036-21030-003 Rev. B (0203)
Unitary Products Group
17
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
E4FD018S06
EVAPORATOR COIL MODEL NO
F2RP/F2FP018
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
600
650
700
MBTUH
K.W.
C.O.P.
MBTUH
K.W.
C.O.P.
MBTUH
K.W.
C.O.P.
60
60
21.1
1.78
3.56
21.7
1.78
3.66
21.9
1.65
4.00
70
20.0
1.81
3.33
20.9
1.83
3.43
21.3
1.70
3.76
80
18.9
1.84
3.08
20.0
1.88
3.20
20.5
1.76
3.50
47
60
18.3
1.65
3.26
18.5
1.67
3.25
18.7
1.57
3.48
70
17.1
1.70
2.95
17.6
1.72
3.00
17.9
1.61
3.25
80
15.7
1.75
2.64
16.6
1.77
2.74
17.0
1.65
3.01
40
60
14.8
1.32
3.25
16.8
1.61
3.03
17.5
1.51
3.36
70
13.7
1.50
2.66
15.8
1.66
2.77
15.7
1.56
2.92
80
12.7
2.00
1.84
14.7
1.72
2.50
13.9
1.89
2.14
30
60
14.0
1.52
2.67
14.4
1.53
2.72
14.1
1.40
2.91
70
12.8
1.56
2.37
13.3
1.58
2.43
13.4
1.47
2.63
80
11.5
1.60
2.07
12.1
1.64
2.15
12.6
1.55
2.35
17
60
10.6
1.40
2.23
11.2
1.42
2.32
11.4
1.35
2.49
70
9.4
1.48
1.87
10.0
1.47
2.00
10.3
1.43
2.12
80
8.2
1.58
1.53
8.8
1.53
1.69
9.2
1.52
1.77
10
60
9.0
1.34
2.04
9.5
1.37
2.10
9.9
1.29
2.32
70
7.6
1.37
1.68
8.2
1.41
1.77
8.7
1.34
1.97
80
6.2
1.42
1.33
7.0
1.47
1.45
7.6
1.40
1.65
NOTE:
ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
F2RP/F2FP024
1.01
0.98
1.03
G2FD024(S,H)14,17
1.02
1.00
1.02
G1HD024
1.03
1.01
1.03
G1UA024S17
1.02
1.02
1.00
G1UA030S14
1.03
1.01
1.02
G1FA024S17
1.02
1.02
1.00
G1FA030S14
1.03
1.03
1.00