As soon as a unit is received, it should be inspected for possible dam-
age during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s delivery receipt. A separate request for
inspection by the carrier’s agent should be made in writing. See Local
Distributor for more information.

Requirements For Installing/Servicing R-410A Equipment

Gauge sets, hoses, refrigerant containers, and recovery system
must be designed to handle the POE type oils, and the higher
pressures of R-410A.

Manifold sets should be high side and low side with low side
retard.

All hoses must have a 700 psig service pressure rating.

Leak detectors should be designed to detect HFC refrigerant.

Recovery equipment (including refrigerant recovery containers)
must be specifically designed to handle R-410A.

Do not use an R-22 TXV.

LIMITATIONS

The unit should be installed in accordance with all National, State and
Local Safety Codes and the limitations listed below:

1.

Limitations for the indoor unit, coil, and appropriate accessories
must also be observed.

2.

The outdoor unit must not be installed with any duct work in the air
stream. The outdoor fan is the propeller type and is not designed
to operate against any additional external static pressure.

3.

The maximum and minimum conditions for operation must be
observed to ensure a system that will give maximum performance
and service life.

4.

The unit should not be operated in cooling mode at outdoor tem-
peratures below 50°F without an approved low ambient operation
accessory kit installed.

5.

The maximum allowable line length for this product is 80 feet. To
install more than the maximum allowable line length, consult the
Piping Application Guide (P/N 247077).

SECTION III: UNIT INSTALLATION

LOCATION

Before starting the installation, select and check the suitability of the
location for both the indoor and outdoor unit. Observe all limitations and
clearance requirements.

The outdoor unit must have sufficient clearance for air entrance to the
condenser coil, air discharge, and service access. See Figure 1.

If the unit is to be installed on a hot sun exposed roof or a paved ground
area that is seasonally hot, the unit should be raised sufficiently above
the roof or ground to avoid taking the accumulated layer of hot air into
the outdoor unit.

If the system is being installed during seasonally cold weather of 55°F
or below, the preferred method is to weigh in the charge. For charging
or checking the system charge at 55°F or below, refer to the “Optional
Cold Weather Charging” procedures near the end of SECTION VI:
SYSTEM CHARGE. There is an “Optional Cold Weather Charging”
accessory kit to prevent the outdoor unit from taking in cold air below
55°F. The kit part number can be found in the list of accessory kits on
the UPGNET web site.

Provide adequate structural support for the unit.

ADD-ON REPLACEMENT/RETROFIT

When this unit is being used as a replacement for an R-410A unit, it is
required that the outdoor unit, indoor coil, and metering device all be
replaced. The following steps should be performed in order to insure
proper system operation and performance. Line-set change out is also
recommended.

1.

Change-out of the indoor coil to an approved R-410A coil/ con-
densing unit combination with the appropriate metering device.

2.

Change-out of the line-set when replacing an R-22 unit with an
R410-A unit is highly recommended to reduce cross-contamina-
tion of oils and refrigerants.

3.

If change-out of the line set is not practical, then the following pre-
cautions should be taken.

Inspect the line set for kinks, sharp bends, or other restrictions,
and for corrosion.

Determine if there are any low spots which might be serving as oil
traps.

Flush the line set with a commercially available flush kit to
remove as much of the existing oil and contaminants as possible.

Install a suction line filter-drier to trap any remaining contami-
nants, and remove after 50 hours of operation.

4.

If the outdoor unit is being replaced due to a compressor burnout,
then installation of a 100% activated alumina suction-line filter
drier in the suction-line is required, in addition to the factory
installed bi-flow liquid-line drier. Operate the system for 10 hours.
Monitor the suction drier pressure drop. If the pressure drop
exceeds 3 psig, replace both the suction-line and liquid-line driers.
After a total of 10 hours run time where the suction-line pressure
drop has not exceeded 3 psig, replace the liquid line drier, and
remove the suction-line drier. Never leave a suction-line drier in
the system longer than 50 hours of run time.

 CAUTION

This product must be installed in strict compliance with the
enclosed installation instructions and any applicable local, state,
and national codes including, but not limited to building, electrical,
and mechanical codes.

 CAUTION

R-410A systems operate at higher pressures than R-22 systems.
Do not use R-22 service equipment or components on R-410A
equipment. Service equipment 

Must Be Rated 

for R-410A.

TABLE 1: 

Maximum / Minimum Operating Limit Conditions

AIR TEMPERATURE AT 

OUTDOOR COIL, °F

AIR TEMPERATURE AT 

INDOOR COIL, °F

Min.

Max.

Min.

Max.

DB 

Cool

DB 

Heat

DB 

Cool

DB 

Heat

WB 

Cool

DB 

Heat

WB 

Cool

DB 

Heat

50° F -10° F 125° F 75° F

57° F

50° F

72° F

80° F

Operation below this temperature is permissible for a short period of time, 
during morning warm-up.

!

!

NOTICE

For multiple unit installations, units must be spaced a minimum of
24” (61 cm) apart (coil face to coil face).

Summary of Contents for YHE Series

Page 1: ...1 YHE60 Heat Charging Charts 12 TEST Input Functionality with Y 15 TEST Input Functionality without Y 15 Status Code Display 16 Status 16 SECTION I GENERAL The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines Sweat connect units are factory charged with refrigerant for a nominal sized matching indoor coil plus 15 feet of field supplied lines Matching in...

Page 2: ...There is an Optional Cold Weather Charging accessory kit to prevent the outdoor unit from taking in cold air below 55 F The kit part number can be found in the list of accessory kits on the UPGNET web site Provide adequate structural support for the unit ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 410A unit it is required that the outdoor unit indoor coil and...

Page 3: ...cess and serviceability as well as the possible sound and vibration transmission into the structure These applications are best served by a properly engineered solution UNIT PLACEMENT 1 Provide a base in the pre determined location 2 Remove the shipping carton and inspect for possible damage 3 Ensure that compressor tie down bolts remain tightened 4 Position the unit on the base provided LIQUID LI...

Page 4: ...n internally clean and dry system PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 4 Also protect all painted surfaces insulation and plastic base during brazing After braz ing cool joint with wet rag Valve can be opened by removing the service valve cap and fully insert ing a hex wrench ...

Page 5: ...discharged loosen and remove the Schrader core 3 Place a backup wrench on distributor loosen and remove brass distributor nut Retain brass nut for use on liquid line Keep Teflon washer in place and discard clear disk 4 Install the thermal expansion valve to the distributor assembly with supplied fittings Ensure Teflon washer is seated in distributor Hand tighten and turn an additional 1 4 turn to ...

Page 6: ...rge added accordingly MEASURE INDOOR AIR FLOW To determine rated air flow for a specific match consult the technical lit erature at www upgnet com When attempting to match this air flow select the lowest possible speed tap measure the actual flow and adjust as necessary To measure actual air flow it is not an acceptable method to just check the jumper pin setting tables and is to assume 0 5 water ...

Page 7: ...brated pressure gauge is not available place a R 410A virgin refrigerant container in a conditioned space long enough to come to tempera ture equilibrium with the surroundings Then measure the tem perature of the air and the pressure of the refrigerant and compare it to the following table Before measuring the pressures use the method above to check the air flow and then consult the table and matc...

Page 8: ...2 378 424 307 353 399 301 349 396 290 336 382 270 314 357 261 303 346 Suction Pressure PSIG 147 120 104 86 63 56 YHE TH4 RHP14L18 FC MC PC24 FC MC PC30 CFM Ambient Temperature F 60 47 40 30 17 10 Indoor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 450 Liquid Pressure PSIG 382 428 474 352 395 437 337 385 433 319 364 410 275 325 376 276 319 362 600 Liquid Pressure PSIG 346 391...

Page 9: ... 350 396 294 340 385 282 327 373 268 306 345 262 301 339 Suction Pressure PSIG 130 106 94 78 59 52 YHE TH4 THE RHP14L30 CF CM CU36 CF CM CU42 AP AVC30 AP AE AVC36 FC MC PC32 FC MC PC35 AHE30 AHV30 CFM Ambient Temperature F 60 47 40 30 17 10 Indoor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 800 Liquid Pressure PSIG 366 413 460 343 390 437 306 366 426 315 360 405 291 331 370...

Page 10: ...7 256 296 337 241 281 322 231 273 316 Suction Pressure PSIG 136 109 96 80 60 52 YHE TH4 RHP14L35 FC MC PC48 AHE AHV42 CFM Ambient Temperature F 60 47 40 30 17 10 Indoor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 1000 Liquid Pressure PSIG 321 365 408 301 344 386 290 335 379 274 318 361 255 296 337 246 288 329 1200 Liquid Pressure PSIG 301 342 383 283 313 367 275 308 362 261...

Page 11: ...essure PSIG 321 347 374 277 320 363 271 316 360 259 299 340 243 284 325 234 276 319 Suction Pressure PSIG 123 101 89 72 50 44 YHE THE TH4 RHP14L42 FC MC PC60 AHE48 AHV48 CFM Ambient Temperature F 60 47 40 30 17 10 Indoor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 1100 Liquid Pressure PSIG 357 386 415 306 349 392 295 340 385 279 323 367 259 301 342 250 292 334 1300 Liquid P...

Page 12: ...0 363 267 311 356 250 289 328 237 280 323 225 256 288 Suction Pressure PSIG 128 105 93 76 57 50 TABLE 9 YHE48 Heat Charging Charts Continued TABLE 10 YHE60 Heat Charging Charts YHE THE TH4 RHP14L60 CF CM CU64 AE60D AVC60D CFM Ambient Temperature F 60 47 40 30 17 10 Indoor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 1615 Liquid Pressure PSIG 340 385 430 315 345 404 302 333 3...

Page 13: ... CONNECTIONS POWER WIRING 1 Install the proper size weatherproof disconnect switch outdoors and within sight of the unit 2 Remove the screws at the top and sides of the corner cover Slide the control box cover down and remove from unit 3 Run power wiring from the disconnect switch to the unit 4 Route wires from disconnect through power wiring exit provided and into the unit control box as shown in...

Page 14: ...ommended that a mini mum air flow of 325 cfm ton be supplied at all times To see connection diagrams of all UPG equipment the Low Voltage System Wiring document is available online at www upgnet com in the Product Catalog Section INDOOR CUBIC FEET PER MINUTE CFM SELEC TION BOARD SETTINGS Typical Refer to the indoor unit Installation Manual instructions for the air han dler or furnace interface wit...

Page 15: ...owing table summarizes the behavior of the control when the two TEST pins are connected More detailed descriptions of the various functions are included in other sec tions of this document TABLE 11 TEST Input Functionality with Y Duration of connection seconds Control behavior with thermostat signals present 2 No response 2 5 Bypass ASCD Reduce timer to zero immediately If Y1 is present and high p...

Page 16: ... arrangement of the refrigeration circuit within the coil The control may initiate a defrost cycle even when the coil is not completely cov ered with frost This is normal operation The control regulates the defrost operation of the heat pump based on accumulated compressor run time outdoor coil temperature and out door ambient temperature The control will cause the heat pump unit to operate in the...

Page 17: ...ccur regardless of the liq uid line coil temperature reading The coil does not have to be cold for the unit to be forced into defrost Once the defrost cycle begins the con trol shall follow the normal defrost cycle routine The control will also initiate a defrost cycle when the TEST terminals are shorted This feature allows an installer or service technician to start a defrost cycle immediately as...

Page 18: ...sh code The control will reset the soft lockout condition when any of the follow ing occur after removal of the fault condition 1 Power is cycled to the R or Y inputs of the control This will cause the soft lockout condition to be reset when the thermostat is satis fied or when the thermostat is set to SYSTEM OFF and back to HEAT or COOL mode 2 The TEST terminals are shorted for more than two seco...

Page 19: ...CTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL DUAL CAPACITOR SHOWN SEPARATE CAPACITORS MAY BE USED ON ACTUAL UNIT WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH 105 C THERMOPLASTIC OR ITS EQUIVALENT WHERE POWER SUPPLY HAS ON...

Page 20: ...IBLE PERSONAL INJURY TO PREVENT ELECTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH 105 C THERMOPLASTIC OR ITS EQUIVALENT 1 2 3 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR ...

Page 21: ... TO PREVENT ELECTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH 105 C THERMOPLASTIC OR ITS EQUIVALENT 1 2 3 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR COIL CCH CRANKCASE H...

Page 22: ...5121495 UIM E 0716 22 Johnson Controls Unitary Products NOTES ...

Page 23: ...Data Venting if applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connected if applicable Supply plenum and return ducts are connected and sealed Filter Size Vent system is connected if applicable Thermostat wiring complete Heat anticipator is set to the r...

Page 24: ... ie ON OFF or the appropriate Value for the fields that apply to the defrost control board installed Run Time Time and Temperature board only 30 60 or 90 minutes Bonnet Sensor Present HEAT Refrigerant Charge and Metering Device TXV Fixed Orifice R 410A Oz 45s Elbows TXV Orifice Size Liquid Line Temp Subcooling Superheat High Side Pressure Low Side Pressure Suction Line Temp Additional Lineset Leng...

Reviews: