47
YORK INTERNATIONAL
FORM 201.19-NM7 (804)
TEMPERATURE AND FLOWS
(SI UNITS)
Excessive fl ow, above the max GPM,
will damage the evaporator.
7
NOTES:
1. For leaving brine temperature below 4.4°C, contact your nearest YORK of
Þ
ce for application requirements.
2. For leaving water temperature higher than 13°C, contact the nearest YORK of
Þ
ce for application guidelines.
3. The evaporator is protected against freeze-up to -28.8°C with an electrical heater as standard.
MODEL
NUMBER
YCAS
LEAVING WATER
TEMPERATURE (°C)
COOLER FLOW
(L/S)
3
AIR ON
CONDENSER (°C)
MIN.
1
MAX.
2
MIN.
MAX.
MIN.
MAX
0295
5.0
13.0
6.9
25.4
-17.7
50.0
0335
5.0
13.0
7.7
25.4
-17.7
50.0
0375
5.0
13.0
8.6
25.4
-17.7
50.0
0425
5.0
13.0
9.5
37.9
-17.7
50.0
0475
5.0
13.0
10.6
42.3
-17.7
50.0
0515
5.0
13.0
11.7
46.9
-17.7
50.0
0555
5.0
13.0
12.4
48.5
-17.7
50.0
0575
5.0
13.0
13.1
48.5
-17.7
50.0
0605
5.0
13.0
13.6
48.5
-17.7
50.0
Summary of Contents for YCAS0295EB
Page 43: ...43 YORK INTERNATIONAL FORM 201 19 NM7 804 5 This page intentionally left blank...
Page 45: ...45 YORK INTERNATIONAL FORM 201 19 NM7 804 6 This page intentionally left blank...
Page 59: ...59 YORK INTERNATIONAL FORM 201 19 NM7 804 This page intentionally left blank 7...
Page 71: ...71 YORK INTERNATIONAL FORM 201 19 NM7 804 7 LEGEND LD09241 YCAS0295 YCAS0605...
Page 73: ...73 YORK INTERNATIONAL FORM 201 19 NM7 804 7 CONNECTION DIAGRAM SYSTEM WIRING LD010030...
Page 74: ...74 YORK INTERNATIONAL FORM 201 19 NM7 804 Technical Data COMPRESSOR TERMINAL BOX LD10029...
Page 77: ...77 YORK INTERNATIONAL FORM 201 19 NM7 804 7 This page intentionally left blank...
Page 115: ...115 YORK INTERNATIONAL FORM 201 19 NM7 804 7 This page intentionally left blank...