background image

5121495-UIM-E-0716

Johnson Controls Unitary Products

7

CHARGING THE UNIT

The factory charge in the outdoor unit includes enough charge for the
unit, 15 ft. (4.6 m) of refrigerant piping, and the smallest indoor coil/air
handler match-up. Some indoor coil/air handler matches may require
additional charge.

See Tabular Data Sheet provided in unit Customer Booklet for charge
requirements. The “TOTAL SYSTEM CHARGE” must be permanently
marked on the unit data plate.

TOTAL SYSTEM CHARGE DETERMINED 

1. Determine outdoor unit factory charge from Tabular Data Sheet.
2. Determine indoor coil adjustment (if any) from Tabular Data Sheet.
3. Calculate the additional charge for refrigerant piping using the Tabu-

lar Data Sheet if line length is greater than 15 feet (4.6 m).

4. Total system charge = item 1 + item 2 + item 3.
5. Check the unit against the pressure value listed on the cooling chart

on the unit or the appropriate heat charging chart on the following
pages of this Installation Manual. Make any adjustment necessary.

6. Add or subtract refrigerant to obtain the pressure listed on charging

chart. Make sure to adjust the total system charge by the amount
added or removed to obtain charging chart pressures. Permanently
mark the unit data plate with the total amount of refrigerant in the
system.

CHARGING WITH GAUGES

All units include a cooling charging chart for cooling. The heating
charging charts in Table 3 through Table 10 in this document use the
chart corresponding to the installed indoor coil. It can also be obtained
at 

www.upgnet.com

 under the Service Application Data section.

Before using gauges, confirm that your gauges are accurate by
comparing the gauges against a calibrated pressure gauge that
has been calibrated against a national standard. If a calibrated
pressure gauge is not available, place a R-410A virgin refrigerant
container in a conditioned space long enough to come to tempera-
ture equilibrium with the surroundings. Then measure the tem-
perature of the air and the pressure of the refrigerant and compare
it to the following table:

:

Before measuring the pressures, use the method above to check the air
flow and then consult the table and match the liquid pressure to that air
flow.

Reference the heat charging charts in Table 3 through Table 10

 CAUTION

Always charge in liquid form. Take care not to slug the compressor.

 CAUTION

Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.

 CAUTION

Do not leave the system open to the atmosphere. Unit damage could
occur due to moisture being absorbed by the POE oil in the system.
This type of oil is highly susceptible to moisture absorption.

 WARNING

DO NOT attempt to pump “Total System Charge” into outdoor unit for
maintenance, service, etc. This may cause damage to the compres-
sor and/or other components. Recover and weigh “System Charge”
into an appropriate recovery cylinder for any instances requiring
evacuation.

!

!

!

!

 CAUTION

IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS-
CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR,
SERVICE, MAINTENANCE OR THE FINAL DISPOSAL OF THIS
UNIT.

 CAUTION

Refrigerant charging should only be carried out by a qualified air con-
ditioning contractor.

 CAUTION

Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.

TABLE 2: 

R-410A Saturation Properties

Temp 

(°F)

Pressure 

(Psig)

Temp 

(°F)

Pressure 

(Psig)

Temp 

(°F)

Pressure 

(Psig)

40

119

75

218

110

365

45

130

80

236

115

391

50

143

85

255

120

418

55

156

90

274

125

447

60

170

95

295

130

477

65

185

100

317

70

201

105

341

!

!

!

Summary of Contents for YHE Series

Page 1: ...1 YHE60 Heat Charging Charts 12 TEST Input Functionality with Y 15 TEST Input Functionality without Y 15 Status Code Display 16 Status 16 SECTION I GENERAL The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines Sweat connect units are factory charged with refrigerant for a nominal sized matching indoor coil plus 15 feet of field supplied lines Matching in...

Page 2: ...There is an Optional Cold Weather Charging accessory kit to prevent the outdoor unit from taking in cold air below 55 F The kit part number can be found in the list of accessory kits on the UPGNET web site Provide adequate structural support for the unit ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 410A unit it is required that the outdoor unit indoor coil and...

Page 3: ...cess and serviceability as well as the possible sound and vibration transmission into the structure These applications are best served by a properly engineered solution UNIT PLACEMENT 1 Provide a base in the pre determined location 2 Remove the shipping carton and inspect for possible damage 3 Ensure that compressor tie down bolts remain tightened 4 Position the unit on the base provided LIQUID LI...

Page 4: ...n internally clean and dry system PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 4 Also protect all painted surfaces insulation and plastic base during brazing After braz ing cool joint with wet rag Valve can be opened by removing the service valve cap and fully insert ing a hex wrench ...

Page 5: ...discharged loosen and remove the Schrader core 3 Place a backup wrench on distributor loosen and remove brass distributor nut Retain brass nut for use on liquid line Keep Teflon washer in place and discard clear disk 4 Install the thermal expansion valve to the distributor assembly with supplied fittings Ensure Teflon washer is seated in distributor Hand tighten and turn an additional 1 4 turn to ...

Page 6: ...rge added accordingly MEASURE INDOOR AIR FLOW To determine rated air flow for a specific match consult the technical lit erature at www upgnet com When attempting to match this air flow select the lowest possible speed tap measure the actual flow and adjust as necessary To measure actual air flow it is not an acceptable method to just check the jumper pin setting tables and is to assume 0 5 water ...

Page 7: ...brated pressure gauge is not available place a R 410A virgin refrigerant container in a conditioned space long enough to come to tempera ture equilibrium with the surroundings Then measure the tem perature of the air and the pressure of the refrigerant and compare it to the following table Before measuring the pressures use the method above to check the air flow and then consult the table and matc...

Page 8: ...2 378 424 307 353 399 301 349 396 290 336 382 270 314 357 261 303 346 Suction Pressure PSIG 147 120 104 86 63 56 YHE TH4 RHP14L18 FC MC PC24 FC MC PC30 CFM Ambient Temperature F 60 47 40 30 17 10 Indoor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 450 Liquid Pressure PSIG 382 428 474 352 395 437 337 385 433 319 364 410 275 325 376 276 319 362 600 Liquid Pressure PSIG 346 391...

Page 9: ... 350 396 294 340 385 282 327 373 268 306 345 262 301 339 Suction Pressure PSIG 130 106 94 78 59 52 YHE TH4 THE RHP14L30 CF CM CU36 CF CM CU42 AP AVC30 AP AE AVC36 FC MC PC32 FC MC PC35 AHE30 AHV30 CFM Ambient Temperature F 60 47 40 30 17 10 Indoor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 800 Liquid Pressure PSIG 366 413 460 343 390 437 306 366 426 315 360 405 291 331 370...

Page 10: ...7 256 296 337 241 281 322 231 273 316 Suction Pressure PSIG 136 109 96 80 60 52 YHE TH4 RHP14L35 FC MC PC48 AHE AHV42 CFM Ambient Temperature F 60 47 40 30 17 10 Indoor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 1000 Liquid Pressure PSIG 321 365 408 301 344 386 290 335 379 274 318 361 255 296 337 246 288 329 1200 Liquid Pressure PSIG 301 342 383 283 313 367 275 308 362 261...

Page 11: ...essure PSIG 321 347 374 277 320 363 271 316 360 259 299 340 243 284 325 234 276 319 Suction Pressure PSIG 123 101 89 72 50 44 YHE THE TH4 RHP14L42 FC MC PC60 AHE48 AHV48 CFM Ambient Temperature F 60 47 40 30 17 10 Indoor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 1100 Liquid Pressure PSIG 357 386 415 306 349 392 295 340 385 279 323 367 259 301 342 250 292 334 1300 Liquid P...

Page 12: ...0 363 267 311 356 250 289 328 237 280 323 225 256 288 Suction Pressure PSIG 128 105 93 76 57 50 TABLE 9 YHE48 Heat Charging Charts Continued TABLE 10 YHE60 Heat Charging Charts YHE THE TH4 RHP14L60 CF CM CU64 AE60D AVC60D CFM Ambient Temperature F 60 47 40 30 17 10 Indoor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 1615 Liquid Pressure PSIG 340 385 430 315 345 404 302 333 3...

Page 13: ... CONNECTIONS POWER WIRING 1 Install the proper size weatherproof disconnect switch outdoors and within sight of the unit 2 Remove the screws at the top and sides of the corner cover Slide the control box cover down and remove from unit 3 Run power wiring from the disconnect switch to the unit 4 Route wires from disconnect through power wiring exit provided and into the unit control box as shown in...

Page 14: ...ommended that a mini mum air flow of 325 cfm ton be supplied at all times To see connection diagrams of all UPG equipment the Low Voltage System Wiring document is available online at www upgnet com in the Product Catalog Section INDOOR CUBIC FEET PER MINUTE CFM SELEC TION BOARD SETTINGS Typical Refer to the indoor unit Installation Manual instructions for the air han dler or furnace interface wit...

Page 15: ...owing table summarizes the behavior of the control when the two TEST pins are connected More detailed descriptions of the various functions are included in other sec tions of this document TABLE 11 TEST Input Functionality with Y Duration of connection seconds Control behavior with thermostat signals present 2 No response 2 5 Bypass ASCD Reduce timer to zero immediately If Y1 is present and high p...

Page 16: ... arrangement of the refrigeration circuit within the coil The control may initiate a defrost cycle even when the coil is not completely cov ered with frost This is normal operation The control regulates the defrost operation of the heat pump based on accumulated compressor run time outdoor coil temperature and out door ambient temperature The control will cause the heat pump unit to operate in the...

Page 17: ...ccur regardless of the liq uid line coil temperature reading The coil does not have to be cold for the unit to be forced into defrost Once the defrost cycle begins the con trol shall follow the normal defrost cycle routine The control will also initiate a defrost cycle when the TEST terminals are shorted This feature allows an installer or service technician to start a defrost cycle immediately as...

Page 18: ...sh code The control will reset the soft lockout condition when any of the follow ing occur after removal of the fault condition 1 Power is cycled to the R or Y inputs of the control This will cause the soft lockout condition to be reset when the thermostat is satis fied or when the thermostat is set to SYSTEM OFF and back to HEAT or COOL mode 2 The TEST terminals are shorted for more than two seco...

Page 19: ...CTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL DUAL CAPACITOR SHOWN SEPARATE CAPACITORS MAY BE USED ON ACTUAL UNIT WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH 105 C THERMOPLASTIC OR ITS EQUIVALENT WHERE POWER SUPPLY HAS ON...

Page 20: ...IBLE PERSONAL INJURY TO PREVENT ELECTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH 105 C THERMOPLASTIC OR ITS EQUIVALENT 1 2 3 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR ...

Page 21: ... TO PREVENT ELECTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH 105 C THERMOPLASTIC OR ITS EQUIVALENT 1 2 3 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR COIL CCH CRANKCASE H...

Page 22: ...5121495 UIM E 0716 22 Johnson Controls Unitary Products NOTES ...

Page 23: ...Data Venting if applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connected if applicable Supply plenum and return ducts are connected and sealed Filter Size Vent system is connected if applicable Thermostat wiring complete Heat anticipator is set to the r...

Page 24: ... ie ON OFF or the appropriate Value for the fields that apply to the defrost control board installed Run Time Time and Temperature board only 30 60 or 90 minutes Bonnet Sensor Present HEAT Refrigerant Charge and Metering Device TXV Fixed Orifice R 410A Oz 45s Elbows TXV Orifice Size Liquid Line Temp Subcooling Superheat High Side Pressure Low Side Pressure Suction Line Temp Additional Lineset Leng...

Reviews: