168
JOHNSON CONTROLS
If discharge pressure drops below 120 PSIG or oil to
suction pressure differential falls below 75 PSID, the
micro will turn off a step of fan cycling every 5 seconds:
until the discharge pressure rises above 120 PSIG and
oil to suction pressure differential rises above 75 PSID
in an effort to quickly control the discharge pressure to
an acceptable range.
TABLE 3 –
CONDENSER FAN CONTROL AND FAN CONTACTOR DATA FOR DXST UNITS
WITH 4 FANS/SYSTEM (EPROM VERSIONS C.ACS.09.01 (F350) AND C.ACS.09.02 (3902)
* Sys 1 Outputs are on Relay Output Board #1
Sys 2 Outputs are on Relay Output Board #2
Fan
ON *
OFF *
Fan
Wire
Relay
Stage
Fans
Conditions
Conditions
Contactor
Number
Board
DP
DP & OAT
Output*
1
1
>220 PSIG
<150 PSIG & <60°F
9M
130
15
S
2
3
>235 PSIG
<165 PSIG & <65°F
10M
131
14
Y
3
5
>250 PSIG
<180 PSIG & <70°F
11M
132
10
S
4
1, 5
>265 PSIG
<195 PSIG & <75°F
9M, 11M
130, 132
10,15
5
3, 5
>280 PSIG
<210 PSIG & <80°F
10M, 11M
131, 132
10, 14
1
6
1, 3, 5
>290 PSIG
<220 PSIG & <85°F
9M, 10M, 11M
130, 131, 132
10, 14, 15
1
2
>220 PSIG
<150 PSIG & <60°F
15M
230
15
S
2
4
>235 PSIG
<165 PSIG & <65°F
16M
231
14
Y
3
6
>250 PSIG
<180 PSIG & <70°F
17M
232
10
S
4
2, 6
>265 PSIG
<195 PSIG & <75°F
15M, 17M
230, 232
10, 15
5
4, 6
>280 PSIG
<210 PSIG & <80°F
16M, 17M
231, 232
10, 14
2
6
2, 4, 6
>290 PSIG
<220 PSIG & <85°F
15M, 16M, 17M
230, 231, 232
10, 14, 15
Table 5 provides a simplified operating graph of the fan
staging for this version.
Fan stages increment identical to the stages shown in
Table 3.
TABLE 4 –
CONDENSER FAN CONTROL AND FAN CONTACTOR DATA FOR DXST UNITS
WITH 5 FANS/SYSTEM (EPROM VERSION C.A17.09.02 (5320)
* Sys 1 Outputs are on Relay Board #1
Sys 2 Outputs are on Relay Output Board #2
Fan
ON *
OFF *
Fan
Wire
Relay
Stage
Fans
Conditions
Conditions
Contactor
Number
Board
DP
DP & OAT
Output*
1
1
>205 PSIG
<135 PSIG & <60°F
9M
130
15
S
2
3
>220 PSIG
<150 PSIG & <65°F
10M
131
14
Y
3
5
>235 PSIG
<165 PSIG & <70°F
11M
132
10
S
4
1, 5
>250 PSIG
<180 PSIG & <75°F
9M, 11M
130, 132
10,15
5
3, 5
>265 PSIG
<195 PSIG & <80°F
10M, 11M
131, 132
10, 14
1
6
1, 3, 5
>275 PSIG
<205 PSIG & <85°F
9M, 10M, 11M
130, 131, 132
10, 14, 15
1
2
>205 PSIG
<135 PSIG & <60°F
15M
230
15
S
2
4
>220 PSIG
<150 PSIG & <65°F
16M
231
14
Y
3
6
>235 PSIG
<165 PSIG & <70°F
17M
232
10
S
4
2, 6
>250 PSIG
<180 PSIG & <75°F
15M, 17M
230, 232
10, 15
5
4, 6
>265 PSIG
<190 PSIG & <80°F
16M, 17M
231, 232
10, 14
2
6
2, 4, 6
>275 PSIG
<205 PSIG & <85°F
15M, 16M, 17M
230, 231, 232
10, 14, 15
Micro Panel Contents
Summary of Contents for YCAS0098EB
Page 50: ...50 JOHNSON CONTROLS This page intentionally left blank...
Page 61: ...61 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank 7...
Page 70: ...70 JOHNSON CONTROLS Technical Data FIG 22A CONTROL PANEL COMPONENT LOCATIONS...
Page 71: ...71 JOHNSON CONTROLS FORM 201 18 NM7 LD03280 FIG 22B POWER PANEL COMPONENT LOCATION 7...
Page 72: ...72 JOHNSON CONTROLS Technical Data LEGEND LD03281...
Page 73: ...73 JOHNSON CONTROLS FORM 201 18 NM7 LD03282 LD03283 LD03284 7...
Page 74: ...74 JOHNSON CONTROLS Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06256 LD03231 LD03232...
Page 75: ...75 JOHNSON CONTROLS FORM 201 18 NM7 COMPRESSOR TERMINAL BOX LD03233 7...
Page 76: ...76 JOHNSON CONTROLS LD03285 Technical Data...
Page 77: ...77 JOHNSON CONTROLS FORM 201 18 NM7 3 4 5 6 3 4 5 6 7 8 5 6 3 4 7 8 9 10 LD06840A 7...
Page 181: ...181 JOHNSON CONTROLS FORM 201 18 NM7 NOTES...
Page 182: ...182 JOHNSON CONTROLS This page intentionally left blank...
Page 183: ...183 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank...