036-21030-003 Rev. B (0203)
18
Unitary Products Group
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
E4FD024S06
EVAPORATOR COIL MODEL NO
F2RP/F2FP024
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
750
800
850
MBTUH
K.W.
C.O.P.
MBTUH
K.W.
C.O.P.
MBTUH
K.W.
C.O.P.
60
60
27.2
2.21
3.72
27.4
2.17
3.80
27.0
1.97
4.12
70
26.1
2.27
3.46
26.7
2.25
3.58
26.5
2.04
3.90
80
25.0
2.48
3.03
25.9
2.47
3.16
26.0
2.26
3.47
47
60
23.2
2.01
3.39
23.2
2.05
3.32
23.7
1.90
3.66
70
22.0
2.07
3.13
22.4
2.12
3.10
23.2
1.98
3.44
80
20.8
2.23
2.74
21.6
2.30
2.76
22.6
2.15
3.08
40
60
18.4
1.63
3.27
21.0
1.99
3.06
21.8
1.87
3.39
70
17.4
1.86
2.73
20.1
2.05
2.84
19.9
1.93
3.00
80
16.5
2.56
1.88
19.2
2.20
2.54
18.1
2.42
2.18
30
60
17.2
1.89
2.63
17.7
1.91
2.68
17.3
1.75
2.86
70
16.1
1.93
2.41
16.8
1.96
2.48
16.9
1.82
2.67
80
15.0
2.02
2.15
15.9
2.06
2.22
16.4
1.95
2.44
17
60
13.0
1.73
2.20
13.5
1.80
2.20
14.0
1.67
2.45
70
12.0
1.75
2.01
12.5
1.83
2.00
13.1
1.70
2.25
80
10.9
1.76
1.82
11.5
1.86
1.81
12.2
1.72
2.07
10
60
10.8
1.72
1.89
11.2
1.75
1.93
11.7
1.64
2.14
70
9.5
1.72
1.67
10.2
1.76
1.74
10.4
1.67
1.88
80
8.2
1.67
1.48
9.1
1.73
1.59
9.1
1.65
1.67
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
F2RP/F2FP030
1.02
0.99
1.03
G2FD035(S,H)14
1.00
1.00
1.00
G2FD030(S,H)17
1.01
1.01
1.00
G2FD024(S,H)14,17
1.00
1.00
1.00
G1HD024
0.98
1.01
0.97
G1UA030S14
0.98
1.04
0.95
G1UA036S17,21
1.00
1.03
0.97
G1FA030S14
0.98
1.04
0.95
G1FA036S17,21
1.00
1.03
0.97