LX COMPACT SERIES INSTALLATION MANUAL

Over/Under Voltage Shutdown -

 An over/under voltage condition 

exists when the control voltage is outside the range of 18 VAC to 
30 VAC. If the over/under voltage shutdown lasts for 15 minutes, 
the lockout and alarm relay will be energized. Over/under voltage 
shutdown is self-resetting in that if the voltage comes back within 
range of 18 VAC to 30 VAC for at least 0.5 seconds, then normal 
operation is restored.

Operation Description

Power Up -

 The unit will not operate until all the inputs and safety 

controls are checked for normal conditions. The unit has a 5 to 80 
second random start delay at power up. Then the compressor has 
a 4 minute anti-short cycle delay after the random start delay.

Standby In standby mode, Y1, Y2, W, DH, and G are not active. 
Input O may be active. The blower and compressor will be off.

Heating Operation

Heating, 1st Stage (Y1) -

 The blower is started on “G” speed 

immediately and the compressor is energized 10 seconds after 
the Y1 input is received. The ECM blower motor is switched to low 
speed 15 seconds after the Y1 input.

Heating, 2nd Stage (Y1, Y2) -

 The compressor will be staged to 

full capacity 20 seconds after Y2 input is received. The ECM blower 
will shift to high speed 15 seconds after the Y2 input is received.

Heating, 3rd Stage (Y1, Y2, W) - 

The hot water pump is de-

energized and the first stage of electric heat is energized 10 
seconds after the W command is received. If the demand 
continues the second stage of electric heat will be energized after 
5 minutes.

Emergency Heat (W) -

 The blower will be started on “G” speed, 

10 seconds later the first stage of electric heat will be turned on. 5 
seconds after the first stage of electric heat is energized the blower 
will shift to Aux speed. If the emergency heat demand is not satisfied 
after 2 minutes the second electric heat stage will be energized.

Blower (G) - 

The blower will start immediately upon receiving 

a thermostat G command. If there are no other commands 
from the thermostat the ECM will run on “G” speed until the G 
command is removed. Regardless of blower input (G) from the 
thermostat, the blower will remain on for 30 seconds at the end 
of each heating cycle.

Cooling Operation

In all cooling operations, the reversing valve directly tracks the O 
input. Thus, anytime the O input is present, the reversing valve will 
be energized.

Cooling, 1st Stage (Y1, O) - 

The blower is started on “G” speed 

immediately and the compressor is energized 10 seconds after the Y1 
input is received. The ECM blower motor is switched to low speed 15 
seconds after the Y1 input.

Cooling, 2nd Stage (Y1, Y2, O) - 

The compressor will be staged to 

full capacity 20 seconds after Y2 input is received. The ECM blower 
will shift to high speed 15 seconds after the Y2 input is received.

Blower (G) -

 The blower will start immediately upon receiving a 

thermostat G command. If there are no other commands from the 
thermostat the ECM will run on “G” speed until the G command is 
removed. Regardless of blower input (G) from the thermostat, the 
blower will remain on for 30 seconds at the end of each heating, 
cooling, and emergency heat cycle.

Dehumidification (Y1, O, DH or Y1, Y2, O, DH) -

 When a DH 

command is received from the thermostat during a compressor 
call for cooling the ECM blower speed will be reduced by 15% to 
increase dehumidification.

Emergency Shutdown -

 Four (4) seconds after a valid ES input, 

P2-7 is present, all control outputs will be turned off and remain 
off until the emergency shutdown input is no longer present. The 
first time that the compressor is started after the control exits 
the emergency shutdown mode, there will be an anti-short cycle 
delay followed by a random start delay. Input must be tied to 
common to activate.

Continuous Blower Operation -

 The blower output will be 

energized any time the control has a G input present, unless the 
control has an emergency shutdown input present. The blower 
output will be turned off when G input is removed.

Load Shed -

 The LS input disables all outputs with the exception 

of the blower output. When the LS input has been cleared, the anti-
short cycle timer and random start timer will be initiated. Input must 
be tied to common to activate.

Controls - Aurora Base Control cont.

Summary of Contents for YBS006-070

Page 1: ...070 50 THRU 6 NOMINAL TONS Due to continuous product improvement specifications are subject to change without notice Visit us on the web at www yorkgeothermal com Additional rating information can fou...

Page 2: ......

Page 3: ...Electrical Connections 17 Electrical Data 18 19 Blower Performance Data 20 23 5 Speed ECM Constant Torque Motors 23 Variable Speec ECM Motors 24 Wiring Schematics 26 31 Controls Aurora Base Control 32...

Page 4: ...inted 1 in MERV 4 Filter Rack 6 Unpainted 2 in MERV 13 Filter Rack Electrical Option N No Phase Guard No Disconnect D No Phase Guard Disconnect P Phase Guard No Disconnect B Phase Guard Disconnect Air...

Page 5: ...o be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowledging the damage Safety Considerations General Installation Information WAR...

Page 6: ...pen return applications Deluxe filter rack for ductable return applications 2 61 cm Service Access Left Return Right Return Opposite Side 2 61 cm Alternate Service Access Field installed duct flange A...

Page 7: ...5 31 2 44 2 2 6 7 6 10 8 1 10 1 6 1 8 1 2 2 cm 64 8 79 2 112 3 6 6 19 3 27 4 25 4 mm 25 7 15 5 20 6 5 6 070 in 25 5 31 2 48 2 2 6 7 6 10 8 1 10 1 6 1 8 1 2 2 cm 64 8 79 2 122 4 6 6 19 3 27 4 25 4 mm 2...

Page 8: ...Front Front CMP AP CMP AP AP AIR COIL SIDE AIR COIL SIDE 1 2 in knockout 1 2 in knockout 1 in knockout 1 in knockout 1 knockout 1 in knockout 1 2 in knockout 1 2 in knockout BP BP FILTER RACK FILTER...

Page 9: ...5 5 53 0 21 2 1 8 6 8 0 8 1 in 9 2 9 1 cm 64 8 134 6 53 8 4 6 17 3 2 0 25 4 mm 23 4 23 1 Horizontal Models Discharge Connection duct flange installed 0 10 in Return Connection using deluxe filter rack...

Page 10: ...1 4 in towards the drain in both directions to facilitate the removal of condensate Horizontal Unit Mounting Use only the bolts provided in the kit to attach hanger brackets The use of longer bolts co...

Page 11: ...A04 45 8 25 1 21 4 cm 116 3 63 8 54 4 060 in 99S500A04 48 8 28 1 24 4 cm 124 0 71 4 62 0 070 in 99S500A04 53 8 28 1 24 4 cm 136 7 71 4 62 0 09 26 12 Weight Distribution Table Model Vertical Shipping W...

Page 12: ...tly and efficiently To maximize sound attenuation of the unit blower the supply and return plenums should include an internal duct liner of fiberglass or constructed of ductboard for the first few fee...

Page 13: ...m 10 50 ppm Less than 1 ppm Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm Chlorine Less than 0 5 ppm Less than 0 5 ppm Less than 0 5 ppm Chlorides Less than 20 ppm Less than 125 ppm L...

Page 14: ...precautions should be taken to protect the system from dirty water conditions Dirty water will result in system wide degradation of performance and solids may clog valves strainers flow regulators etc...

Page 15: ...should be used The valve should be sized for full flow Open System Groundwater Application Flexible Duct Collar Vibration Absorbing Pad P T Plugs Drain Low Voltage to Thermostat and Valve Unit Supply...

Page 16: ...circuit board for applications using a closed loop antifreeze solution to 15 F 9 4 C On applications using an open loop ground water system or closed loop no antifreeze set this dip switch to 30 F 1 1...

Page 17: ...e voltage wires to L1 and L2 of the contactor for single phase unit Consult the Electrical Data tables for correct fuse sizes Aurora Base Control Box Electrical Connections 208 Volt Operation All LX C...

Page 18: ...0 60 3 187 253 13 9 8 9 58 0 1 5 10 4 12 6 20 460 60 3 414 506 6 5 4 2 28 0 1 0 5 2 6 3 10 15 036 208 230 60 1 187 253 22 0 14 1 77 0 2 2 16 3 19 8 30 265 60 1 238 292 19 0 12 2 72 0 1 1 13 3 16 4 25...

Page 19: ...8 230 60 1 187 253 22 0 14 1 77 0 4 1 18 2 21 7 35 265 60 1 238 292 19 0 12 2 72 0 3 6 15 8 18 9 30 208 230 60 3 187 253 14 0 9 0 71 0 4 1 13 1 15 4 20 460 60 3 414 506 8 8 5 6 38 0 2 1 7 7 9 1 10 15...

Page 20: ...8 9 58 0 4 0 12 9 15 1 20 460 60 3 414 506 6 5 4 2 28 0 4 1 8 3 9 4 10 15 036 208 230 60 1 187 253 22 0 14 1 77 0 4 0 18 1 21 6 35 265 60 1 238 292 19 0 12 2 72 0 4 1 16 3 19 4 30 208 230 60 3 187 25...

Page 21: ...375 L 620 610 600 590 575 550 525 490 455 395 340 290 024 H 9 x 7 1 5 1035 1015 995 970 950 925 900 865 835 795 760 685 560 M 880 860 845 820 805 785 765 740 720 690 665 590 530 L 810 790 775 755 740...

Page 22: ...9 x 7 1 2 1285 1250 1215 1180 1150 1115 1085 1055 1025 980 940 875 600 510 Med High 4 1225 1195 1170 1140 1115 1085 1045 1020 995 955 920 855 585 495 Med 3 1120 1100 1085 1070 1055 1040 1030 995 960 9...

Page 23: ...but the motor speed is energized by 24VAC Power Connection 3 16 in quick connects Line 1 orange wire to L Ground green wire to G Line 2 for 208V 230V units to N brown wire Signal Connection 1 4 in qui...

Page 24: ...7 1 2 400 500 600 700 875 1050 1150 1250 1325 1375 L M H 042 0 50 11 x 10 1 2 500 600 700 875 1050 1150 1250 1325 1375 1475 1550 L M H 048 0 50 11 x 10 1 2 500 600 700 875 1050 1150 1250 1325 1375 14...

Page 25: ...een and then select ECM Setup This screen displays the current variable speed ECM settings It allows the technician to enter the setup screens to change the variable speed ECM settings Change the high...

Page 26: ...1 3 Isolation Valve Red 51 Green 50 White 52 Note 3 Note 3 RV HP LP T FD RV Blue 07 Blue 08 Black 09 Black 10 Yellow Yellow Red 53 24V CFM P13 P4 SW1 P5 JW2 P9 LO O B Y2 W DH P8 P7 RS485 NET RS485 NE...

Page 27: ...5 Flash Code 8 Flash Code 6 Flash Code 7 Flash Code 9 Flash Code 10 Flash Code 11 ECM Configure Mode Fast Flash Reset Configure Mode Off Fuse SW1 Push button SW2 DIP package 8 position RB Blower Relay...

Page 28: ...94 Brown Orange Red 56 Blue 55 Black 54 Red 56 Blue 55 Black 54 CC 470 470 Resistor Violet 14 Black 15 Orange 01 Orange 02 Condensate Brown 23 Green RV HP LP T FD RV Blue 07 Blue 08 Black 09 Black 10...

Page 29: ...art Up Bypass Low Pressure Fault RecognitionDelay Low Pressure Start Up Bypass Low Water Air Coil Limit Fault RecognitionDelay Low Water Air Coil Limit Fault RecognitionDelay Condensate Overflow Therm...

Page 30: ...G Green 93 Red 97 1 2 3 L N G X13 Fan Motor C 4 5 Green Orange Brown Tan 31 Gray 30 Blue 33 Red 32 Black 35 Black White Black White Yellow LED4 LED5 G G UltraTech Dual Capacity Units Only RCP CS Blue...

Page 31: ...Terminal FieldWiringLug Ground Relay Contacts N O N C FieldZoneSensor Wiring Legend L1 Capacitor T 1 2 3 CC Compressor Contactor CO Condensate OverflowSensor ES Emergency Shutdown HP High PressureSwi...

Page 32: ...LED1 red will flash the last lockout one time Test mode will automatically time out after 30 minutes Test mode can be exited by pressing and holding the SW1 button for 2 to 5 seconds or by cycling the...

Page 33: ...lt type identification display LED1 Red shall flash the fault code To reset lockout conditions with SW2 8 On thermostat inputs Y1 Y2 and W must be removed for at least 3 seconds To reset lockout condi...

Page 34: ...e ECM will run on G speed until the G command is removed Regardless of blower input G from the thermostat the blower will remain on for 30 seconds at the end of each heating cycle Cooling Operation In...

Page 35: ...ool simply plugs into the exterior of the cabinet in the AID Tool port ABC Control Board Layout Aurora Base Control LED Displays These three LEDs display the status configuration and fault codes for t...

Page 36: ...water flow rate is correct by measuring the pressure drop through the heat exchanger using the P T plugs and comparing to the pressure drop table 6 Check the temperature of both the supply and discha...

Page 37: ...inimum or maximum levels the other two factors must be at the normal level for proper and reliable unit operation Entering Water Temp F Water Flow GPM ton Cooling Suction Pressure psig Discharge Press...

Page 38: ...8 0 12 9 10 9 9 5 8 8 7 9 8 0 11 0 0 53 030 4 0 2 4 2 3 2 2 2 0 1 8 3 4 4 0 10 1 0 16 6 0 5 1 4 9 4 7 4 5 4 3 6 0 10 6 0 32 8 0 7 8 7 5 7 1 6 9 6 7 8 0 11 0 0 53 10 0 10 5 10 1 9 6 9 3 8 9 10 0 11 5 0...

Page 39: ...Low Low High High Low Low Scaled Coaxial Heat Exchanger Heating Low Low Low Normal Low High Low Low Scaled Coaxial Heat Exchanger Cooling High High High Normal Low Low Low Low Restricted Filter Drier...

Page 40: ...8 28 8 4 5 13 2 16 5 20 5 22 9 33 1 33 0 31 3 28 8 26 1 6 0 11 9 17 2 20 8 23 3 33 3 33 4 31 7 29 1 26 3 030 4 0 19 9 25 4 31 0 39 9 37 4 34 8 6 0 16 1 20 7 26 5 31 5 39 0 40 3 37 7 34 8 31 4 8 0 14 5...

Page 41: ...PSI and feet of water EAT entering air temperature Fahrenheit dry bulb wet bulb HC air heating capacity MBtu h TC total cooling capacity MBtu h SC sensible cooling capacity MBtu h KW total power unit...

Page 42: ...connect power Check continuity with ohm meter If the winding is open replace the compressor If sufficient cooling or heating is not obtained 1 Check control for improper location or setting 2 Check fo...

Page 43: ..._____ VOLTS Total Amps Comp Fan n _____ AMPS n ______ AMPS Watts m x n x 0 85 o _____ WATTS o ______ WATTS 6 CAPACITY Cooling Capacity HR o x 3 413 p _____ btu hr Heating Capacity HE o x 3 413 p _____...

Page 44: ...ormance problem Line Voltage Loop Open Unit Amp Draw Closed COAX SOURCE HEA7 1 ANALYSIS EXPANSION VALVE F AIR COIL F COMPRESSOR DISCHARGE SUCTION Subcooling Superheat REVERSING VALVE PSI F SAT F PSI S...

Page 45: ...en necessary Units should never be operated without a filter Condensate Drain In areas where airborne bacteria produce a slime in the drain pan it may be necessary to treat chemically to minimize the...

Page 46: ...46 LX COMPACT SERIES INSTALLATION MANUAL Notes...

Page 47: ...47 LX COMPACT SERIES INSTALLATION MANUAL Pages Description Date By All Document Creation 10 Aug 2018 JM Revision Guide...

Page 48: ...eries Type Geothermal Water Source Heat Pumps Size 0 50 6 Ton Document Type Part Number Release Date Installation Manual IM1202AK6 08 18 2018 The manufacturer has a policy of continual product researc...

Reviews: