SECTION 9 – SERVICE AND TROUBLESHOOTING
Digital Outputs
Refer to the unit wiring diagram and
. The digital outputs are located on TB7, TB8, and
TB9 and TB-10 of the microboard. ALL OUTPUTS
ARE 120 VAC with the exception of TB8-6 to TB8-7
which are the contacts that can be used for a remote
evaporator pump start signal. The voltage applied to
either of these terminals would be determined by field
wiring.
Each output is controlled by the microprocessor by
switching 120 VAC to the respective output connection
energizing contactors, evaporator heater, and solenoids
according to the operating sequence (see
120 VAC is supplied to the I/O board via connections
at TB7-1, TB7-6, TB10-1, TB10-6, TB8-1 and TB9-1
illustrates the relay contact
architecture on the microboard.
FIGURE 29 -
I/O BOARD RELAY CONTACT
ARCHITECTURE
LD12722
SYS 1
COMP 1
TB7-2
SYS 1
COMP 2
TB7-4
SYS 1
COMP 3
TB7-5
TB7-3
LLSV 1
TB8-6
EVAP
PUMP
TB8-7
TB7
SYS 2
HGSV
TB10-7
SYS 2
FAN 2
TB10-8
TB10-9
TB10-10 SYS 2
FAN 4
TB10
TB8
TB10
SYS 2
COMPR 1 (4)
TB10-2
LLSV 2
TB10-3
SYS 2
COMPR 2 (5)
TB10-4
SYS 2
COMPR 3 (6)
TB10-5
TB7
SYS 1
HGSV
TB7-7
SYS 1
FAN 1
TB7-9
SYS 1
FAN 3
TB7-10
TB7-8
SYS 1
FAN 2
TB8-2
HEAT EXCH
HEATER
*
*
* Not Used
Summary of Contents for YLUA0078
Page 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 42: ...JOHNSON CONTROLS 42 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 100: ...JOHNSON CONTROLS 100 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 130: ...JOHNSON CONTROLS 130 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 152: ...JOHNSON CONTROLS 152 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...