56
JOHNSON CONTROLS
ELECTRICAL DATA
One field provided power supply circuit to the unit with
field supplied circuit protection. Field connections to
factory provided Non-Fused Disconnect Switch (Opt),
or Terminal Block (Opt) in the Options Panel. Factory
connections to Terminal Blocks in each of the two
Power Panels.
OPTIONAL SINGLE-POINT POWER SUPPLY
CONNECTION WITH FIELD SUPPLIED CIRCUIT
PROTECTION
Suitable for:
Y -
∆
Start and
Across-The-Line-Start
OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION – 2 COMPRESSOR UNITS
(One Field Provided Power Supply Circuit to the Chiller. Field connections to Factory Provided Terminal Block (Standard) or Non-Fused
Disconnect (option) in the ‘Options’ Panel. No Internal Branch Circuit Protection (Breakers) per Motor Control Center
10
)
See page 58 for Electrical Data footnotes.
CHILLER FIELD-SUPPLIED WIRING
MODEL VOLTS
FIELD PROVIDED POWER SUPPLY
FACTORY PROVIDED (LUGS) WIRE RANGE
7
YCAS
MIN NF OVER-CURRENT PROTECTION
13
STANDARD
OPTIONAL NF
MCA
1
DISC SW
2, 9
MIN.
3, 5
MAX.
4, 6
TERMINAL BLOCK
DISC. SWITCH
380
228
250
250
300
1/0 - 300
# 6 - 350
0098EB
460
188
200
225
250
# 2 - 4/0
# 6 - 350
575
151
200
175
200
1/0 - 300
# 6 - 350
380
285
400
350
400
2/0 - 500
(2) 3/0 - 250
0118EB
460
236
250
300
350
1/0 - 300
# 6 - 350
575
189
200
225
250
1/0 - 300
# 6 - 350
380
275
400
350
350
2/0 - 500
(2) 3/0 - 250
0128EB
460
228
250
300
300
1/0 - 300
# 6 - 350
575
182
200
225
250
1/0 - 300
# 6 - 350
380
313
400
350
400
2/0 - 500
(2) 3/0 - 250
0138EB
460
259
400
300
350
2/0 - 500
(2) 3/0 - 250
575
206
250
250
250
1/0 - 300
# 6 - 350
380
313
400
350
400
2/0 - 500
(2) 3/0 - 250
0148EB
460
260
400
300
350
2/0 - 500
(2) 3/0 - 250
575
207
250
250
250
1/0 - 300
# 6 - 350
380
371
400
450
500
(2) # 2 - 4/0
(2) 3/0 - 250
0158EB
460
308
400
350
400
2/0 - 500
(2) 3/0 - 250
575
244
250
300
350
2/0 - 500
# 6 - 350
380
418
600
500
500
(2) 1/0 - 300
(2) 250 - 500
0178EB
460
347
400
400
450
(2) # 2 - 4/0
(2) 3/0 - 250
575
275
400
350
350
2/0 - 500
(2) 3/0 - 250
380
451
600
600
600
(2) 1/0 - 300
(2) 250 - 500
0198EB
460
374
400
450
500
(2) # 2 - 4/0
(2) 3/0 - 250
575
297
400
350
400
2/0 - 500
(2) 3/0 - 250
380
493
600
600
600
(2) 1/0 - 300
(2) 250 - 500
0208EB
460
408
600
500
500
(2) 1/0 - 300
(2) 250 - 500
575
325
400
350
400
2/0 - 500
(2) 3/0 - 250
LD05550
Optional Field
Provided 115-1-60
Micropanel Supply
See Note 3
See page 56 for notes.
Technical Data
Summary of Contents for YCAS0098EB
Page 50: ...50 JOHNSON CONTROLS This page intentionally left blank...
Page 61: ...61 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank 7...
Page 70: ...70 JOHNSON CONTROLS Technical Data FIG 22A CONTROL PANEL COMPONENT LOCATIONS...
Page 71: ...71 JOHNSON CONTROLS FORM 201 18 NM7 LD03280 FIG 22B POWER PANEL COMPONENT LOCATION 7...
Page 72: ...72 JOHNSON CONTROLS Technical Data LEGEND LD03281...
Page 73: ...73 JOHNSON CONTROLS FORM 201 18 NM7 LD03282 LD03283 LD03284 7...
Page 74: ...74 JOHNSON CONTROLS Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06256 LD03231 LD03232...
Page 75: ...75 JOHNSON CONTROLS FORM 201 18 NM7 COMPRESSOR TERMINAL BOX LD03233 7...
Page 76: ...76 JOHNSON CONTROLS LD03285 Technical Data...
Page 77: ...77 JOHNSON CONTROLS FORM 201 18 NM7 3 4 5 6 3 4 5 6 7 8 5 6 3 4 7 8 9 10 LD06840A 7...
Page 181: ...181 JOHNSON CONTROLS FORM 201 18 NM7 NOTES...
Page 182: ...182 JOHNSON CONTROLS This page intentionally left blank...
Page 183: ...183 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank...