolt or the position of the motor on the base 
style motor mount.  A defl ection of about 3/4” to 1” 
per foot of span should be obtained by pressing the 
belt fi rmly 

(see Figure 6)

  The adjusting bolt should 

be locked in position after the adjustment is made.  
Alignment of pulley grooves is made by locating the 
motor pulley on the motor shaft or by moving the 
entire motor along the motor mounting bracket.  For 
blower speed adjustment, refer to that section.

BLOWER

Inspect the bearings for wear.  They are ball bearing, 
self-aligning and grease packed.  Replace if required.  
Inspect the thrust collars for end play and alignment 
of wheel.  Check the blades for accumulations of dirt 
and clean in order to avoid imbalance and vibration. 
Check mounting brackets, base bolts and isolation 
material.

MOTOR

Check motor connections to ensure that they are secure 
and made in accordance with the wiring diagram.

The blower motor should be cleaned annually and if it 
has oiling ports, it should be oiled with a good grade 
of SAE 20 oil.  Normally a few drops of oil in each 
bearing is suffi cient.

COIL

Any dust or other contaminants, which accumulate on 
the heat transfer surfaces, interferes with the airfl ow 
and impairs heat transfer.  The coil must be kept clean 
by any of the following methods:

• Cleaning with low-pressure compressed air.
• Flushing or rinsing with water (a detergent is 

advisable for greasy surfaces).

• If strainers are installed in the valve packages, 

clean the strainers once a year per manufactures 
directions.

FILTER

The air fi lter should be cleaned or replaced as often as 
necessary to prevent restriction of air fl ow.  Always 
replace the fi lter with the same type as originally 
furnished.

To clean permanent fi lters, remove the fi lter and wash 
in water to remove the old fi lter oil.  Rinse in clean, hot 
water and allow to dry.  Recoat both sides of the fi lter 
with RP fi lter coat, or an equivalent.  Allow to drain 
and dry thoroughly before reinstalling the fi lter.

DRAIN PIPING

The drain should always be connected or piped to an 
acceptable disposal point sloped away from the unit.  
Check the drain line for restrictions or blockage before 
summer operation and  monthly during the cooling 
season.

DRAIN PAN

The drain pan should be clean to allow proper conden-
sate fl ow.  Remove any accumulation of residue from 
the drain pan and inspect for rust and leaks. 

3/4" to 1" PER

FOOT OF SPAN

PULLEY ALIGNMENT

FIG 6 -  PULLEY ALIGNMENT AND BELT
  

ADJUSTMENT

7

YORK INTERNATIONAL

FORM 115.22-NOM5 (704)

Summary of Contents for YSHW

Page 1: ...ION RECORD THE UNIT MODEL AND SERIAL NO IN THE SPACE PROVIDED RETAIN FOR FUTURE REFERENCE Model No _____________________ Serial No ___________________ INSTALLER S RESPONSIBILITY Installer Please Note...

Page 2: ...lding construction provisions for mounting the unit must be made by the contractor according to architects drawings Before mounting unit remove red headed shipping bolts and metal bush ing at blower b...

Page 3: ...in the proper level This will ensure that the condensate will drain from the unit POWER WIRING All wiring must comply with the local and national code requirements Units are provided with wiring diagr...

Page 4: ...valves throughout the building CONTROL WIRING These blower coil units can be provided with an optional class 2 relay transformer for 24 volt control circuits 3 4 HP maximum load rating Should any add...

Page 5: ...12 1 4 10 7 8 27 1 2 16 1 4 16 X 16 3 7 8 ODS 48YSHW6 39 43 1 2 38 22 7 8 13 5 8 11 7 8 29 20 1 4 16 X 20 3 7 8 ODS 60YSHW6 42 50 1 2 45 22 7 8 16 13 7 8 36 20 1 4 20 X 20 2 1 1 8 ODS 4 ROW COIL FILT...

Page 6: ...19 1 8 48 30 1 4 26 X 29 2 1 3 8 ODS 180YSHW6 56 1 2 66 39 1 2 16 3 8 44 3 4 57 37 3 4 20 X 36 5 3 1 3 8 ODS 240YSHW6 62 1 2 66 52 16 3 8 44 3 4 57 50 1 4 20 X 49 3 1 3 8 ODS 4 ROW COIL FILTER SIZE L...

Page 7: ...packed Replace if required Inspect the thrust collars for end play and alignment of wheel Check the blades for accumulations of dirt and clean in order to avoid imbalance and vibration Check mounting...

Page 8: ...just as required Check all electrical connections for tightness Review electrical print for correct wiring Check condensate drain trap Main coil drain pan and auxiliary floor drains must be properly t...

Reviews: