34
P5417090
(3) Unit No. Setting (RSW2 and DSW6)
Setting is not required.
Indoor unit numbers are set by the auto-address function. If an indoor unit number setting is required,
set the unit number of all indoor units respectively and sequentially by following setting position. It is
recommended that you assign a number to each indoor unit from “1”. A maximum of 64 indoor units
per refrigerant cycle can be connected to an H-LINK ll System. Though the available numbers range
from zero to 63, the applicable number for the 64
th
indoor unit in theory supplants the number "zero".
For the centralized control, this setting is required.
(4) Capacity Code Setting (DSW3)
No setting is required, due to setting before shipment. This switch is utilized for setting the capacity
code that corresponds to the capacity of the indoor unit.
(5) Refrigerant Cycle No. Setting (RSW1 and DSW5)
This setting is required. The unit arrives with all settings in the OFF position.
8.5 DIP Switch Settings
(1) Turn OFF the power supply to both indoor and outdoor units before adjusting DIP switch settings.
Otherwise, the settings are invalidated and do not take effect.
(2) Correct DIP switch settings are shown here. Remove the panel to make these adjustments and
reattach when finished.
DIP Switch PCB
(PCB2)
Switch Cover
PCB2
Setting Position
006
008
012
Indoor Unit Capacity
(MBH)
015
018
024
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
030
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
DSW5
RSW1
RSW2
DSW6
DSW9 DSW2
SW2
DSW3
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
DSW6 (Tens Digit)
Unit No. Setting
RSW2 (Units Digit)
Setting
Position
Set by inserting
slotted screwdriver
into the groove.
Ex.) Set at No.16 Unit
DSW6
RSW2
Set No.1 Pin at ON side
Set at "6"
34
1
0
89
2
56
7
34
1
0
89
2
56
7
Before shipment, DSW6 and RSW2 are set at "0".
For the units supporting H-LINK II,
the unit No. can be set for Max. 64 indoor units
(No.0~63).
34
1
0
89
2
56
7
34
1
0
89
2
56
7
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
DSW5 (Tens Digit)
Refrigerant Cycle No. Setting
RSW1 (Units Digit)
Setting
Position
Set by inserting
slotted screwdriver
into the groove.
Ex.) Set at No.5 Cycle
DSW5
RSW1
Set All Pins OFF
Set at "5"
Before shipment, DSW5 and RSW1 are set at "0".
For the units supporting H-LINK II,
the ref. cycle No. can be set for Max. 64 cycles.
(No. 0~63)
Summary of Contents for TIWM006B22S
Page 2: ......
Page 49: ......
Page 50: ...2018 Johnson Controls Inc P5417090 Code No LIT 12013130 Issued September 2018...