LX COMPACT SERIES INSTALLATION MANUAL
Electrical Data cont.
Variable Speed ECM Motor
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
Breaker
MCC
RLA
LRA
006
115/60/1
104/127
9.5
6.1
29.0
1.8
7.9
9.4
15
208-230/60/1
187/253
4.7
3.0
15.0
0.9
3.9
4.7
10/15
009
115/60/1
104/127
12.5
8.0
50.0
1.8
9.8
11.8
20
208-230/60/1
187/253
6.4
4.1
21.0
0.9
5.0
6.1
10/15
012
115/60/1
104/127
14.8
9.5
50.0
1.8
11.25
13.6
20
208-230/60/1
187/253
7.7
4.9
25.0
0.9
5.8
7.1
10/15
015
208-230/60/1
187/253
9.2
5.9
29.0
4.0
9.9
11.4
15
265/60/1
238/292
7.8
5.0
28.0
4.1
9.1
10.3
15
018
208-230/60/1
187/253
10.4
6.7
33.5
4.0
10.7
12.4
15
265/60/1
238/292
8.7
5.6
28.0
4.1
9.7
11.1
15
024
208-230/60/1
187/253
21.0
13.5
58.3
4.0
17.5
20.9
30
265/60/1
238/292
14.0
9.0
54.0
4.1
13.1
15.4
20
208-230/60/3
187/253
11.0
7.1
55.4
4.0
11.1
12.9
15
460/60/3
414/506
5.5
3.5
28.0
4.1
7.6
8.5
10/15
030
208-230/60/1
187/253
22.0
14.1
73.0
4.0
18.1
21.6
35
265/60/1
238/292
17.5
11.2
60.0
4.1
15.3
18.1
25
208-230/60/3
187/253
13.9
8.9
58.0
4.0
12.9
15.1
20
460/60/3
414/506
6.5
4.2
28.0
4.1
8.3
9.4
10/15
036
208-230/60/1
187/253
22.0
14.1
77.0
4.0
18.1
21.6
35
265/60/1
238/292
19.0
12.2
72.0
4.1
16.3
19.4
30
208-230/60/3
187/253
14.0
9.0
71.0
4.0
13.0
15.3
20
460/60/3
414/506
8.8
5.6
38.0
4.1
9.7
11.1
15
041
208-230/60/1
187/253
28.0
17.9
112.0
4.0
21.9
26.4
40
208-230/60/3
187/253
20.6
13.2
88.0
4.0
17.2
20.5
30
460/60/3
414/506
9.3
6.0
44.0
4.1
10.1
11.6
15
042
208-230/60/1
187/253
28.0
17.9
112.0
4.0
21.9
26.4
40
208-230/60/3
187/253
20.6
13.2
88.0
4.0
17.2
20.5
30
460/60/3
414/506
9.3
6.0
44.0
4.1
10.1
11.6
15
048
208-230/60/1
187/253
34.0
21.8
117.0
4.0
25.8
31.3
50
208-230/60/3
187/253
21.4
13.7
83.1
4.0
17.7
21.1
30
460/60/3
414/506
9.7
6.2
41.0
4.1
10.3
11.9
15
060
208-230/60/1
187/253
41.2
26.4
134.0
7.0
33.4
40.0
60
208-230/60/3
187/253
24.9
16.0
110.0
7.0
23.0
27.0
40
460/60/3
414/506
12.1
7.8
52.0
6.9
14.7
16.7
20
070
208-230/60/1
187/253
44.2
28.3
178.0
7.0
35.3
42.4
70
208-230/60/3
187/253
30.0
19.2
136.0
7.0
26.2
31.0
50
460/60/3
414/506
13.6
8.7
66.1
6.9
15.6
17.8
25
HACR circuit breaker in USA only 8/1/18
Caution: When installing a unit with a Variable Speed ECM blower motor in 460/60/3 voltage, a neutral wire is
required to allow proper unit operation.