FORM 150.60-NM3
59
YORK INTERNATIONAL
This message informs the operator that the micro has
commanded the auxiliary contacts (optional) for the con-
denser water pump to close.
History
The HISTORY key also allows the user to scroll through
the SAFETY SHUTDOWN buffers to display information
relating to the last 3 Safety Shutdowns which occurred.
Information contained in the SAFETY SHUTDOWN Buff-
ers is very important when attempting to troubleshoot a
system problem. This data reflects system conditions at
the
instant
the fault occcured.
Information is stored in the SAFETY SHUTDOWN Buff-
ers on every fault regardless of whether the fault caused
a Lockout to occur. The information is also not affected
by power failures (long term internal memory battery
back-up is built into the circuit board) or manual resetting
of a fault lock-out.
When the HISTORY key is passed, the following mes-
sage will appear.
The operator must then select which SAFETY SHUT-
DOWN Buffer is desired. When deciding this, keep in
mind that Buffer No. 1 is always the most recent fault. As
new fault information is stored, it is always placed in
Buffer No. 1, No. 1 is loaded to No. 2, No. 2 is loaded to
No. 3, and information previously in No. 3 is discarded.
To select a buffer, simply press the 1, 2, or 3 ENTRY
key and press ENTER. Repetitively pressing the ENTER
key will allow the operator to scroll through the informa-
tion available in the SAFETY SHUTDOWN Buffer.
In the information that follows, a sample message along
with an explanation is provided for all available mes-
sages.
This message informs the operator of the time and date
of the fault.
This message informs the operator of the nature of the
fault which occurred.
This message indicates the Return Water Temperature
at the time of the fault.
This message indicates the Leaving Water Temperature
at the time of the fault.
This display shows the Low Water Cut-out (Leaving)
which was programmed at the time of the fault.
This display shows the Setpoint Temp which was pro-
grammed at the time of the fault.
This message indicates the Outdoor Ambient Tempera-
ture at the time of the fault.
This display shows the Low Ambient Cut-out pro-
grammed at the time of the fault.
This display shows the Low Pressure Cut-out pro-
grammed at the time of the fault.
C O N D E N S E R
W A T E R
P U M P
S T A T U S
O F F
D I S P L A Y
S A F E T Y
S H U T
D O W N
N O . 1
( 1
T O
3 )
S H U T D O W N
O C C U R R E D
3 : 2 4 P M
3 / 1 2 / 9 1
S Y S # 1
L O W
O I L
P R E S S
S Y S # 2
N O
F A U L T S
R E T U R N
W A T E R
T E M P
5 2 . 7
D E G F
L E A V I N G
W A T E R
T E M P
4 4 . 3
D E G F
L O W
W A T E R
C U T O U T
3 6 . 0
D E G F
S E T P O I N T
T E M P
4 4 . 0
D E G F
O U T S I D E
A I R
T E M P
7 7 . 6
D E G F
L O W
A M B I E N T
C U T O U T
3 5 . 0
P S I G
L O W
P R E S S U R E
C U T O U T
4 4
P S I G
Summary of Contents for YCAJ44HE8
Page 16: ...16 YORK INTERNATIONAL WIRING DIAGRAMS LD02165 FIG 5 ELEMENTARY DIAGRAM...
Page 17: ...FORM 150 60 NM3 17 YORK INTERNATIONAL FIG 5 ELEMENTARY DIAGRAM Cont d LD02166...
Page 20: ...20 YORK INTERNATIONAL CONNECTION DIAGRAM ELECTRICAL BOX FIG 7 CONNECTION DIAGRAM LD02171...
Page 21: ...FORM 150 60 NM3 21 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02172...