40
P5417090
(d) Though temperature recordings by the thermistors are invalid during the Test Run phase, the
protection devices are valid.
(e)
For VRF System
According to the label; “Checking Method by 7-Segment Display” affixed to the inside of the front
cover of the outdoor unit, check temperature, pressure, and operation frequency, and interconnected
indoor unit numbers by 7-Segment displays
.
(f) To complete Test Run, press “ On/Off” again or wait for the
set Test Run time to pass.
When changing the Test Run time, press “ ” or “ ” to select
“Test Time”
. Then, set the test run time (30 to 600 minutes)
by pressing “ ” or “ ”.
Adj.
Sel.
OFF
Test Run: 2 units
MODE
SPEED
AUTO
COOL
LOUV.
Test Time
120min
Inverter
60Hz
● The RUN indicator on the wired controller for the indoor unit flashes orange (0.5 second ON/ 0.5
second OFF), indicative of a fault or error having been generated with activation of protection devices
during the Test Run phase. Alarm code, unit model code, and the number of interconnected indoor units
will be displayed on the LCD as shown below. If the RUN indicator on the wired controller flashes for
2 seconds ON and 2 seconds OFF, the source of the problem could be a failure in the communication
cable between the indoor unit and the wired controller (a loose or severed connection). In this case,
verify Section 9.3 “Alarm Code” and perform the appropriate troubleshooting measures. Consult with an
authorized service engineer if the problem cannot be resolved at your end.
Unit Model Code
The relationship between the unit model code
and the unit model is shown in the table below.
Indication
Unit Model
F
VRF System
E
Except Above Models
Sel.
OP MODE
I.U.
: RCI-3.0FSN3
MODEL : F .02
Alarm Code:
22
O.U.
: RAS-3HVRNM2
01-02
AlarmRst
Address
Entr
IDU
: ******
ODU : ******
Chek
OK
Refrigerant Cycle No.
of Indoor Unit Having
Trouble
Indoor Unit No. of Indoor Unit
Having Trouble
MODEL : F . 02
Alarm Code:
22
Alarm Code No.
Total No. of Indoor Units in the
Same Refrigerant Cycle as the
Indoor Unit Having Trouble
01 - 02
Unit Model Code
Summary of Contents for TIWM006B22S