178
YORK INTERNATIONAL
FORM 201.19-NM7 (804)
Micro Panel Contents
ANALOG INPUTS
Not all of the sensors are installed in every unit as some
of them are optional. However, the software must still be
able to read the sensors if the optional ones are installed.
Table 9 lists all of the analog inputs and whether they
are on the Microboard or the I/O Expansion Board.
TABLE 9 -
ANALOG INPUTS
Microboard
J11-7
Leaving Chilled Liquid Temp Sensor
Microboard
J11-8
Return Chilled Liquid Temp Sensor
Microboard
J11-9
Ambient Air Temp Sensor
Microboard
J12-1
SPARE
Microboard
J12-3
SPARE
Microboard
J13-7
Sys 1 Suction Pressure Transducer
Microboard
J13-8
Sys 1 Oil Pressure Transducer
Microboard
J14-7
Sys 2 Suction Pressure Transducer
Microboard
J14-8
Sys 2 Oil Pressure Transducer
Microboard
J15-7
Sys 2 Discharge Pressure Transducer
Microboard
J15-8
Sys 1 Discharge Pressure Transducer
Microboard
J16-4
Sys 2 Suction Temp Sensor
Microboard
J16-6
Sys 1 Suction Temp Sensor
Microboard
J17-9
Input from I/O Expansion Board
Microboard
J17-10
SPARE
Microboard
J17-11
Mixed Chilled Liquid Temp Sensor (optional)
Hot Leaving Temp Sensor (Heat Recovery only)
I/O Expansion
J4-4
Sys 1 Motor Current
I/O Expansion
J4-5
SPARE
I/O Expansion
J4-8
SPARE
I/O Expansion
J4-10
Sys 2 Motor Current
I/O Expansion
J4-11
SPARE
I/O Expansion
J4-12
SPARE
I/O Expansion
J5-6
SPARE
I/O Expansion
J5-7
SPARE
I/O Expansion
J6-2
SPARE
Sys 1 Fan Pressure Transducer (Heat Recovery only)
I/O Expansion
J7-2
Sys 2 Evaporator Inlet Refrigerant Temp Sensor (R-407c only)
I/O Expansion
J8-4
Sys 1 Discharge Temp Sensor
I/O Expansion
J8-6
Sys 2 Discharge Temp Sensor
I/O Expansion
J9-2
SPARE
Sys 2 Fan Pressure Transducer (Heat Recovery only)
I/O Expansion
J10-6
Sys 2 Oil Temp Sensor
I/O Expansion
J10-7
Sys 1 Oil Temp Sensor
I/O Expansion
J11-2
Sys 1 Evaporator Inlet Refrigeration Temp Sensor (R-407c only)
Summary of Contents for YCAS0295EB
Page 43: ...43 YORK INTERNATIONAL FORM 201 19 NM7 804 5 This page intentionally left blank...
Page 45: ...45 YORK INTERNATIONAL FORM 201 19 NM7 804 6 This page intentionally left blank...
Page 59: ...59 YORK INTERNATIONAL FORM 201 19 NM7 804 This page intentionally left blank 7...
Page 71: ...71 YORK INTERNATIONAL FORM 201 19 NM7 804 7 LEGEND LD09241 YCAS0295 YCAS0605...
Page 73: ...73 YORK INTERNATIONAL FORM 201 19 NM7 804 7 CONNECTION DIAGRAM SYSTEM WIRING LD010030...
Page 74: ...74 YORK INTERNATIONAL FORM 201 19 NM7 804 Technical Data COMPRESSOR TERMINAL BOX LD10029...
Page 77: ...77 YORK INTERNATIONAL FORM 201 19 NM7 804 7 This page intentionally left blank...
Page 115: ...115 YORK INTERNATIONAL FORM 201 19 NM7 804 7 This page intentionally left blank...