P5417090
33
TB1
TB2
Outside of Unit
Inside of Unit
Secure the PVC Tube
by Cable Bands (Accessory)
Wired Controller Cable
Communication Cable
Rubber Bushing on Conduit Plate
Conduit Tube
Power Supply Wiring
PVC Tube “VW-1 600V” (Accessory)
Install and secure all electrical wiring correctly through the connecting hole, to the terminal blocks
using the cable bands provided. Wiring should be spaced appropriately and firmly fastened to
guarantee against electrical short, sparks, and flame.
NOTES:
•
Remove the sheath part of communication cable and wired controller cable (field-supplied) before
passing through the rubber bushing on the conduit plate.
•
Then, insert the communication cable and wired controller cable into the PVC tube “VW-1 600V”
(Accessory) to separate from the power supply wiring for the indoor unit.
End of PVC tube should be routed just before the rubber bushing on the conduit plate.
Cut the PVC tube for any excess length.
•
Secure the both ends of the PVC tube by cable band (Accessory).
•
If shielded cable is used, terminate at the ground terminal.
•
Separate the power supply wiring from the terminal block for controller and communication cables (TB2).