FORM 150.60-NM3
61
YORK INTERNATIONAL
This message indicates the number of fans on SYS 1
which were running in the reverse direction at the time of
the fault. *
This display indicates whether the Hot Gas Solenoid
Valve was energized on SYS 1 at the time of the fault.
NOTE: The micro will attempt to control the Hot Gas,
Solenoid Valve regardless of whether the option
is installed.
This message indicates whether Compressor 2 was ON
or OFF at the time of the fault.
This message indicates SYS 2 motor current at the time
of the fault.
This display shows the suction pressure of SYS 2 at the
time of the fault.
This message indicates SYS 2 discharge pressure at
the time of the fault. This display will be a fixed value
unless the Discharge Pressure Readout is installed.
This display shows the oil pressure of SYS 2 at the time
of the fault.
This display informs the operator whether SYS 2 liquid
line solenoid was energized (ON) or de-energized (OFF)
at the time of the fault.
This message informs the operator if SYS 2 Run Per-
missive (flow switch, remote START/STOP) was in the
RUN mode (ON) or STOP mode (OFF).
This message indicates the number of stages which
were loaded on SYS 2 at the time of the fault.
This display indicates the number of fans on SYS 2
which were running forward at the time of the fault.*
This message indicates the number of fans on SYS 2
which were running in the reverse direction at the time of
the fault. *
This display indicates whether the Hot Gas Solenoid
Valve was energized on SYS 2 at the time of the fault.
NOTE: The micro will attempt to control the Hot Gas
Solenoid Valve regardless of whether the option
is installed.
* The software designed to control fans whether or not they are present on the chiller as is the case on water cooled indoor units. If an indoor
unit exists, ignore this display.
S Y S
1
R E V E R S E
F A N S
O F F
S Y S
1
H O T
G A S
V A L V E
O F F
S Y S
2
C O M P R E S S O R
O F F
S Y S
2
M O T O R
A M P S
6 0
% F L A
S Y S
2
S U C T I O N
P R E S S
6 2
P S I G
S Y S
2
D S C H
P R E S S
2 4 0
P S I G
S Y S
2
O I L
P R E S S U R E
7 4
P S I D
S Y S
2
L I Q
L I N E
O N
S Y S
2
R U N
P E R M I S S I V E
O N
S Y S
2
L O A D I N G
S T A G E S
1
S Y S
2
F O R W A R D
F A N S
O F F
S Y S
2
R E V E R S E
F A N S
O F F
S Y S
2
H O T
G A S
V A L V E
O F F
Summary of Contents for YCAJ44HE8
Page 16: ...16 YORK INTERNATIONAL WIRING DIAGRAMS LD02165 FIG 5 ELEMENTARY DIAGRAM...
Page 17: ...FORM 150 60 NM3 17 YORK INTERNATIONAL FIG 5 ELEMENTARY DIAGRAM Cont d LD02166...
Page 20: ...20 YORK INTERNATIONAL CONNECTION DIAGRAM ELECTRICAL BOX FIG 7 CONNECTION DIAGRAM LD02171...
Page 21: ...FORM 150 60 NM3 21 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02172...