SECTION 7 – UNIT CONTROLS
S Y S 1 A R T I M E R X X S
S Y S 2 A R T I M E R X X S
The anti-recycle timer message shows the amount of
time left on the respective systems anti-recycle timer.
This message is displayed when the system is unable to
start due the anti-recycle timer being active.
S Y S 1 A C T I M E R X X S
S Y S 2 A C T I M E R X X S
The anti-coincidence timer is a software feature that
guards against 2 systems starting simultaneously. This
ensures instantaneous starting current does not become
excessively high due to simultaneous starts. The micro
limits the time between compressor starts to 1 minute
regardless of demand or the anti-recycle timer being
timed out. The anti-coincidence timer is only present
on two system units.
S Y S 1 D S C H L I M I T I N G
S Y S 2 D S C H L I M I T I N G
When this message appears, discharge pressure limit-
ing is in effect. The Discharge Pressure Limiting fea-
ture is integral to the standard software control; howev-
er the discharge transducer is optional on some models.
Therefore, it is important to keep in mind that this con-
trol will not function unless the discharge transducer is
installed in the system.
The limiting pressure is a factory set limit to keep the
system from faulting on the high discharge pressure
cutout due to high load or pull down conditions. When
the unload point is reached, the micro will automati-
cally unload the affected system by de energizing one
compressor. The discharge pressure unload will occur
when the discharge pressure gets within 15 psig of the
programmed discharge pressure cutout. This will only
happen if the system is fully loaded and will shut only
one compressor off. If the system is not fully loaded,
discharge limiting will not go into effect. Reloading the
affected system will occur when the discharge pressure
drops to 85% of the unload pressure and 10 minutes
have elapsed.
S Y S 1 S U C T L I M I T I N G
S Y S 2 S U C T L I M I T I N G
When this message appears, suction pressure limiting
is in effect. The suction pressure limit is a control point
that limits the loading of a system when the suction
pressure drops to within 15% above the suction pres-
sure cutout. On a standard system programmed for 80
psig/5.52 Bar suction pressure cutout, the micro would
inhibit loading of the affected system with the suction
pressure less than or equal to 1.15 * 80 psig/5.52 Bar
= 92 psig/6.34 Bar. The system will be allowed to load
after 60 seconds and after the suction pressure rises
above the suction pressure load limit point.
S Y S 1 L O A D L I M I T X X %
S Y S 2 L O A D L I M I T X X %
This message indicates that load limiting is in effect
and the percentage of the limiting in effect. This limit-
ing could be due to the load limit/pwm input, ISN or
RCC controller sending a load limit command.
M
A N
U A L
O
V E R
R I D E
If MANUAL OVERRIDE mode is selected, the STA-
TUS display will display this message. This will indi-
cate that the Daily Schedule is being ignored and the
unit will start-up when chilled liquid temperature al-
lows, Remote Contacts, UNIT switch and SYSTEM
switches permitting. This is a priority message and can-
not be overridden by anti-recycle messages, fault mes-
sages, etc. when in the STATUS display mode. There-
fore, do not expect to see any other STATUS messages
when in the MANUAL OVERRIDE mode. MANUAL
OVERRIDE is to only be used in emergencies or for
servicing. Manual override mode automatically disables
itself after 30 minutes.
S Y S 1 P U M P I N G D O W N
S Y S 2 P U M P I N G D O W N
The PUMPING DOWN message indicates that a com-
pressor in the respective system is presently in the pro-
cess of pumping the system down. When pumpdown is
initiated on shutdown, the liquid line solenoid or EEV
will close and a compressor will continue to run. When
the suction pressure decreases to the suction pressure
cutout setpoint or runs for 180 seconds, whichever
comes first, the compressor will cycle off.
Fault Safety Status Messages
Safety Status messages appear when safety thresholds
in the unit have been exceeded. Safeties are divided
into two categories – system safeties and unit safeties.
Summary of Contents for YLUA0078
Page 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 42: ...JOHNSON CONTROLS 42 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 100: ...JOHNSON CONTROLS 100 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 130: ...JOHNSON CONTROLS 130 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 152: ...JOHNSON CONTROLS 152 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...