background image

5121495-UIM-E-0716

4

Johnson Controls Unitary Products

PIPING CONNECTIONS

The outdoor condensing unit must be connected to the indoor evapora-
tor coil using field supplied refrigerant grade (ACR) copper tubing that is
internally clean and dry. Units should be installed only with the tubing
sizes for approved system combinations as specified in tabular data
sheet. The charge given is applicable for total tubing lengths up to 15
feet (4.6 m). See Piping Application Guide (P/N 247077) for installing
tubing of longer lengths and elevation differences.

PRECAUTIONS DURING LINE INSTALLATION

1.

Install the lines with as few bends as possible. Care must be taken
not to damage the couplings or kink the tubing. Use clean hard
drawn copper tubing where no appreciable amount of bending
around obstruction is necessary. If soft copper must be used, care
must be taken to avoid sharp bends which may cause a restriction.

2.

The lines should be installed so that they will not obstruct service
access to the coil, air handling system, or filter.

3.

Care must also be taken to isolate the refrigerant lines to minimize
noise transmission from the equipment to the structure.

4.

The vapor line must be insulated with a minimum of 1/2” foam rub-
ber insulation (Armaflex or equivalent). Liquid lines that will be
exposed to direct sunlight, high temperatures, or excessive humid-
ity must also be insulated.

5.

Tape and suspend the refrigerant lines as shown. DO NOT allow
tube metal-to-metal contact. See Figure 2.

6.

Use PVC piping as a conduit for all underground installations as
shown in Figure 3. Buried lines should be kept as short as possible
to minimize the build up of liquid refrigerant in the vapor line during
long periods of shutdown.

7.

Pack fiberglass insulation and a sealing material such as perma-
gum around refrigerant lines where they penetrate a wall to reduce
vibration and to retain some flexibility.

8.

For systems with total line length exceeding 75 feet (22.86 m), see
Piping Application Guide (P/N 247077) for vapor and liquid line
sizing, calibration of liquid line pressure loss or gain, determination
of vapor line velocity, elevation limitations, TXV connections, sys-
tem charging, traps, etc.

PRECAUTIONS DURING BRAZING OF LINES

All outdoor unit and evaporator coil connections are copper-to-copper
and should be brazed with a phosphorous-copper alloy material such
as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units
have reusable service valves on both the liquid and vapor connections.
The total system refrigerant charge is retained within the outdoor unit
during shipping and installation. The reusable service valves are pro-
vided to evacuate and charge per this instruction.

Serious service problems can be avoided by taking adequate precau-
tions to assure an internally clean and dry system.

PRECAUTIONS DURING BRAZING SERVICE VALVE

Precautions should be taken to prevent heat damage to service valve
by wrapping a wet rag around it as shown in Figure 4. Also, protect all
painted surfaces, insulation, and plastic base during brazing. After braz-
ing, cool joint with wet rag.

Valve can be opened by removing the service valve cap and fully insert-
ing a hex wrench into the stem and backing out counter-clockwise until
valve stem just touches the chamfered retaining wall.

Connect the refrigerant lines using the following procedure:

1.

Remove the cap and Schrader core from both the liquid and vapor
service valve service ports at the outdoor unit. Connect low pres-
sure nitrogen to the liquid line service port.

2.

Braze the liquid line to the liquid valve at the outdoor unit. Be sure
to wrap the valve body with a wet rag. Allow the nitrogen to con-
tinue flowing.

3.

Carefully remove the plugs from the evaporator liquid and vapor
connections at the indoor coil.

NOTICE

Using a larger than specified line size could result in oil return prob-
lems. Using too small a line will result in loss of capacity and other
problems caused by insufficient refrigerant flow. Slope  horizontal
vapor lines at least 1" (2.5 cm) every 20 feet (6.1 m) toward the out-
door unit to facilitate proper oil return. If more than the 75 foot line
length is necessary, facilitate proper refrigerant velocity with
adjusted line diameter in accordance with the Piping Application
Guide (P/N 247077). 

 CAUTION

This system uses R-410A refrigerant which operates at higher pres-
sures than R-22. No other refrigerant may be used in this system.
Gauge sets, hoses, refrigerant containers, and recovery system
must be designed to handle R-410A. If you are unsure, consult the
equipment manufacturer.

 WARNING

Never install a suction-line filter drier in the liquid line of an R-410A
system. Failure to follow this warning can cause a fire, injury or
death.

 FIGURE 2:  

Installation of Vapor Line

!

!

$

+$1*(5

/,48,'
/,1(

,1&255(&7

&255(&7

,168/$7('9$325/,1(

7$3(

 FIGURE 3:  

Underground Installation

 CAUTION

Dry nitrogen should always be supplied through the tubing while it is
being brazed, because the temperature required is high enough to
cause oxidation of the copper unless an inert atmosphere is provided.
The flow of dry nitrogen should continue until the joint has cooled.

Always use a pressure regulator and safety valve to insure that only

low pressure dry nitrogen is introduced into the tubing. Only a small
flow is necessary to displace air and prevent oxidation.

 WARNING

This is not a backseating valve. The service access port has a valve
core. Opening or closing valve does not close service access port.
If the valve stem is backed out past the chamfered retaining wall, the
O-ring can be damaged causing leakage or system pressure could
force the valve stem out of the valve body possibly causing personal
injury.

TO INDOOR COIL

TO OUTDOOR UNIT

LIQUID LINE

CAP

PVC
CONDUIT

INSULATED

VAPOR LINE

A0152-001

!

!

Summary of Contents for YHE Series

Page 1: ...1 YHE60 Heat Charging Charts 12 TEST Input Functionality with Y 15 TEST Input Functionality without Y 15 Status Code Display 16 Status 16 SECTION I GENERAL The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines Sweat connect units are factory charged with refrigerant for a nominal sized matching indoor coil plus 15 feet of field supplied lines Matching in...

Page 2: ...There is an Optional Cold Weather Charging accessory kit to prevent the outdoor unit from taking in cold air below 55 F The kit part number can be found in the list of accessory kits on the UPGNET web site Provide adequate structural support for the unit ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 410A unit it is required that the outdoor unit indoor coil and...

Page 3: ...cess and serviceability as well as the possible sound and vibration transmission into the structure These applications are best served by a properly engineered solution UNIT PLACEMENT 1 Provide a base in the pre determined location 2 Remove the shipping carton and inspect for possible damage 3 Ensure that compressor tie down bolts remain tightened 4 Position the unit on the base provided LIQUID LI...

Page 4: ...n internally clean and dry system PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 4 Also protect all painted surfaces insulation and plastic base during brazing After braz ing cool joint with wet rag Valve can be opened by removing the service valve cap and fully insert ing a hex wrench ...

Page 5: ...discharged loosen and remove the Schrader core 3 Place a backup wrench on distributor loosen and remove brass distributor nut Retain brass nut for use on liquid line Keep Teflon washer in place and discard clear disk 4 Install the thermal expansion valve to the distributor assembly with supplied fittings Ensure Teflon washer is seated in distributor Hand tighten and turn an additional 1 4 turn to ...

Page 6: ...rge added accordingly MEASURE INDOOR AIR FLOW To determine rated air flow for a specific match consult the technical lit erature at www upgnet com When attempting to match this air flow select the lowest possible speed tap measure the actual flow and adjust as necessary To measure actual air flow it is not an acceptable method to just check the jumper pin setting tables and is to assume 0 5 water ...

Page 7: ...brated pressure gauge is not available place a R 410A virgin refrigerant container in a conditioned space long enough to come to tempera ture equilibrium with the surroundings Then measure the tem perature of the air and the pressure of the refrigerant and compare it to the following table Before measuring the pressures use the method above to check the air flow and then consult the table and matc...

Page 8: ...2 378 424 307 353 399 301 349 396 290 336 382 270 314 357 261 303 346 Suction Pressure PSIG 147 120 104 86 63 56 YHE TH4 RHP14L18 FC MC PC24 FC MC PC30 CFM Ambient Temperature F 60 47 40 30 17 10 Indoor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 450 Liquid Pressure PSIG 382 428 474 352 395 437 337 385 433 319 364 410 275 325 376 276 319 362 600 Liquid Pressure PSIG 346 391...

Page 9: ... 350 396 294 340 385 282 327 373 268 306 345 262 301 339 Suction Pressure PSIG 130 106 94 78 59 52 YHE TH4 THE RHP14L30 CF CM CU36 CF CM CU42 AP AVC30 AP AE AVC36 FC MC PC32 FC MC PC35 AHE30 AHV30 CFM Ambient Temperature F 60 47 40 30 17 10 Indoor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 800 Liquid Pressure PSIG 366 413 460 343 390 437 306 366 426 315 360 405 291 331 370...

Page 10: ...7 256 296 337 241 281 322 231 273 316 Suction Pressure PSIG 136 109 96 80 60 52 YHE TH4 RHP14L35 FC MC PC48 AHE AHV42 CFM Ambient Temperature F 60 47 40 30 17 10 Indoor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 1000 Liquid Pressure PSIG 321 365 408 301 344 386 290 335 379 274 318 361 255 296 337 246 288 329 1200 Liquid Pressure PSIG 301 342 383 283 313 367 275 308 362 261...

Page 11: ...essure PSIG 321 347 374 277 320 363 271 316 360 259 299 340 243 284 325 234 276 319 Suction Pressure PSIG 123 101 89 72 50 44 YHE THE TH4 RHP14L42 FC MC PC60 AHE48 AHV48 CFM Ambient Temperature F 60 47 40 30 17 10 Indoor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 1100 Liquid Pressure PSIG 357 386 415 306 349 392 295 340 385 279 323 367 259 301 342 250 292 334 1300 Liquid P...

Page 12: ...0 363 267 311 356 250 289 328 237 280 323 225 256 288 Suction Pressure PSIG 128 105 93 76 57 50 TABLE 9 YHE48 Heat Charging Charts Continued TABLE 10 YHE60 Heat Charging Charts YHE THE TH4 RHP14L60 CF CM CU64 AE60D AVC60D CFM Ambient Temperature F 60 47 40 30 17 10 Indoor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 1615 Liquid Pressure PSIG 340 385 430 315 345 404 302 333 3...

Page 13: ... CONNECTIONS POWER WIRING 1 Install the proper size weatherproof disconnect switch outdoors and within sight of the unit 2 Remove the screws at the top and sides of the corner cover Slide the control box cover down and remove from unit 3 Run power wiring from the disconnect switch to the unit 4 Route wires from disconnect through power wiring exit provided and into the unit control box as shown in...

Page 14: ...ommended that a mini mum air flow of 325 cfm ton be supplied at all times To see connection diagrams of all UPG equipment the Low Voltage System Wiring document is available online at www upgnet com in the Product Catalog Section INDOOR CUBIC FEET PER MINUTE CFM SELEC TION BOARD SETTINGS Typical Refer to the indoor unit Installation Manual instructions for the air han dler or furnace interface wit...

Page 15: ...owing table summarizes the behavior of the control when the two TEST pins are connected More detailed descriptions of the various functions are included in other sec tions of this document TABLE 11 TEST Input Functionality with Y Duration of connection seconds Control behavior with thermostat signals present 2 No response 2 5 Bypass ASCD Reduce timer to zero immediately If Y1 is present and high p...

Page 16: ... arrangement of the refrigeration circuit within the coil The control may initiate a defrost cycle even when the coil is not completely cov ered with frost This is normal operation The control regulates the defrost operation of the heat pump based on accumulated compressor run time outdoor coil temperature and out door ambient temperature The control will cause the heat pump unit to operate in the...

Page 17: ...ccur regardless of the liq uid line coil temperature reading The coil does not have to be cold for the unit to be forced into defrost Once the defrost cycle begins the con trol shall follow the normal defrost cycle routine The control will also initiate a defrost cycle when the TEST terminals are shorted This feature allows an installer or service technician to start a defrost cycle immediately as...

Page 18: ...sh code The control will reset the soft lockout condition when any of the follow ing occur after removal of the fault condition 1 Power is cycled to the R or Y inputs of the control This will cause the soft lockout condition to be reset when the thermostat is satis fied or when the thermostat is set to SYSTEM OFF and back to HEAT or COOL mode 2 The TEST terminals are shorted for more than two seco...

Page 19: ...CTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL DUAL CAPACITOR SHOWN SEPARATE CAPACITORS MAY BE USED ON ACTUAL UNIT WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH 105 C THERMOPLASTIC OR ITS EQUIVALENT WHERE POWER SUPPLY HAS ON...

Page 20: ...IBLE PERSONAL INJURY TO PREVENT ELECTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH 105 C THERMOPLASTIC OR ITS EQUIVALENT 1 2 3 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR ...

Page 21: ... TO PREVENT ELECTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH 105 C THERMOPLASTIC OR ITS EQUIVALENT 1 2 3 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR COIL CCH CRANKCASE H...

Page 22: ...5121495 UIM E 0716 22 Johnson Controls Unitary Products NOTES ...

Page 23: ...Data Venting if applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connected if applicable Supply plenum and return ducts are connected and sealed Filter Size Vent system is connected if applicable Thermostat wiring complete Heat anticipator is set to the r...

Page 24: ... ie ON OFF or the appropriate Value for the fields that apply to the defrost control board installed Run Time Time and Temperature board only 30 60 or 90 minutes Bonnet Sensor Present HEAT Refrigerant Charge and Metering Device TXV Fixed Orifice R 410A Oz 45s Elbows TXV Orifice Size Liquid Line Temp Subcooling Superheat High Side Pressure Low Side Pressure Suction Line Temp Additional Lineset Leng...

Reviews: