119
JOHNSON CONTROLS
FORM 201.18-NM7
5. Program the required operating values into the
micro for cut-outs, safeties, etc. and record them
in the chart below. See Page 160 for details.
If Default Values are desired for programming
convenience, press the PROGRAM key, 6140,
and ENTER. This loads default values. Record
these values in the chart below.
PROGRAMMED VALUES
Refrigerant Type =
__________________________
Dischg Press Cutout =
______________PSIG (kPa)
Disch Press Unld =
________________PSIG (kPa)
Suction Press Cutout =
_____________PSIG (kPa)
High Amb Cutout =
____________________
°F (°C)
Low Amb Cutout =
____________________
°F (°C)
Leaving Chilled Liquid Temp Cutout =
_____
°F (°C)
High Motor Current Unload =
____________ % FLA
Anti-Recycle Time =
____________________Secs
6. Program the Chilled Liquid Setpoint/Range and
record:
Setpoint = __________________ °F (°C)
Range = ________ to ________ °F (°C)
Keep in mind that the Target temperature dis-
played by the micro should equal the desired
leaving water temperature.
7. Assure that the CLK jumper J18 on the Micro-
processor Board is in the ON position (Top 2
pins).
8. Set the Time and Date.
9. Program the Daily Schedule start and stop times.
Panel Checks
(Power ON – Both System Switches “OFF”)
1. Apply 3-phase power and verify its value (See
Fig. 8 and 9 pages 35 and 36).
2. Apply 115VAC and verify its value on the ter-
minal block in the lower left of the Power Panel.
Make the measurement between terminals 5 and
2 (See Fig. 13, page 40). The voltage should be
/- 10%.
3. Assure the heaters on each compressor are on.
Allow the compressor heaters to remain on a
minimum of 24 hours before start- up. This is
important to assure that no refrigerant is in the
compressor oil at start-up!
4. Program the dip switches on the microprocessor
board for the desired operating requirements. See
Fig. 49, Page 143. OPEN = Left side of switch
pushed down. CLOSED = Right side of switch
pushed down.
Verify the selections by pressing the OPTIONS
Key on the control panel. Check them off.
Damage to the chiller could result if
switches are improperly programmed.
Dip switches 4 through 8 are spares
and have no function.
SWITCH
SWITCH “OPEN” SWITCH “CLOSED”
SETTING SETTING
1
Water Cooling
Brine Cooling
2
Standard Ambient
Low Ambient
Control Control
3
Refrigerant R-407C
Refrigerant R-22
7
Summary of Contents for YCAS0098EB
Page 50: ...50 JOHNSON CONTROLS This page intentionally left blank...
Page 61: ...61 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank 7...
Page 70: ...70 JOHNSON CONTROLS Technical Data FIG 22A CONTROL PANEL COMPONENT LOCATIONS...
Page 71: ...71 JOHNSON CONTROLS FORM 201 18 NM7 LD03280 FIG 22B POWER PANEL COMPONENT LOCATION 7...
Page 72: ...72 JOHNSON CONTROLS Technical Data LEGEND LD03281...
Page 73: ...73 JOHNSON CONTROLS FORM 201 18 NM7 LD03282 LD03283 LD03284 7...
Page 74: ...74 JOHNSON CONTROLS Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06256 LD03231 LD03232...
Page 75: ...75 JOHNSON CONTROLS FORM 201 18 NM7 COMPRESSOR TERMINAL BOX LD03233 7...
Page 76: ...76 JOHNSON CONTROLS LD03285 Technical Data...
Page 77: ...77 JOHNSON CONTROLS FORM 201 18 NM7 3 4 5 6 3 4 5 6 7 8 5 6 3 4 7 8 9 10 LD06840A 7...
Page 181: ...181 JOHNSON CONTROLS FORM 201 18 NM7 NOTES...
Page 182: ...182 JOHNSON CONTROLS This page intentionally left blank...
Page 183: ...183 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank...