START-UP
START UP-UP CHECKLIST
FAN INSPECTION
❑
Remove or loosen all shipping bolts on fan assembly.
❑
Tighten set screws on pulleys, bearings and fan, if applicable.
❑
Check tightness of fan bearing bolts, if applicable.
❑
Check tightness of blower wheel and fans to shaft.
❑
Check tightness of fan and motor sheaves, if applicable.
❑
Check tightness of all motor base and mounting bolts.
❑
Check sheave alignment - adjust if required.
❑
Adjust belt tension per sticker on fan blower assembly.
NOTE: Use “O” ring type defl ection belt tension checker.
❑
Equipment received as ordered.
❑
Unit checked for damage interior and exterior.
❑
Make sure all ductwork is complete and available for full air fl ow.
❑
Unit installed with proper clearances.
❑
Installer has cleaned out interior.
❑
Clean air fi lters installed properly and secured.
❑
Controls installation complete
❑
Rotate all moving components manually. Adjust as required.
❑
Check all electrical connections for tightness.
❑
Review electrical print for correct wiring.
❑
Check condensate drain trap.
❑
Main coil drain pan and auxiliary fl oor drains must be properly trapped and charged with water before units are started.
NOTE: If the motor and fan have not been operated in the last (4) four weeks or more, lubricate all the bearings and rotate the motor and fan
monthly to prevent moisture from accumulating in the bearings. (See Form 50.20-NM3, Long Term Storage)
ADJUSTMENT FOLLOWING INSTALLATION
The following adjustments should be made after
installation:
• Blower Speed Adjustment
Adjustment of blower speed is made by loosening
the set screw in the outer (movable) pulley face
and turning this face half or full turns only, so that
the adjusting set screw will be positioned precisely
over the fl at on the pulley hub. Speed is reduced by
adjusting the pulley faces so that they are further
apart; speed is increased with faces closer together.
Check all of the pulleys’ set screws for tightness.
• Room Thermostat
Adjust room thermostat to desired temperature.
This depends upon the environment and the
individual. For peak load conditions, the ideal
thermostat setting for “winter” and “summer” is
72°F and 76°F respectively.