49
YORK INTERNATIONAL
FORM 201.19-NM7 (804)
7
OPERATING LIMITATIONS AND SOUND POWER DATA
OPERATING LIMITATIONS –
SI UNITS
* Maximum Ambient w/ High Ambient Kit is 54°C.
MIN MAX
LEAVING CHILLED LIQUID TEMP ( °C) 5.0 13
CHILLED WATER TEMP DIFFERENCE ( °C) 3 10
WATER SIDE PRESSURE (BAR) – 10
REFRIGERANT SIDE PRESSURE (BAR) – 20
EVAPORATOR FLOW
MODEL
LITERS/SECOND
YCAS
MIN. MAX.
0295EB 6.9 25.4
0335EB 7.7 25.4
0375EB 8.6 25.4
0425EB 9.5 37.9
0475EB 10.6 42.3
0515EB 11.7 46.9
0555EB 12.4 48.5
0575EB 13.1 48.5
0605EB 13.6 48.5
AIR
STANDARD FANS –18 46
ENTERING
CONDENSER (
°
C)
FAN STANDARD FANS 20
AVAILABLE STATIC HIGH PRESS. FANS OPTION 1 85
PRESSURE (Pa) HIGH PRESS. FANS OPTION 2 150
SLOW SPEED FANS 10
ELECTRICAL THREE PHASE 50 Hz (V) 380