PROBLEM
CAUSE
SOLUTION
Compressor wont
1. Suction pressure > programmed
1. Excessive load. Check OPERATING
load
unload point or operating limitations
LIMITATIONS. Check programmed
(Solenoid valve
have been exceeded.
unloading point.
de-energizes to load
2. Discharge pressure > programmed
2. Check OPERATING LIMITATIONS.
compressor
load point or operating limitations
Check programmed unloading point.
have been exceeded.
3. Demand not great enough.
3. OK. Become familiar with control
operating
4. Defective loading solenoid.
4. Replace compressor loading solenoid.
5. Faulty wiring to loading solenoid.
5. Check wiring.
6. Defective water temperature sensor.
6. Compare sensor with a thermometer.
Variation of sensor vs. thermometer of
+2°F is not unusual. Replace if necessary.
7. Defective evaporator or optional
7. Replace transducer after verifying with a
discharge transducer.
gauge.
Lack of Cooling
1. Fouled evaporator surface.
1. Contact the local YORK service
Effect
representative.
2. Faulty compressor suction and/or
2. Contact the local YORK service
discharge valves.
representative.