LX COMPACT SERIES INSTALLATION MANUAL

Aurora ‘Base’ Control

NOTE:

 Refer to the Aurora Base Control Application and 

Troubleshooting Guide and the Instruction Guide: Aurora Interface and 
Diagnostics (AID) Tool for additional information.

Control Features

Software ABC Standard Version 2.0

Single or Dual Capacity Compressors

Either single or dual capacity compressors can be operated.

ECM Blower Motor Option

An ECM blower motor can be driven directly using the onboard 
PWM output. Four blower speeds are available based upon the 
G, Y1, Y2, and W input signals to the board. The blower speeds 
can be changed either by the ECM manual configurations mode 
method or by using the Aurora AID Tool directly. All four blower 
speeds can be set to the same speed if desired. 

5-Speed ECM Blower Motor Option

A 5-Speed ECM blower motor will be driven directly using the 
thermostat connections. Any of the G, Y1, or Y2/W signals can 
drive any of the 5 available pre-programmed blower speeds on 
the motor.

Other Control Features

•  Random start at power up
•  Anti-short cycle protection
•  High and low pressure cutouts
•  Loss of charge
•  Water coil freeze detection
•  Air coil freeze detection
•  Over/under voltage protection
•  Condensate overflow sensor
• Load shed
•  Dehumidification (where applicable)
• Emergency shutdown
•  Hot gas reheat operation (where applicable)
• Diagnostic LED
•  Test mode push button switch
•  Two auxiliary electric heat outputs
• Alarm output
•  Accessory output with N.O. and N.C.
•  Modbus communication (master)
•  Modbus communication (slave)

Field Selectable Options via Hardware

DIP Switch (SW1)

 

– Test/Configuration Button (See SW1 

Operation Table)

Test Mode

The control is placed in the test mode by holding the push button 
switch SW1 for 2 - 5 seconds. In test mode most of the control 
timings will be shortened by a factor of sixteen (16). LED3 (green) 
will flash at 1 second on and 1 second off. Additionally, when 
entering test mode LED1 (red) will flash the last lockout one 
time. Test mode will automatically time out after 30 minutes. Test 
mode can be exited by pressing and holding the SW1 button for 
2 to 5 seconds or by cycling the power. 

NOTE: 

Test mode will 

automatically be exited after 30 minutes.

ECM Configuration Mode

The control is placed in the ECM configuration mode by holding 
the pushbutton switch SW1 for 5 to 10 seconds, the high, low, 
and “G” ECM speeds can be selected by following the LED 
display lights. LED2 (yellow) will fast flash when entering the 
ECM configuration. When setting “G” speed LED3 (green) will 
be continuously lit, for low speed LED1 (red) will be continuously 
lit, and for high speed both LED3 (green) and LED1 (red) will be 
continuously lit. During the ECM configuration mode LED2 (yellow) 
will flash each of the 12 possible blower speeds 3 times. When 
the desired speed is flashed press SW1, LED2 will fast flash until 
SW1 is released. “G” speed has now been selected. Next select 
low speed, and high speed blower selections following the same 
process above. After third selection has been made, the control 
will exit the ECM configuration mode. Aux fan speed will remain at 
default or current setting and requires the AID Tool for adjustment.

Reset Configuration Mode

The control is placed in reset configuration mode by holding the 
push button switch SW1 for 50 to 60 seconds. This will reset 
all configuration settings and the EEPROM back to the factory 
default settings. LED3 (green) will turn off when entering reset 
configuration mode. Once LED3 (green) turns off, release SW1 
and the control will reset.

DIP Switch (SW2) 

SW2-1

  FP1 Selection – Low water coil temperature limit setting 

for freeze detection. On = 30°F; Off = 15°F.

SW2-2

  FP2 Selection – On = 30°F; Off = N/A

SW2-3

  RV – O/B - thermostat type. Heat pump thermostats 

with “O” output in cooling or “B” output in Heating can be 
selected. On = O;   Off = B.

SW2-4

  Access Relay Operation (P2)

and 2-5

Access Relay Operation

SW2-4

SW2-5

Cycle with Blower

ON

ON

Cycle with Compressor

OFF

OFF

Water Valve Slow Opening

ON

OFF

Cycle with Comm. T-stat Hum Cmd

OFF

ON

Controls - Aurora Base Control

Summary of Contents for YBS006-070

Page 1: ...070 50 THRU 6 NOMINAL TONS Due to continuous product improvement specifications are subject to change without notice Visit us on the web at www yorkgeothermal com Additional rating information can fou...

Page 2: ......

Page 3: ...Electrical Connections 17 Electrical Data 18 19 Blower Performance Data 20 23 5 Speed ECM Constant Torque Motors 23 Variable Speec ECM Motors 24 Wiring Schematics 26 31 Controls Aurora Base Control 32...

Page 4: ...inted 1 in MERV 4 Filter Rack 6 Unpainted 2 in MERV 13 Filter Rack Electrical Option N No Phase Guard No Disconnect D No Phase Guard Disconnect P Phase Guard No Disconnect B Phase Guard Disconnect Air...

Page 5: ...o be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowledging the damage Safety Considerations General Installation Information WAR...

Page 6: ...pen return applications Deluxe filter rack for ductable return applications 2 61 cm Service Access Left Return Right Return Opposite Side 2 61 cm Alternate Service Access Field installed duct flange A...

Page 7: ...5 31 2 44 2 2 6 7 6 10 8 1 10 1 6 1 8 1 2 2 cm 64 8 79 2 112 3 6 6 19 3 27 4 25 4 mm 25 7 15 5 20 6 5 6 070 in 25 5 31 2 48 2 2 6 7 6 10 8 1 10 1 6 1 8 1 2 2 cm 64 8 79 2 122 4 6 6 19 3 27 4 25 4 mm 2...

Page 8: ...Front Front CMP AP CMP AP AP AIR COIL SIDE AIR COIL SIDE 1 2 in knockout 1 2 in knockout 1 in knockout 1 in knockout 1 knockout 1 in knockout 1 2 in knockout 1 2 in knockout BP BP FILTER RACK FILTER...

Page 9: ...5 5 53 0 21 2 1 8 6 8 0 8 1 in 9 2 9 1 cm 64 8 134 6 53 8 4 6 17 3 2 0 25 4 mm 23 4 23 1 Horizontal Models Discharge Connection duct flange installed 0 10 in Return Connection using deluxe filter rack...

Page 10: ...1 4 in towards the drain in both directions to facilitate the removal of condensate Horizontal Unit Mounting Use only the bolts provided in the kit to attach hanger brackets The use of longer bolts co...

Page 11: ...A04 45 8 25 1 21 4 cm 116 3 63 8 54 4 060 in 99S500A04 48 8 28 1 24 4 cm 124 0 71 4 62 0 070 in 99S500A04 53 8 28 1 24 4 cm 136 7 71 4 62 0 09 26 12 Weight Distribution Table Model Vertical Shipping W...

Page 12: ...tly and efficiently To maximize sound attenuation of the unit blower the supply and return plenums should include an internal duct liner of fiberglass or constructed of ductboard for the first few fee...

Page 13: ...m 10 50 ppm Less than 1 ppm Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm Chlorine Less than 0 5 ppm Less than 0 5 ppm Less than 0 5 ppm Chlorides Less than 20 ppm Less than 125 ppm L...

Page 14: ...precautions should be taken to protect the system from dirty water conditions Dirty water will result in system wide degradation of performance and solids may clog valves strainers flow regulators etc...

Page 15: ...should be used The valve should be sized for full flow Open System Groundwater Application Flexible Duct Collar Vibration Absorbing Pad P T Plugs Drain Low Voltage to Thermostat and Valve Unit Supply...

Page 16: ...circuit board for applications using a closed loop antifreeze solution to 15 F 9 4 C On applications using an open loop ground water system or closed loop no antifreeze set this dip switch to 30 F 1 1...

Page 17: ...e voltage wires to L1 and L2 of the contactor for single phase unit Consult the Electrical Data tables for correct fuse sizes Aurora Base Control Box Electrical Connections 208 Volt Operation All LX C...

Page 18: ...0 60 3 187 253 13 9 8 9 58 0 1 5 10 4 12 6 20 460 60 3 414 506 6 5 4 2 28 0 1 0 5 2 6 3 10 15 036 208 230 60 1 187 253 22 0 14 1 77 0 2 2 16 3 19 8 30 265 60 1 238 292 19 0 12 2 72 0 1 1 13 3 16 4 25...

Page 19: ...8 230 60 1 187 253 22 0 14 1 77 0 4 1 18 2 21 7 35 265 60 1 238 292 19 0 12 2 72 0 3 6 15 8 18 9 30 208 230 60 3 187 253 14 0 9 0 71 0 4 1 13 1 15 4 20 460 60 3 414 506 8 8 5 6 38 0 2 1 7 7 9 1 10 15...

Page 20: ...8 9 58 0 4 0 12 9 15 1 20 460 60 3 414 506 6 5 4 2 28 0 4 1 8 3 9 4 10 15 036 208 230 60 1 187 253 22 0 14 1 77 0 4 0 18 1 21 6 35 265 60 1 238 292 19 0 12 2 72 0 4 1 16 3 19 4 30 208 230 60 3 187 25...

Page 21: ...375 L 620 610 600 590 575 550 525 490 455 395 340 290 024 H 9 x 7 1 5 1035 1015 995 970 950 925 900 865 835 795 760 685 560 M 880 860 845 820 805 785 765 740 720 690 665 590 530 L 810 790 775 755 740...

Page 22: ...9 x 7 1 2 1285 1250 1215 1180 1150 1115 1085 1055 1025 980 940 875 600 510 Med High 4 1225 1195 1170 1140 1115 1085 1045 1020 995 955 920 855 585 495 Med 3 1120 1100 1085 1070 1055 1040 1030 995 960 9...

Page 23: ...but the motor speed is energized by 24VAC Power Connection 3 16 in quick connects Line 1 orange wire to L Ground green wire to G Line 2 for 208V 230V units to N brown wire Signal Connection 1 4 in qui...

Page 24: ...7 1 2 400 500 600 700 875 1050 1150 1250 1325 1375 L M H 042 0 50 11 x 10 1 2 500 600 700 875 1050 1150 1250 1325 1375 1475 1550 L M H 048 0 50 11 x 10 1 2 500 600 700 875 1050 1150 1250 1325 1375 14...

Page 25: ...een and then select ECM Setup This screen displays the current variable speed ECM settings It allows the technician to enter the setup screens to change the variable speed ECM settings Change the high...

Page 26: ...1 3 Isolation Valve Red 51 Green 50 White 52 Note 3 Note 3 RV HP LP T FD RV Blue 07 Blue 08 Black 09 Black 10 Yellow Yellow Red 53 24V CFM P13 P4 SW1 P5 JW2 P9 LO O B Y2 W DH P8 P7 RS485 NET RS485 NE...

Page 27: ...5 Flash Code 8 Flash Code 6 Flash Code 7 Flash Code 9 Flash Code 10 Flash Code 11 ECM Configure Mode Fast Flash Reset Configure Mode Off Fuse SW1 Push button SW2 DIP package 8 position RB Blower Relay...

Page 28: ...94 Brown Orange Red 56 Blue 55 Black 54 Red 56 Blue 55 Black 54 CC 470 470 Resistor Violet 14 Black 15 Orange 01 Orange 02 Condensate Brown 23 Green RV HP LP T FD RV Blue 07 Blue 08 Black 09 Black 10...

Page 29: ...art Up Bypass Low Pressure Fault RecognitionDelay Low Pressure Start Up Bypass Low Water Air Coil Limit Fault RecognitionDelay Low Water Air Coil Limit Fault RecognitionDelay Condensate Overflow Therm...

Page 30: ...G Green 93 Red 97 1 2 3 L N G X13 Fan Motor C 4 5 Green Orange Brown Tan 31 Gray 30 Blue 33 Red 32 Black 35 Black White Black White Yellow LED4 LED5 G G UltraTech Dual Capacity Units Only RCP CS Blue...

Page 31: ...Terminal FieldWiringLug Ground Relay Contacts N O N C FieldZoneSensor Wiring Legend L1 Capacitor T 1 2 3 CC Compressor Contactor CO Condensate OverflowSensor ES Emergency Shutdown HP High PressureSwi...

Page 32: ...LED1 red will flash the last lockout one time Test mode will automatically time out after 30 minutes Test mode can be exited by pressing and holding the SW1 button for 2 to 5 seconds or by cycling the...

Page 33: ...lt type identification display LED1 Red shall flash the fault code To reset lockout conditions with SW2 8 On thermostat inputs Y1 Y2 and W must be removed for at least 3 seconds To reset lockout condi...

Page 34: ...e ECM will run on G speed until the G command is removed Regardless of blower input G from the thermostat the blower will remain on for 30 seconds at the end of each heating cycle Cooling Operation In...

Page 35: ...ool simply plugs into the exterior of the cabinet in the AID Tool port ABC Control Board Layout Aurora Base Control LED Displays These three LEDs display the status configuration and fault codes for t...

Page 36: ...water flow rate is correct by measuring the pressure drop through the heat exchanger using the P T plugs and comparing to the pressure drop table 6 Check the temperature of both the supply and discha...

Page 37: ...inimum or maximum levels the other two factors must be at the normal level for proper and reliable unit operation Entering Water Temp F Water Flow GPM ton Cooling Suction Pressure psig Discharge Press...

Page 38: ...8 0 12 9 10 9 9 5 8 8 7 9 8 0 11 0 0 53 030 4 0 2 4 2 3 2 2 2 0 1 8 3 4 4 0 10 1 0 16 6 0 5 1 4 9 4 7 4 5 4 3 6 0 10 6 0 32 8 0 7 8 7 5 7 1 6 9 6 7 8 0 11 0 0 53 10 0 10 5 10 1 9 6 9 3 8 9 10 0 11 5 0...

Page 39: ...Low Low High High Low Low Scaled Coaxial Heat Exchanger Heating Low Low Low Normal Low High Low Low Scaled Coaxial Heat Exchanger Cooling High High High Normal Low Low Low Low Restricted Filter Drier...

Page 40: ...8 28 8 4 5 13 2 16 5 20 5 22 9 33 1 33 0 31 3 28 8 26 1 6 0 11 9 17 2 20 8 23 3 33 3 33 4 31 7 29 1 26 3 030 4 0 19 9 25 4 31 0 39 9 37 4 34 8 6 0 16 1 20 7 26 5 31 5 39 0 40 3 37 7 34 8 31 4 8 0 14 5...

Page 41: ...PSI and feet of water EAT entering air temperature Fahrenheit dry bulb wet bulb HC air heating capacity MBtu h TC total cooling capacity MBtu h SC sensible cooling capacity MBtu h KW total power unit...

Page 42: ...connect power Check continuity with ohm meter If the winding is open replace the compressor If sufficient cooling or heating is not obtained 1 Check control for improper location or setting 2 Check fo...

Page 43: ..._____ VOLTS Total Amps Comp Fan n _____ AMPS n ______ AMPS Watts m x n x 0 85 o _____ WATTS o ______ WATTS 6 CAPACITY Cooling Capacity HR o x 3 413 p _____ btu hr Heating Capacity HE o x 3 413 p _____...

Page 44: ...ormance problem Line Voltage Loop Open Unit Amp Draw Closed COAX SOURCE HEA7 1 ANALYSIS EXPANSION VALVE F AIR COIL F COMPRESSOR DISCHARGE SUCTION Subcooling Superheat REVERSING VALVE PSI F SAT F PSI S...

Page 45: ...en necessary Units should never be operated without a filter Condensate Drain In areas where airborne bacteria produce a slime in the drain pan it may be necessary to treat chemically to minimize the...

Page 46: ...46 LX COMPACT SERIES INSTALLATION MANUAL Notes...

Page 47: ...47 LX COMPACT SERIES INSTALLATION MANUAL Pages Description Date By All Document Creation 10 Aug 2018 JM Revision Guide...

Page 48: ...eries Type Geothermal Water Source Heat Pumps Size 0 50 6 Ton Document Type Part Number Release Date Installation Manual IM1202AK6 08 18 2018 The manufacturer has a policy of continual product researc...

Reviews: