LX COMPACT SERIES INSTALLATION MANUAL
Blower Performance Data cont.
Variable Speed ECM Motor
Model
Max
Blower
Size
Motor
hp
Air Flow Dip Switch Settings
ESP
1
2
3
4
5
6
7
8
9
10
11
12
015
0.50
9 x 7
1/2
300
400
500
600
700
800
L
M
H
018
0.50
9 x 7
1/2
300
400
500
600
700
800
L
M
H
024
0.50
9 x 7
1/2
400
500
600
700
800
900
1000
1100
L
M
H
030
0.50
9 x 7
1/2
400
500
600
700
800
900
1000
1100
L
M
H
036
0.50
9 x 7
1/2
400
500
600
700
800
900
1000
1100
1200
L
M H
041
0.50
9 x 7
1/2
400
500
600
700
875
1050
1150
1250
1325
1375
L
M
H
042
0.50
11 x 10
1/2
500
600
700
875
1050
1150
1250
1325
1375
1475
1550
L
M
H
048
0.50
11 x 10
1/2
500
600
700
875
1050
1150
1250
1325
1375
1475
1550
1600
L
M
H
060
0.75
11 x 10
1
600
800
1000
1300
1500
1750
1950
2100
2200
2300
L
M
H
070
0.75
11 x 10
1
600
800
1000
1300
1500
1750
1950
2100
2200
2300
L
M
H
Factory settings are at recommended L-M-H DIP switch locations 10/15/15
CFM is controlled within ±5% up to the maximum ESP
M-H settings MUST be located within boldface CFM range
Max ESP includes allowance for wet coil and standard fi lter
Lowest and Highest DIP switch settings are assumed to be L and H respectively