background image

835961-UIM-D-0213

6

Johnson Controls Unitary Products

SECTION VI: EVACUATION

It will be necessary to evacuate the system to 500 microns or less. If a
leak is suspected, leak test with dry nitrogen to locate the leak. Repair
the leak and test again.

To verify that the system has no leaks, simply close the valve to the vac-
uum pump suction to isolate the pump and hold the system under vac-
uum. Watch the micron gauge for a few minutes. If the micron gauge
indicates a steady and continuous rise, it’s an indication of a leak. If the
gauge shows a rise, then levels off after a few minutes and remains
fairly constant, its an indication that the system is leak free but still con-
tains moisture and may require further evacuation if the reading is
above 500 microns.

SECTION VII: SYSTEM CHARGE

To ensure that your unit performs at the published levels, it is important
that the indoor airflow is determined and refrigerant charge added
accordingly.

Measure Indoor Air Flow:

To determine rated air flow for a specific match, consult the technical lit-
erature at www.upgnet.com.

Examples:

GHGD1 AHE18B3XH21 = 610 CFM

THGF FC35B3XN1 = 800 CFM

THJR3 AHV36C3XH21 = 940 CFM

YHJD4 FC60 TM9X100C20MP11A = 1625 CFM.

THGF6 MC6 MV20DN21C = 1855 CFM(High) & 1160 (Low)

When attempting to match this air flow, select the lowest possible speed
tap and measure the actual flow and adjust as necessary. Checking
jumper pin setting tables is not an acceptable method for determining
air flow. To determine indoor air flow, first measure the static pressure
with a manometer between the filter and blower. On a single-piece air
handler, take a second reading after the coil. On a furnace or modular
air handler, take the second reading after the heat exchanger, but
before the indoor coil. Add the negative return static to the positive sup-
ply static to determine the system total static pressure. Treat the nega-
tive return static as a positive pressure as even though it is a negative
reading, it is static pressure on the blower; i.e. -.10 return static added
to a .40 supply static equals a .50 total system static pressure. Compare
this value the indoor unit's static pressure chart vs. CFM table or curve.

Charging the Unit:

The factory charge in the outdoor unit includes enough charge for the
unit, a 15 ft. (4.6 m) line set, and the smallest indoor coil/air handler
match-up. Some indoor coil/air handler matches may require additional
charge. See Tabular Data Sheet provided in unit Customer Booklet for
charge requirements.

The "TOTAL SYSTEM CHARGE" must be permanently marked on the
unit data plate.

Total system charge is determined as follows:

1. Determine outdoor unit factory charge from Tabular Data Sheet.

2. Determine indoor coil adjustment (if any) from Tabular Data Sheet.

3. Calculate the additional charge for lineset using the Tabular Data

Sheet if line length is greater than 15 feet (4.6 m).

4. Total system charge = item 1 + item 2 + item 3.

5. Permanently mark the unit data plate with the total amount of refrig-

erant in the system.

Using the charging charts:

The unit includes heating charging charts and cooling charging charts.
All units include a subcooling charging chart for cooling. If the unit can
be used with an indoor orifice, then a cooling superheat chart is also
included. If a charging chart is not on the unit, then it can be obtained at
www.upgnet.com.

These charts should not be used to charge the unit. They are refer-
ence charts for servicing the unit. After the unit has been serviced,
collect the charge and weigh it back in according to the directions.

Charging by only one method (cooling or heating), as well as charging
to a superheating or subcooling value is not acceptable. Most heat
pumps are sensitive to charge in one mode, so charging by only one
mode can cause it under perform in the other.

Before confirming system performance against the charging charts, you
should first confirm that your gauges are accurate by either comparing
your gauges against a calibrated pressure gauge that has been cali-
brated against a national standard, or if that is not available, then place
a R-410A virgin refrigerant container in a conditioned space long
enough to come to temperature equilibrium with the surroundings. Then
measure the temperature of the air and the pressure of the refrigerant
and compare it to the following table:

If the gauges are correct, then measure the pressures using both the cooling and heating charts.

Do not leave the system open to the atmosphere.

This method is for systems that only have interconnecting lines. If
any other objects that adjust the charge levels are placed between
the indoor and outdoor units (example: a refrigerant flow meter), then
before adding charge, the device must first be removed. Follow the
steps above. Run the system in both cooling and heating mode and
record the high side pressure in each mode. Then insert the device
and charge the system by matching the same high side pressure in
both heating and cooling as that value recorded without the device. It
is not acceptable to add a pre-determined charge amount listed by
the device manufacturer nor is it acceptable to use any other method.

DO NOT attempt to pump “Total System Charge” into outdoor unit for
maintenance, service, etc. This may cause damage to the compres-
sor and/or other components. The outdoor unit only has enough vol-
ume for the factory charge, not the “Total System Charge”.

NOTICE

Temp (°F)

Pressure (Psig)

Temp (°F)

Pressure (Psig)

Temp (°F)

Pressure (Psig)

40

119

75

218

110

365

45

130

80

236

115

391

50

143

85

255

120

418

55

156

90

274

125

447

60

170

95

295

130

477

65

185

100

317

70

201

105

341

Summary of Contents for THGD Series

Page 1: ...nt charge may need to be changed for some indoor out door unit combinations elevation differences or total line lengths Refer to Application Data covering General Piping Recommendations and Refrigerant Line Length Part Number 247077 SECTION II SAFETY This is a safety alert symbol When you see this symbol on labels or in manuals be alert to the potential for personal injury Understand and pay parti...

Page 2: ... to insure proper system operation and performance Line set change out is also recommended 1 Change out of the indoor coil to an approved R 410A coil condens ing unit combination with the appropriate metering device 2 Change out of the line set when replacing an R 22 unit with an R410 A unit is highly recommended to reduce cross contamination of oils and refrigerants 3 If change out of the line se...

Page 3: ...s necessary If soft copper must be used care must be taken to avoid sharp bends which may cause a restriction 2 The lines should be installed so that they will not obstruct service access to the coil air handling system or filter 3 Care must also be taken to isolate the refrigerant lines to minimize noise transmission from the equipment to the structure 4 The vapor line must be insulated with a mi...

Page 4: ...erant piping connections including the service port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40 and 60 inch lbs maximum 9 Evacuate the vapor line evaporator and the liquid line to 500 microns or less 10 Replace cap on service ports Do not remove the flare caps from the service ports except when necessary for servicing the system 11 Release the refrigerant charge into th...

Page 5: ...r line as follows a Hand tighten the 1 4 SAE nut to the Schrader fitting and an additional 1 3 turn to seal 7 Install the TXV bulb to the vapor line near the equalizer line using the bulb clamp s furnished with the TXV assembly Ensure the bulb is making maximum contact a Bulb should be installed on a horizontal run of the vapor line if possible On lines under 7 8 O D the bulb may be installed on t...

Page 6: ...Determine indoor coil adjustment if any from Tabular Data Sheet 3 Calculate the additional charge for lineset using the Tabular Data Sheet if line length is greater than 15 feet 4 6 m 4 Total system charge item 1 item 2 item 3 5 Permanently mark the unit data plate with the total amount of refrig erant in the system Using the charging charts The unit includes heating charging charts and cooling ch...

Page 7: ...out 5 ft above the floor where it will be exposed to normal room air circulation Do not place it on an outside wall or where it is exposed to the radiant effect from exposed glass or appliances drafts from outside doors or supply air grilles 6 Route the 24 volt control wiring NEC Class 2 from the outdoor unit to the indoor unit and thermostat Refrigerant charging should only be carried out by a qu...

Page 8: ...e airflow using the LED display on the CFM selection board FIGURE 8 Typical Field Wiring Air Handler Electrical Heat Three Phase FIGURE 9 Typical Field Wiring Air Handler Electrical Heat Single Phase THERMOSTAT INDOOR UNIT OUTDOOR UNIT LOW VOLTAGE TERMINAL BLOCK IN AIR HANDLER WITH ELECTRIC HEAT 3 4 DEFROST CONTROL 1 FIELD INSTALLED JUMPER GND SCREW CONTACTOR T2 T1 L2 L1 M R Y O W G T2 E 2 R R Y Y...

Page 9: ...hermostat demand to provide cooling as needed An attempt to start the compressor without at least 8 hours of crank case heat will damage the compressor TABLE 1 R 410A Saturation Properties Temp F Pressure PSIG Temp F Pressure PSIG Temp F Pressure PSIG Temp F Pressure PSIG Temp F Pressure PSIG 45 130 60 170 75 217 90 274 105 341 46 132 61 173 76 221 91 278 106 345 47 135 62 176 77 224 92 282 107 35...

Page 10: ...cause of a pressure switch lockout it will energize the X L output as shown in Table 3 The control has a three second delay between fault code flashes If the conditions above exist during cooling mode the system could be in the loss of charge condition DEFROST OPERATION Time Temperature Defrost 13 Seer 2 5 Ton The defrost control is a time temp control which includes a field select able tap locate...

Page 11: ...le Initiation The control will allow the heat pump to operate in the heating mode until the combination of outdoor ambient and outdoor coil temperatures indi cate that a defrost cycle is necessary The control will initiate a defrost cycle when the liquid line temperature is below the initiate point for the measured ambient temperature See Figure 13 continuously for 4 1 2 minutes This delay elimina...

Page 12: ...ollowing removal of the fault condition 1 Power is cycled to the R or Y inputs of the control This will cause the soft lockout condition to be reset when the thermostat is satisfied or when the thermostat is set to SYSTEM OFF and back to HEAT or COOL mode 2 The TEST terminals are shorted for more than two seconds When the soft lockout condition is reset the control will stop displaying the fault c...

Page 13: ...835961 UIM D 0213 Johnson Controls Unitary Products 13 SECTION VII WIRING DIAGRAM FIGURE 14 Wiring Diagram Single Phase Demand Defrost ...

Page 14: ...ANGE PNK PINK PUR PURPLE RED RED WHT WHITE YEL YELLOW BLK BLK BRN PNK YEL PNK HPS HTS LPS BRN PNK YEL PNK YEL PNK SEE UNIT INSTALLATION INSTRUCTIONS FOR LOW VOLTAGE TERMINATIONS COND FAN X L PUR RED DEFROST CONTROL BLK WHT BRN BLK REV VALVE YEL ORG RV R C Y O W W1 66 PRES SWITCH DFST T STAT M BRN PNK YEL PNK BLK GRY LS BLU DANGER SHOCK HAZARD TURN OFF ELECTRICAL POWER BEFORE SERVICING TO PREVENT P...

Page 15: ...OMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH 105 C THERMOPLASTIC OR ITS EQUIVALENT WHERE POWER SUPPLY HAS ONE 1 240 VOLT CONDUCTOR AND ONE 1 NEUTRAL CONDUCTOR CONNECT L2 OF CONTACTOR TO NEUTRAL FAN RELAY AND WIRES LABELED 460V ONLY USED ON 380 415V OR 460V 1 2...

Page 16: ... BLK 208 230 BRN PNK YEL PNK HPS HTS LPS BRN PNK YEL PNK YEL PNK SEE UNIT INSTALLATION INSTRUCTIONS FOR LOW VOLTAGE TERMINATIONS COND FAN X L PUR RED DEFROST CONTROL BLK WHT BRN BLK REV VALVE YEL ORG RV R C Y O W W1 66 PRESS SWITCH DFST T STAT M BRN PNK GRY BLK YEL 460V BLK 460V LS BLU DANGER SHOCK HAZARD TURN OFF ELECTRICAL POWER BEFORE SERVICING TO PREVENT POSSIBLE DAMAGE TO THE EQUIPMENT AND PO...

Page 17: ...835961 UIM D 0213 Johnson Controls Unitary Products 17 NOTES ...

Page 18: ...pplicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connected if applicable Supply plenum and return ducts are connected and sealed Filter Size Vent system is connected if applicable Thermostat wiring complete Heat anticipator is set to the recommended value ...

Page 19: ...mp Cut Out Balance Point Defrost Curve Y2 Lock FFUEL Switch Point Hot Heat Pump Fill in the information ie ON OFF or the appropriate Value for the fields that apply to the defrost control board installed Run Time Time and Temperature board only 30 60 or 90 minutes Bonnet Sensor Present HEAT Refrigerant Charge and Metering Device TXV Fixed Orifice R 22 R 410A Oz 45s Elbows TXV Orifice Size Liquid L...

Page 20: ...edes 835961 UIM C 0712 York International Corp 5005 York Drive Norman OK 73069 Explain operation of system to equipment owner Explain the importance of regular filter replacement and equipment maintenance Owner Education Provide owner with the owner s manual Explain thermostat use and programming if applicable to owner Comments Section ...

Reviews: