JOHNSON CONTROLS
150
FORM 150.73-NM1
ISSUE DATE: 09/04/2020
SECTION 9 – SERVICE AND TROUBLESHOOTING
TABLE 38 -
TROUBLESHOOTING
PROBLEM
CAUSE
SOLUTION
NO DISPLAY ON PANEL.
UNIT WILL NOT OPERATE
1. No 115 VAC to 24 VAC Transformer.
2. No 24 VAC to Microboard.
3. Control Transformer defective, no 24
VAC output.
4. Short in wire to temp. sensors or
pressure transducers.
5. Defective IPU II and I/O Board or the
Display Board.
1a. Check wiring and fuse 1FU.
1b. Check wiring emergency stop
contacts 5 to L of XTBC2
Terminal Block.
1c. Replace Control Transformer.
2. Check wiring Control Transformer to
Microboard.
3. Replace Control Transformer.
4. Unplug connections at IPU I and I/O
Board to isolate.
5. Replace IPU II and I/O Board or the
Display Board.
Contact Johnson
Controls Service be-
fore replacing Circuit
Boards!
“FLOW SWITCH/REM STOP NO RUN
PERMISSIVE”
1. No air flow.
2. Air Proving Switch improperly
installed.
3. Defective Air Proving Switch.
4. Remote cycling device open.
1. Check air flow.
2. Check that the Air Proving Switch is
installed according to manufacturer’s
instructions.
3. Replace Air Proving Switch.
4. Check cycling devices connected to
terminals 13 and 14 of the XTBC1
Terminal Block.
“LOW SUCTION PRESSURE FAULT”
1. Improper suction pressure cutouts
adjustments.
2. Low refrigerant charge.
3. Fouled Filter Dryer.
4. TXV defective.
5. Reduced air flow.
6. Defective Suction Pressure
Transducer/Low Pressure Switch or
wiring.
7. LLSV defective.
1. Adjust per recommended settings.
2. Repair leak if necessary and add
refrigerant.
3. Change Dryer/Core.
4. Replace TXV.
5. Check air flow.
6. Replace Transducer/Low Pressure
Switch or faulty wiring. See
SECTION 9 – SERVICE AND
TROUBLESHOOTING
voltage formula.
7. Replace LLSV.
Summary of Contents for YLUA0078
Page 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 42: ...JOHNSON CONTROLS 42 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 100: ...JOHNSON CONTROLS 100 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 130: ...JOHNSON CONTROLS 130 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 152: ...JOHNSON CONTROLS 152 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...