background image

835961-UIM-D-0213

4

Johnson Controls Unitary Products

PRECAUTIONS DURING BRAZING OF LINES

All outdoor unit and evaporator coil connections are copper-to-copper
and should be brazed with a phosphorous-copper alloy material such
as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units
have reusable service valves on both the liquid and vapor connections.
The total system refrigerant charge is retained within the outdoor unit
during shipping and installation. The reusable service valves are pro-
vided to evacuate and charge per this instruction.

Serious service problems can be avoided by taking adequate precau-
tions to assure an internally clean and dry system.

PRECAUTIONS DURING BRAZING SERVICE VALVE

Precautions should be taken to prevent heat damage to service valve
by wrapping a wet rag around it as shown in Figure 4. Also, protect all
painted surfaces, insulation, and plastic base during brazing. After braz-
ing cool joint with wet rag.

Valve can be opened by removing the plunger cap and fully inserting a
hex wrench into the stem and backing out counter-clockwise until valve
stem just touches the chamfered retaining wall.

Connect the refrigerant lines using the following procedure:

1. Remove the cap and Schrader core from both the liquid and vapor

service valve service ports at the outdoor unit. Connect low pressure
nitrogen to the liquid line service port.

2. Braze the liquid line to the liquid valve at the outdoor unit. Be sure to

wrap the valve body with a wet rag. Allow the nitrogen to continue
flowing. Refer to the Tabular Data Sheet for proper liquid line sizing.

3. Go to “SECTION IV” or “SECTION V” for orifice or TXV Installation

depending on application.

4. Braze the liquid line to the evaporator liquid connection. Nitrogen

should be flowing through the evaporator coil.

5. Slide the grommet away from the vapor connection at the indoor coil.

Braze the vapor line to the evaporator vapor connection. After the
connection has cooled, slide the grommet back into original position.
Refer to the Tabular Data Sheet for proper vapor line sizing.

6. Protect the vapor valve with a wet rag and braze the vapor line con-

nection to the outdoor unit. The nitrogen flow should be exiting the
system from the vapor service port connection. After this connection
has cooled, remove the nitrogen source from the liquid fitting service
port.

7. Replace the Schrader core in the liquid and vapor valves.

8. Leak test all refrigerant piping connections including the service port

flare caps to be sure they are leak tight. DO NOT OVERTIGHTEN
(between 40 and 60 inch - lbs. maximum).

9. Evacuate the vapor line, evaporator, and the liquid line to 500

microns or less.

10.Replace cap on service ports. Do not remove the flare caps from the

service ports except when necessary for servicing the system.

11.Release the refrigerant charge into the system. Open both the liquid

and vapor valves by removing the plunger cap and with an allen
wrench back out counter-clockwise until valve stem just touches the
chamfered retaining wall. If the service valve is a ball valve, use a
cresent wrench to turn valve stem one-quarter turn counterclockwise
to open. Do not overturn or the valve stem may break or become
damaged. See “PRECAUTIONS DURING BRAZING SERVICE
VALVE”.

12.Replace plunger cap finger tight, then tighten an additional 1/12 turn

(1/2 hex flat). Cap must be replaced to prevent leaks.

See "System Charge” section for checking and recording system
charge.

 Dry nitrogen should always be supplied through the tubing while it is
being brazed, because the temperature is high enough to cause oxi-
dation of the copper unless an inert atmosphere is provided. The flow
of dry nitrogen should continue until the joint has cooled. Always use
a pressure regulator and safety valve to insure that only low pressure
dry nitrogen is introduced into the tubing. Only a small flow is neces-
sary to displace air and prevent oxidation.

This is not a backseating valve. The service access port has a valve
core. Opening or closing valve does not close service access port.
If the valve stem is backed out past the chamfered retaining wall, the
O-ring can be damaged causing leakage or system pressure could
force the valve stem out of the valve body possibly causing personal
injury.

 FIGURE 4:  

Heat Protection

Do not install any coil in a furnace which is to be operated during the
heating season without attaching the refrigerant lines to the coil. The
coil is under 30 to 35 psig inert gas pressure which must be released
to prevent excessive pressure build-up and possible coil damage.

Line set and indoor coil can be pressurized to 250 psig with dry nitro-
gen and leak tested with a bubble type leak detector. Then release
the nitrogen charge.
Do not use the system refrigerant in the outdoor unit to purge or leak
test.

Do not connect manifold gauges unless trouble is suspected. Approx-
imately 3/4 ounce of refrigerant will be lost each time a standard man-
ifold gauge is connected.

Never attempt to repair any brazed connections while the system is
under pressure. Personal injury could result.

NOTICE

Summary of Contents for THGD Series

Page 1: ...nt charge may need to be changed for some indoor out door unit combinations elevation differences or total line lengths Refer to Application Data covering General Piping Recommendations and Refrigerant Line Length Part Number 247077 SECTION II SAFETY This is a safety alert symbol When you see this symbol on labels or in manuals be alert to the potential for personal injury Understand and pay parti...

Page 2: ... to insure proper system operation and performance Line set change out is also recommended 1 Change out of the indoor coil to an approved R 410A coil condens ing unit combination with the appropriate metering device 2 Change out of the line set when replacing an R 22 unit with an R410 A unit is highly recommended to reduce cross contamination of oils and refrigerants 3 If change out of the line se...

Page 3: ...s necessary If soft copper must be used care must be taken to avoid sharp bends which may cause a restriction 2 The lines should be installed so that they will not obstruct service access to the coil air handling system or filter 3 Care must also be taken to isolate the refrigerant lines to minimize noise transmission from the equipment to the structure 4 The vapor line must be insulated with a mi...

Page 4: ...erant piping connections including the service port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40 and 60 inch lbs maximum 9 Evacuate the vapor line evaporator and the liquid line to 500 microns or less 10 Replace cap on service ports Do not remove the flare caps from the service ports except when necessary for servicing the system 11 Release the refrigerant charge into th...

Page 5: ...r line as follows a Hand tighten the 1 4 SAE nut to the Schrader fitting and an additional 1 3 turn to seal 7 Install the TXV bulb to the vapor line near the equalizer line using the bulb clamp s furnished with the TXV assembly Ensure the bulb is making maximum contact a Bulb should be installed on a horizontal run of the vapor line if possible On lines under 7 8 O D the bulb may be installed on t...

Page 6: ...Determine indoor coil adjustment if any from Tabular Data Sheet 3 Calculate the additional charge for lineset using the Tabular Data Sheet if line length is greater than 15 feet 4 6 m 4 Total system charge item 1 item 2 item 3 5 Permanently mark the unit data plate with the total amount of refrig erant in the system Using the charging charts The unit includes heating charging charts and cooling ch...

Page 7: ...out 5 ft above the floor where it will be exposed to normal room air circulation Do not place it on an outside wall or where it is exposed to the radiant effect from exposed glass or appliances drafts from outside doors or supply air grilles 6 Route the 24 volt control wiring NEC Class 2 from the outdoor unit to the indoor unit and thermostat Refrigerant charging should only be carried out by a qu...

Page 8: ...e airflow using the LED display on the CFM selection board FIGURE 8 Typical Field Wiring Air Handler Electrical Heat Three Phase FIGURE 9 Typical Field Wiring Air Handler Electrical Heat Single Phase THERMOSTAT INDOOR UNIT OUTDOOR UNIT LOW VOLTAGE TERMINAL BLOCK IN AIR HANDLER WITH ELECTRIC HEAT 3 4 DEFROST CONTROL 1 FIELD INSTALLED JUMPER GND SCREW CONTACTOR T2 T1 L2 L1 M R Y O W G T2 E 2 R R Y Y...

Page 9: ...hermostat demand to provide cooling as needed An attempt to start the compressor without at least 8 hours of crank case heat will damage the compressor TABLE 1 R 410A Saturation Properties Temp F Pressure PSIG Temp F Pressure PSIG Temp F Pressure PSIG Temp F Pressure PSIG Temp F Pressure PSIG 45 130 60 170 75 217 90 274 105 341 46 132 61 173 76 221 91 278 106 345 47 135 62 176 77 224 92 282 107 35...

Page 10: ...cause of a pressure switch lockout it will energize the X L output as shown in Table 3 The control has a three second delay between fault code flashes If the conditions above exist during cooling mode the system could be in the loss of charge condition DEFROST OPERATION Time Temperature Defrost 13 Seer 2 5 Ton The defrost control is a time temp control which includes a field select able tap locate...

Page 11: ...le Initiation The control will allow the heat pump to operate in the heating mode until the combination of outdoor ambient and outdoor coil temperatures indi cate that a defrost cycle is necessary The control will initiate a defrost cycle when the liquid line temperature is below the initiate point for the measured ambient temperature See Figure 13 continuously for 4 1 2 minutes This delay elimina...

Page 12: ...ollowing removal of the fault condition 1 Power is cycled to the R or Y inputs of the control This will cause the soft lockout condition to be reset when the thermostat is satisfied or when the thermostat is set to SYSTEM OFF and back to HEAT or COOL mode 2 The TEST terminals are shorted for more than two seconds When the soft lockout condition is reset the control will stop displaying the fault c...

Page 13: ...835961 UIM D 0213 Johnson Controls Unitary Products 13 SECTION VII WIRING DIAGRAM FIGURE 14 Wiring Diagram Single Phase Demand Defrost ...

Page 14: ...ANGE PNK PINK PUR PURPLE RED RED WHT WHITE YEL YELLOW BLK BLK BRN PNK YEL PNK HPS HTS LPS BRN PNK YEL PNK YEL PNK SEE UNIT INSTALLATION INSTRUCTIONS FOR LOW VOLTAGE TERMINATIONS COND FAN X L PUR RED DEFROST CONTROL BLK WHT BRN BLK REV VALVE YEL ORG RV R C Y O W W1 66 PRES SWITCH DFST T STAT M BRN PNK YEL PNK BLK GRY LS BLU DANGER SHOCK HAZARD TURN OFF ELECTRICAL POWER BEFORE SERVICING TO PREVENT P...

Page 15: ...OMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH 105 C THERMOPLASTIC OR ITS EQUIVALENT WHERE POWER SUPPLY HAS ONE 1 240 VOLT CONDUCTOR AND ONE 1 NEUTRAL CONDUCTOR CONNECT L2 OF CONTACTOR TO NEUTRAL FAN RELAY AND WIRES LABELED 460V ONLY USED ON 380 415V OR 460V 1 2...

Page 16: ... BLK 208 230 BRN PNK YEL PNK HPS HTS LPS BRN PNK YEL PNK YEL PNK SEE UNIT INSTALLATION INSTRUCTIONS FOR LOW VOLTAGE TERMINATIONS COND FAN X L PUR RED DEFROST CONTROL BLK WHT BRN BLK REV VALVE YEL ORG RV R C Y O W W1 66 PRESS SWITCH DFST T STAT M BRN PNK GRY BLK YEL 460V BLK 460V LS BLU DANGER SHOCK HAZARD TURN OFF ELECTRICAL POWER BEFORE SERVICING TO PREVENT POSSIBLE DAMAGE TO THE EQUIPMENT AND PO...

Page 17: ...835961 UIM D 0213 Johnson Controls Unitary Products 17 NOTES ...

Page 18: ...pplicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connected if applicable Supply plenum and return ducts are connected and sealed Filter Size Vent system is connected if applicable Thermostat wiring complete Heat anticipator is set to the recommended value ...

Page 19: ...mp Cut Out Balance Point Defrost Curve Y2 Lock FFUEL Switch Point Hot Heat Pump Fill in the information ie ON OFF or the appropriate Value for the fields that apply to the defrost control board installed Run Time Time and Temperature board only 30 60 or 90 minutes Bonnet Sensor Present HEAT Refrigerant Charge and Metering Device TXV Fixed Orifice R 22 R 410A Oz 45s Elbows TXV Orifice Size Liquid L...

Page 20: ...edes 835961 UIM C 0712 York International Corp 5005 York Drive Norman OK 73069 Explain operation of system to equipment owner Explain the importance of regular filter replacement and equipment maintenance Owner Education Provide owner with the owner s manual Explain thermostat use and programming if applicable to owner Comments Section ...

Reviews: