Closed:
Low Ambient Mode allows the Low Ambient Cut-Out
to be programmed from 0 to 50 °F (-18 to 10°C). Values
above 25°F (-4°C) can be used to automatically shut
down the chiller when direct cooling methods become
operational.
SWITCH 3: Refrigerant
Open:
The R-407C Mode MUST be selected for models using
refrigerant R-407C. Incorrect selection of this switch
may cause serious damage to the chiller.
Closed:
The R-22 Mode MUST be selected for models using
refrigerant type R-22. Incorrect selection of this switch
may cause serious damage to the chiller.
SWITCH 4: Unit Type
Open:
S 1 - 4 U N I T T Y P E
Y C
W
S
Set this switch to Open if the chiller type is YCWS.
Closed:
S 1 - 4 U N I T T Y P E
Y
C
A
S
Set this switch to Closed if the chiller type is YCAS.
S 1 - 2 A M B I E N T C O N T R O L
L O
W A
M
B I E N T
S 1 - 3 R E F R I G E R A N T
R - 4 0 7 C
S 1 - 3 R E F R I G E R A N T
R - 2 2
8
SWITCH 5: Motor Current Averaging
Open:
S 1 - 5 M O T O R C U R R E N T A V E R A G I N G
D O N O T U S E
If do not use “motor current averaging”, set this switch
to Open.
Closed:
S 1 - 5 M O T O R C U R R E N T A V E R A G I N G
A V G. D I S A B L E
If need to disable “motor current averaging”, set this
switch to Closed.
SWITCH 6: Heat Recovery
Open:
S 1 - 6 H E A T R E C O V E R Y
D I S A B L E D
Set this switch to Open if no “heat recovery” or do not
need to use it.
Closed:
S 1 - 6 H E A T R E C O V E R Y
E N A B L E D
Set this switch to Closed if chiller with “heat recovery”
and need to use it.
SWITCH 7: Exp. Valve Type
Open:
S 1 - 7 E X P. V A L V E T Y P E
T H E R
M
O
S T A T I C
If TXV is used, set this switch to Open position.
Closed:
S 1 - 7 E X P. V A L V E T Y P E
E L E C T R
O
N I C
If EEV is used, set this switch to Closed position.
SWITCH 8: Spare
Summary of Contents for YCAS0098EB
Page 50: ...50 JOHNSON CONTROLS This page intentionally left blank...
Page 61: ...61 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank 7...
Page 70: ...70 JOHNSON CONTROLS Technical Data FIG 22A CONTROL PANEL COMPONENT LOCATIONS...
Page 71: ...71 JOHNSON CONTROLS FORM 201 18 NM7 LD03280 FIG 22B POWER PANEL COMPONENT LOCATION 7...
Page 72: ...72 JOHNSON CONTROLS Technical Data LEGEND LD03281...
Page 73: ...73 JOHNSON CONTROLS FORM 201 18 NM7 LD03282 LD03283 LD03284 7...
Page 74: ...74 JOHNSON CONTROLS Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06256 LD03231 LD03232...
Page 75: ...75 JOHNSON CONTROLS FORM 201 18 NM7 COMPRESSOR TERMINAL BOX LD03233 7...
Page 76: ...76 JOHNSON CONTROLS LD03285 Technical Data...
Page 77: ...77 JOHNSON CONTROLS FORM 201 18 NM7 3 4 5 6 3 4 5 6 7 8 5 6 3 4 7 8 9 10 LD06840A 7...
Page 181: ...181 JOHNSON CONTROLS FORM 201 18 NM7 NOTES...
Page 182: ...182 JOHNSON CONTROLS This page intentionally left blank...
Page 183: ...183 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank...