16
LX COMPACT SERIES INSTALLATION MANUAL
For Aurora Base Control, set SW2-1, FP1, on the printed circuit
board for applications using a closed loop antifreeze solution to
15°F [-9.4°C]. On applications using an open loop/ground water
system (or closed loop no antifreeze), set this dip switch to 30°F
[-1.1°C], the factory default setting. (Refer to the Dip Switch Field
Selection table).
Freeze Detection