Thermal Overload
Three PTC (positive temperature coefficient) thermistors
in the motor windings of each phase provides thermal
protection. The sensor resistance stays relatively con-
stant at 1k
Ω
until a temperature of 266°F (130°C) is
sensed. The sensor experiences a rapid rise in resistance
beyond this temperature. Whenever the resistance of one
of the sensors reaches 13k
Ω
, the 2ACE module trips,
which ultimately de-energizes the motor’s pilot circuit.
Reset is manual after the motor cools and the sensor
resistance drops to 3.25k
Ω
.
Current Imbalance (Loaded & Unloaded)/
Loss of Phase
A 2 second delay at start-up allows for any imbalances
resulting during normal starting conditions. After this
initial delay, the 2ACE module compares the “Oper-
ating Current” to the measured half line current. The
“Operating Current” is given by 0.65 X factory overload
current setting.
An
unloaded compressor condition
occurs when any
measured half line current is less than the “Operating
Current.” A current imbalance exceeding an unloaded
level of 25% will result in the motor pilot circuit being
de-energized.
A
loaded compressor condition
occurs when any mea-
sured half line current is greater than or equal to the
“Operating Current.” A current imbalance exceeding a
loaded level of 17% will result in the motor pilot circuit
being de-energized.
Imbalance
is defined as
(High Phase - Low Phase)/High Phase
Improper Phase Sequence
The 2ACE module calculates the phase sequence at
start-up using the three current transformers to deter-
mine whether the three phase sequence on the load
side of the main contactor is miswired. Upon detection
of a miswired motor load, the module will de-energize
the main contactor pilot circuit within 50 millisecond
response time.
2
Summary of Contents for YCAS0098EB
Page 50: ...50 JOHNSON CONTROLS This page intentionally left blank...
Page 61: ...61 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank 7...
Page 70: ...70 JOHNSON CONTROLS Technical Data FIG 22A CONTROL PANEL COMPONENT LOCATIONS...
Page 71: ...71 JOHNSON CONTROLS FORM 201 18 NM7 LD03280 FIG 22B POWER PANEL COMPONENT LOCATION 7...
Page 72: ...72 JOHNSON CONTROLS Technical Data LEGEND LD03281...
Page 73: ...73 JOHNSON CONTROLS FORM 201 18 NM7 LD03282 LD03283 LD03284 7...
Page 74: ...74 JOHNSON CONTROLS Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06256 LD03231 LD03232...
Page 75: ...75 JOHNSON CONTROLS FORM 201 18 NM7 COMPRESSOR TERMINAL BOX LD03233 7...
Page 76: ...76 JOHNSON CONTROLS LD03285 Technical Data...
Page 77: ...77 JOHNSON CONTROLS FORM 201 18 NM7 3 4 5 6 3 4 5 6 7 8 5 6 3 4 7 8 9 10 LD06840A 7...
Page 181: ...181 JOHNSON CONTROLS FORM 201 18 NM7 NOTES...
Page 182: ...182 JOHNSON CONTROLS This page intentionally left blank...
Page 183: ...183 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank...