036-21030-003 Rev. B (0203)

Unitary Products Group

3

PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaportor and for 15 feet of interconnecting line

tubing.

2. Verify the orifice size and additional charge required for specific evaportor coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for 

eva adder for line set.

5. If the orifice in the evaportor was change

Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 & 3 Phase

OUTDOOR UNIT

E4FD018

E4FD024

E4FD030

E4FD036

E4FD042

E4FD048

E4FD060 

Orifice in OD Distributor

37

45

51

59

67

76

76

FACTORY CHARGE, LBS. - OZ.

4-11

4-12

5-3

5-11

7-6

7-6

9-5

ID Orifice included w/Instruction Package

53

61

67

75

78, 81

84, 87

93

INDOOR COIL

COIL ORIFICE

1

REQUIRED SYSTEM O ADDITIONAL CHARGE, OZ.

G1FA/G1UA024S14, 17

59

53+2

-

-

-

-

-

-

G1FA/G1UA030S14

65

53+5

61+0

-

-

-

-

-

G1FA/G1UA036S14

73

-

61+2

67+0

-

-

-

-

G1FA/G1UA036S17

73

-

-

67+5

-

-

-

-

G1FA/G1UA048S17

84

-

-

-

75+3

81+5

84+0

-

G1FA/G1UA048S21

84

-

-

-

75+5

81+5

84+0

-

G1FA/G1UA060S21, 24

90

-

-

-

-

-

87+7

93+0

G2FD024(S,H)14, 17

61

53+5

61+0

-

-

-

-

-

G2FD030(S,H)17

65

-

61+2

67+0

-

-

-

-

G2FD035(S,H)14

65

-

61+2

67+0

-

-

-

-

G2FD036(S,H)17, 21

75

-

-

67+5

75+0

-

-

-

G2FD042(S,H)21

78

-

-

75+1

78+0

-

-

G2FD046(S,H)17

78

-

-

-

75+3

78+0

-

-

G2FD048(S,H)21, 24

84

-

-

-

-

81+5

84+2

-

G2FD060(S,H)24

90

-

-

-

-

-

87+4

93+0

G2FD061SH24

90

-

-

-

-

-

-

93+8

G1HD024

59

53+5

61+1

-

-

-

-

-

G1HD036

69

-

-

67+5

75+0

-

-

-

G1HD048

81

-

-

-

-

78+2

87+0

-

G1HD060

93

-

-

-

-

81+9

87+0

93+8

F2RP/FP018

53

53+0

-

-

-

-

-

-

F2RP/FP024

61

53+4

61+0

-

-

-

-

-

F2RP/FP030

65

-

61+2

67+0

-

-

-

-

F2RP/FP036

75

-

-

67+5

75+0

-

-

-

F2RP/FP042

78

-

-

-

75+3

78+0

-

-

F2FP048

84

-

-

-

-

81+5

84+2

-

F2FP060

90

-

-

-

-

-

-

93+0

REFRIGERANT LINE ADDER OZ. / FT.

0.66

0.66

0.68

0.68

0.68

0.70

0.70

FOOTNOTES:

1. These orifices are factory mounted in the flow control device of each indoor coil.

Summary of Contents for STELLAR 2000 EFD Series

Page 1: ...damage by a polymer mesh applied between the coil face and a PVC coated steel coil guard DEFROST CONTROL Time Temperature defrost control provides field selectable time periods between defrost cycles...

Page 2: ...8 E4FD060 25 46 Unit Supply Voltage 208 230 3 60 460 3 60 Normal Voltage Range 1 187 TO 253 432 TO 504 Minimum Circuit Ampacity 15 2 20 1 25 0 8 0 9 0 11 4 Max Overcurrent Device Amps 2 25 30 40 15 15...

Page 3: ...FACTORY CHARGE LBS OZ 4 11 4 12 5 3 5 11 7 6 7 6 9 5 ID Orifice included w Instruction Package 53 61 67 75 78 81 84 87 93 INDOOR COIL COIL ORIFICE1 REQUIRED SYSTEM ORIFICE ADDITIONAL CHARGE OZ G1FA G1...

Page 4: ...S H 21 1225 36 2 27 2 11 20 10 00 E4FD042 N1VSC16 5 7 5 10 15 20 21 G2FD048 S H 21 1425 42 0 31 1 11 00 10 00 E4FD048 N1VSC16 5 7 5 10 15 20 21 G2FD048 S H 21 1600 46 0 34 0 11 00 10 00 N1VSD20 7 5 10...

Page 5: ...50 9 30 17 G2FD036 S H 17 1025 29 4 22 1 11 00 9 40 21 G2FD036 S H 21 1025 29 4 22 1 11 00 9 40 E4FD036S06 1050 1350 21 24 G1FA048S21 1250 35 6 26 7 10 30 9 20 21 24 G1UA048S21 1250 35 6 26 7 10 30 9...

Page 6: ...8 2 1 17 2 23 21 2 2 35 24 8 2 48 29 2 58 34 2 2 68 F2RP F2FP036 28 4 3 20 17 4 2 30 7 50 10 2 1 95 13 6 2 11 17 4 2 22 22 2 37 24 8 2 5 28 4 2 57 34 6 2 69 G2FD030 S H 17 29 2 3 20 17 2 30 7 60 7 8 1...

Page 7: ...6 4 3 25 44 6 3 56 G1FA048S21 35 0 3 2 20 0 2 10 7 4 8 9 1 93 14 7 2 21 20 4 2 49 26 1 2 77 30 0 2 97 37 0 3 29 44 8 3 62 G1UA048S21 35 0 3 2 20 0 2 10 7 4 8 9 1 93 14 7 2 21 20 4 2 49 26 1 2 77 30 0...

Page 8: ...f supplemental electric heat Room Thermostats A wide selection of matching thermo stats is available to provide features required for any installa tion 2H 1C manual change over electronic non programm...

Page 9: ...OR UNIT OUTDOOR UNIT POWER WIRING 208 230 1 60 CONTACTOR GND SCREW T2 T1 L2 L1 M CIRCUIT BREAKER4 POWER WIRING 24V CONTROL WIRING NEC CLASS 2 GND LUG LOW VOLTAGE TERMINAL BLOCK IN AIR HANDLER WITH ELE...

Page 10: ...15 9 14 6 19 5 17 8 16 0 14 8 19 7 17 9 16 1 14 9 S C 13 0 12 9 13 0 13 2 13 4 13 4 13 4 13 6 13 8 13 8 13 8 14 0 K W 1 70 1 68 1 65 1 62 1 72 1 70 1 67 1 64 1 76 1 75 1 72 1 69 105 T C 17 6 15 7 14...

Page 11: ...17 4 17 4 17 5 17 8 K W 2 24 2 18 2 12 2 05 2 26 2 20 2 13 2 06 2 30 2 24 2 17 2 11 105 T C 22 5 20 5 18 4 17 0 22 6 20 6 18 6 17 0 22 7 20 7 18 6 17 1 S C 16 1 16 0 16 0 16 3 16 5 16 4 16 5 16 5 16 9...

Page 12: ...0 22 4 22 7 22 7 22 9 23 2 K W 2 84 2 75 2 65 2 56 2 89 2 80 2 70 2 62 2 93 2 84 2 74 2 67 105 T C 28 9 26 4 23 9 21 9 29 2 26 7 24 5 22 2 29 4 26 9 24 8 22 9 S C 20 4 20 3 20 6 20 8 21 4 21 3 22 0 2...

Page 13: ...3 35 3 25 3 60 3 50 3 40 3 30 3 70 3 60 3 50 3 40 105 T C 33 2 30 6 27 9 25 5 33 4 30 8 28 1 26 0 33 7 31 0 28 4 26 4 S C 24 0 24 0 24 2 24 1 25 0 25 1 25 2 25 3 26 1 26 1 26 3 25 7 K W 3 78 3 68 3 56...

Page 14: ...5 40 5 36 7 33 2 44 6 40 6 37 0 33 6 S C 28 9 28 9 29 2 29 2 30 0 30 0 30 3 30 1 30 8 30 8 31 2 31 1 K W 42 00 4 25 4 08 3 93 4 47 4 31 4 14 3 99 4 55 4 39 4 22 4 08 105 T C 41 3 37 6 34 0 30 8 41 5 3...

Page 15: ...3 33 8 34 0 34 7 34 8 35 4 35 6 36 2 36 2 K W 4 84 4 77 4 71 4 63 4 95 4 88 4 80 4 73 5 18 5 10 5 02 4 95 105 T C 45 8 42 3 38 9 35 7 46 3 42 6 39 3 36 2 46 4 43 0 39 6 37 4 S C 31 2 31 4 32 0 32 1 3...

Page 16: ...5 46 5 36 5 68 5 58 5 48 5 39 5 71 5 59 5 49 5 40 95 T C 62 0 56 9 51 8 47 3 62 6 57 5 52 4 48 0 63 1 58 0 53 0 48 4 S C 41 2 41 4 41 8 42 0 42 9 43 1 43 6 44 0 44 7 44 8 45 5 45 5 K W 6 09 5 98 5 87...

Page 17: ...25 16 8 1 61 3 03 17 5 1 51 3 36 70 13 7 1 50 2 66 15 8 1 66 2 77 15 7 1 56 2 92 80 12 7 2 00 1 84 14 7 1 72 2 50 13 9 1 89 2 14 30 60 14 0 1 52 2 67 14 4 1 53 2 72 14 1 1 40 2 91 70 12 8 1 56 2 37 13...

Page 18: ...7 3 39 70 17 4 1 86 2 73 20 1 2 05 2 84 19 9 1 93 3 00 80 16 5 2 56 1 88 19 2 2 20 2 54 18 1 2 42 2 18 30 60 17 2 1 89 2 63 17 7 1 91 2 68 17 3 1 75 2 86 70 16 1 1 93 2 41 16 8 1 96 2 48 16 9 1 82 2 6...

Page 19: ...3 22 27 6 2 46 3 27 27 8 2 48 3 26 70 25 3 2 51 2 93 26 2 2 55 2 99 26 5 2 57 2 99 80 23 9 2 62 2 65 24 8 2 64 2 73 25 2 2 67 2 74 30 60 23 2 2 30 2 91 24 1 2 32 2 99 24 5 2 35 3 00 70 21 2 2 35 2 61...

Page 20: ...3 7 2 98 3 29 34 5 2 99 3 35 70 31 0 3 09 2 92 31 9 3 10 2 99 32 8 3 12 3 06 80 29 3 3 22 2 65 30 2 3 24 2 71 31 2 3 26 2 78 30 60 27 5 2 80 2 84 28 9 2 84 2 94 29 0 2 86 2 92 70 25 8 2 87 2 60 27 2 2...

Page 21: ...2 3 23 3 37 37 1 3 22 3 38 70 36 0 3 56 2 97 35 6 3 51 2 97 35 6 3 49 2 99 80 35 2 3 91 2 64 34 9 3 85 2 66 35 1 3 82 2 69 30 60 31 6 3 07 3 02 31 6 3 05 3 04 31 6 3 05 3 04 70 30 3 3 38 2 63 29 9 3...

Page 22: ...27 3 35 42 6 3 99 3 13 43 0 3 64 3 47 70 37 0 3 68 2 94 42 6 4 07 3 07 42 2 3 82 3 24 80 36 2 5 36 1 98 42 1 4 62 2 67 39 7 5 06 2 30 30 60 35 8 3 69 2 85 36 8 3 72 2 90 37 7 3 57 3 10 70 34 8 3 83 2...

Page 23: ...2 89 59 7 6 08 2 88 40 60 55 4 4 98 3 24 56 0 5 01 3 27 53 8 4 95 3 17 70 56 0 5 37 3 04 56 0 5 32 3 07 55 5 5 29 3 06 80 55 7 6 00 2 71 55 1 5 86 2 75 56 4 5 84 2 82 30 60 49 7 4 83 3 00 50 1 4 78 3...

Page 24: ...9 MATCHING INDOOR COMPONENTS G1UA 1 2 CASED UPFLOW G1HD HORIZONTAL DUCT G2FD MULTI POSITION UPFLOW HORIZONTAL AND DOWNFLOW Available with factory installed horizontal drain pan ADD ON COILS FOR FURNAC...

Reviews: